
FXFQ20~125AVEB
VRV System air conditioners
3P320142-1A – 2012.10
Installation and operation manual
8
W
IRING
EXAMPLE
Fit the power supply wiring of each unit with a switch and fuse as
shown in
figure 17
.
Complete system example (3 systems)
See figures
13
,
14
and
15
.
When using 1 remote controller for 1 indoor unit. (Normal
operation)
(See figure 13)
.
For group control or use with 2 remote controllers
(See figure 14)
.
When including BS unit
(See figure 15)
.
Precautions
1.
A single switch can be used to supply power to units on the
same system. However, branch switches and branch circuit
breakers must be selected carefully.
2.
For a group control remote controller, choose the remote
controller that suits the indoor unit which has the most functions.
3.
Do not ground the equipment on gas pipes, water pipes,
lightning rods or crossground with telephones. Improper
grounding could result in electric shock.
I
NSTALLATION
OF
THE
DECORATION
PANEL
Refer to the installation manual delivered with the decoration panel.
After installing the decoration panel, ensure that there is no space
between the unit body and decoration panel. Otherwise air may leak
through the gap and cause dewdrop.
F
IELD
SETTING
Field setting must be made from the remote controller in accordance
with the installation condition.
■
Setting can be made by changing the "Mode number", "First
code No." and "Second code No.".
■
For setting and operation, refer to the "Field setting" in the
installation manual of the remote controller.
Summary of field settings
■
When using wireless remote controllers it is necessary to use
address setting. Refer to the installation manual attached to the
wireless remote controller for the setting instructions.
1
Power supply
2
Main switch
3
Power supply wiring
4
Unit transmission wiring
5
Switch
6
Fuse
7
BS unit (REYQ only)
8
Indoor unit
9
Remote controller
1
Outdoor unit
2
Indoor unit
3
Remote controller (Optional accessories)
4
Most downstream indoor unit
5
For use with 2 remote controllers
6
BS unit
NOTE
It is not necessary to designate indoor unit address
when using group control. The address is automatically
set when the power is activated.
Mode
No.
(Note 1)
First
code
No.
Description of setting
Second code No. (Note 2)
01
02
03
04
10
(20)
0
Filter contamination
- Heavy/Light
= Setting to define
time between 2 filter
cleaning display
indications. (When
contamination is
high, setting can be
changed to half the
time inbetween 2
filter cleaning
display indications.)
Long-life
filter
Light ±2,500 hrs.
Hea
vy
±1,250 hrs.
–
–
2
Thermostat sensor selection
Use both the
unit sensor (or
remote sensor if
installed) AND
the remote
controller
sensor.
(See note 5+6)
Use unit sensor
only (or remote
sensor if
installed).
(See note 5+6)
Use remote
controller
sensor only.
(See note 5+6)
—
3
Setting for display of time
between 2 filter cleaning display
indications
Display
Do not display
—
—
5
Information to I-manager,
I-touch controller
Only unit sensor
value (or remote
sensor value if
installed).
Sensor value as
set by 10-2-0X
or 10-6-0X.
—
—
6
Thermostat sensor in group
control
Use unit sensor
only (or remote
sensor if
installed).
(See note 6)
Use both the
unit senor (or
remote sensor if
installed) AND
the remote
controller
sensor. (See
note 4+5+6)
—
—
12
(22)
0
Output signal X1-X2 of the
optional KRP1B PCB kit
Thermostat-on
+ compressor
run
—
Operation
Mal-
function
1
ON/OFF input from outside
(T1/T2 input) = Setting when
forced ON/OFF is to be
operated from outside.
Forced OFF
ON/OFF
operation
—
—
2
Thermostat differential
changeover = Setting when
remote sensor is used.
1°C
0.5°C
—
—
3
Fan setting during thermostat
OFF at heating operation
LL
Set speed
OFF
(See note 3)
—
4
Differential automatic
changeover
0°C
1°C
2°C
3°C
(See
note 7)
5
Auto-restart after power failure
Disabled
Enabled
—
—
13
(23)
0
Setting for air outlet
velocity
This setting is to be
changed in function
of ceiling height.
other
models
≤
2.7 m
>2.7
≤
3.0 m
>3.0
≤
3.5 m
—
FXFQ125
only
≤
3.2 m
>3.2
≤
3.6 m
>3.6
≤
4.2 m
—
1
Selection for air flow direction
This setting is to be changed
when blocking pad optional kit
is used.
4-way flow
3-way flow
—
—
4
Airflow direction range setting
This setting is to be changed
when range of swing flap
movement needs to be
changed.
Upper
Medium
Lower
—
Note 1 :
Setting is carried out in the group mode, however, if the mode number inside parentheses is selected,
indoor units can also be set individually.
Note 2 :
Factory settings of the Second code No. are marked in grey backgrounds.
Note 3 :
Only use in combination with optional remote sensor or when setting 10-2-03 is used.
Note 4 :
If group control is selected and remocon sensor is to be used, then set 10-6-02 & 10-2-03.
Note 5 :
If setting 10-6-02 + 10-2-01 or 10-2-02 or 10-2-03 are set at the same time, then setting 10-2-01,
10-2-02 or 10-2-03 have priority.
Note 6 :
If setting 10-6-01 + 10-2-01 or 10-2-02 or 10-2-03 are set at the same time, then setting for group
connection, 10-6-01 has priority and for individual connection, 10-2-01, 10-2-02 or 10-2-03 have
priority.
Note 7 :
More settings for Differential automatic change over temperatures are:
Second code No.
05
4°C
06
5°C
07
6°C
08
7°C