background image

FXFQ20~125AVEB
VRV System air conditioners
3P320142-1A – 2012.10

Installation and operation manual

2

Optional accessories

There are two types of remote controllers: wired and wireless.
Select a remote controller according to customers request and
install in an appropriate place.
Refer to catalogues and technical literature for selecting a
suitable remote controller.

This indoor unit requires installation of an optional decoration
panel.

For the following items, take special care during 
construction and check after installation is finished

Notes to the installer

Read this manual carefully to ensure correct installation. Be sure
to instruct the customer how to properly operate the system and
show him/her the enclosed operation manual.

Explain to the customer what system is installed on the site. Be
sure to fill out the appropriate installation specifications in the
chapter "What to do before operation" of the outdoor unit
operation manual.

I

MPORTANT

 

INFORMATION

 

REGARDING

 

THE

 

REFRIGERANT

 

USED

This product contains fluorinated greenhouse gases covered by the
Kyoto Protocol.

Refrigerant type:

R410A

GWP

(1)

 value:

1975

(1)

 GWP = global warming potential

Periodical inspections for refrigerant leaks may be required
depending on European or local legislation. Please contact your local
dealer for more information.

S

ELECTING

 

INSTALLATION

 

SITE

When the conditions in the ceiling are exceeding 30°C and a relative
humidity of 80%, or when fresh air is inducted into the ceiling, an
additional insulation is required (minimum 10 

mm thickness,

polyethylene foam).

For this unit you can select different air flow directions. It is necessary
to purchase an optional blocking pad kit to discharge the air in 3 or
4 (closed corners) directions.

Install the unit so that air vents, lights, or machines near the unit do
not interfere with the air flow.

1

Select an installation site where the following conditions
are fulfilled and that meets your customer's approval.

Where optimum air distribution can be ensured.

Where nothing blocks air passage.

Where condensate water can be properly drained.

Where the false ceiling is not noticeably on an incline.

Where sufficient clearance for maintenance and service can be
ensured.

Where there is no risk of flammable gas leaking.

The equipment is not intended for use in a potentially explosive
atmosphere.

Where piping between indoor and outdoor units is possible within
the allowable limit. (Refer to the installation manual of the outdoor
unit.)

This is a class A product. In a domestic environment this product
may cause radio interference in which case the user may be
required to take adequate measures.

Keep indoor unit, outdoor unit, inter unit wiring and remote
controller at least 1 meter away from televisions and radios. This
is to prevent image interference and noise in those electrical
appliances.
(Noise may be generated depending on the conditions under
which the electric wave is generated, even if 1 meter is kept.)

When installing the wireless remote controller kit, the distance
between wireless remote controller and indoor unit might be
shorter if there are fluorescent lights who are electrically started
in the room. The indoor unit must be installed as far as possible
away from fluorescent lights.

2

Ceiling height

This indoor unit may be installed on ceilings up to 3.5 m in height
(for 125 units: 4.2 m). However, it becomes necessary to make
field settings by the remote controller when installing the unit at
a height over 2.7 m (for 125 units: 3.2 m). Install the unit higher
than 2.5 m to avoid accidental touching.
Refer to 

"Field setting" on page 8

 and to the decoration panel

installation manual.

3

Air flow directions

Select the air flow directions best suited to the room and point of
installation. (For air discharge in 3 directions, it is necessary to
make field settings by means of the remote controller and to
close the air outlet(s). Refer to the installation manual of the
optional blocking pad kit and to 

"Field setting" on page 8

.) (See

figure 1

 (

 = air flow direction))

Tick 

 

when 

checked

Is the indoor unit fixed firmly?

The unit may drop, vibrate or make noise.

Is the gas leak test finished?

It may result in insufficient cooling or heating.

Is the unit fully insulated?

Condensate water may drip.

Does drainage flow smoothly?

Condensate water may drip.

Does the power supply voltage correspond to that shown on the 
name plate?

The unit may malfunction or components may burn out.

Are wiring and piping correct?

The unit may malfunction or components may burn out.

Is the unit safely grounded?

Dangerous at electric leakage.

Is the wiring size according to specifications?

The unit may malfunction or components may burn out.

Is nothing blocking the air outlet or inlet of either the indoor or 
outdoor units?

It may result in insufficient cooling or heating.

Are refrigerant piping length and additional refrigerant charge 
noted down?

The refrigerant charge in the system might not be clear.

a

Indoor unit

b

Lighting
The figure describes about a ceiling lighting, but a recessed 
ceiling light is not restricted.

c

Air fan

A

If the air outlet is closed, space marked (A) should be 500 mm at 
least. In addition, if both the right and left corner of this air outlet 
are closed, space marked (A) should be 200 mm at least.

B

1500 mm from any static volume

1

All round air discharge

2

Air discharge in 4 directions

3

Air discharge in 3 directions

1500 mm

2000 mm

4000 mm

(

A

)

1500 mm

(

B

)

1500 mm

a

c

b

a

Summary of Contents for FXFQ20AVEB

Page 1: ...VRV System air conditioners INSTALLATION AND OPERATION MANUAL FXFQ20AVEB FXFQ25AVEB FXFQ32AVEB FXFQ40AVEB FXFQ50AVEB FXFQ63AVEB FXFQ80AVEB FXFQ100AVEB FXFQ125AVEB System air conditioners...

Page 2: ...4 2 1 950 950 860 910 840 780 860 910 4 125 130 0 3 3 1 1 840 910 840 910 1 1 5 35 35 3 5 0 75 675 850 175 300 mm 1 1 5 m 2 3 1 5 6 100 mm 1 0 675 mm 1 3 3 1 2 4 100 4 3 5 1 2 2 2 1 4 70 90 mm 0 15 m...

Page 3: ...es valorado positivamente por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o pare...

Page 4: ...ms or for commercial use by lay persons Do not install or operate the unit in rooms mentioned below Places with mineral oil or filled with oil vapour or spray like in kitchens Plastic parts may deteri...

Page 5: ...ke adequate measures Keep indoor unit outdoor unit inter unit wiring and remote controller at least 1 meter away from televisions and radios This is to prevent image interference and noise in those el...

Page 6: ...ing ceilings and a sunken insert sunken anchors or other field supplied parts for new ceilings to reinforce the ceiling in order to bear the weight of the unit Adjust clearance from the ceiling before...

Page 7: ...piping Otherwise this can sometimes result in water leakage Before rigging tubes check which type of refrigerant is used Use a pipe cutter and flare suitable for the used refrigerant To prevent dust m...

Page 8: ...ket between drain hose and unit body Wrap the supplied large sealing pad over the metal clamp and drain hose to insulate and fix it with clamps Insulate the complete drain piping inside the building f...

Page 9: ...er supply line A main switch or other means for disconnection having a contact separation in all poles must be incorporated in the fixed wiring in accordance with relevant local and national legislati...

Page 10: ...material field supply thus to prevent small animals or dirt from entering the unit from outside and causing short circuits in the control box 2 Keep total current of crossover wiring between indoor u...

Page 11: ...aning display indications Long life filter Light 2 500 hrs Heavy 1 250 hrs 2 Thermostat sensor selection Use both the unit sensor or remotesensorif installed AND the remote controller sensor See note...

Page 12: ...e obtaining access to terminal devices all power supply circuits must be interrupted To clean the air conditioner be sure to stop operation and turn the power switch off Otherwise an electric shock an...

Page 13: ...ration panel Hold the suction grille open at 45 degrees and lift it upward to unhook it from the decoration panel 3 Remove the air filter actions 2 to 4 in the illustration Refer to procedure step 2 i...

Page 14: ...adaptor for wiring X35A Connector group control adaptor X36A Connector self cleaning decoration panel X38A Connector multi tenant Notes 1 Terminal block Connector Field wiring 2 In case of using a cen...

Page 15: ...IN D OUT D F1 F2 F1 F2 Control box LN P1 P2 P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 1 4 2 3 5 IN D OUT D F1 F2 F1 F2 Control box LN P1 P2 P1 P2 F1...

Page 16: ...3P320142 1A 2012 10 Copyright 2012 Daikin...

Reviews: