background image

FXFQ20~125AVEB
VRV System air conditioners
3P320142-1A – 2012.10

Installation and operation manual

8

W

IRING

 

EXAMPLE

Fit the power supply wiring of each unit with a switch and fuse as
shown in 

figure 17

.

Complete system example (3 systems)

See figures 

13

14

 and 

15

.

When using 1 remote controller for 1 indoor unit. (Normal
operation) 

(See figure 13)

.

For group control or use with 2 remote controllers 

(See figure 14)

.

When including BS unit 

(See figure 15)

.

Precautions

1.

A single switch can be used to supply power to units on the
same system. However, branch switches and branch circuit
breakers must be selected carefully.

2.

For a group control remote controller, choose the remote
controller that suits the indoor unit which has the most functions.

3.

Do not ground the equipment on gas pipes, water pipes,
lightning rods or crossground with telephones. Improper
grounding could result in electric shock.

I

NSTALLATION

 

OF

 

THE

 

DECORATION

 

PANEL

Refer to the installation manual delivered with the decoration panel.

After installing the decoration panel, ensure that there is no space
between the unit body and decoration panel. Otherwise air may leak
through the gap and cause dewdrop.

F

IELD

 

SETTING

Field setting must be made from the remote controller in accordance
with the installation condition.

Setting can be made by changing the "Mode number", "First
code No." and "Second code No.".

For setting and operation, refer to the "Field setting" in the
installation manual of the remote controller.

Summary of field settings

When using wireless remote controllers it is necessary to use
address setting. Refer to the installation manual attached to the
wireless remote controller for the setting instructions.

1

Power supply

2

Main switch

3

Power supply wiring

4

Unit transmission wiring

5

Switch

6

Fuse

7

BS unit (REYQ only)

8

Indoor unit

9

Remote controller

1

Outdoor unit

2

Indoor unit

3

Remote controller (Optional accessories)

4

Most downstream indoor unit

5

For use with 2 remote controllers

6

BS unit

NOTE

It is not necessary to designate indoor unit address
when using group control. The address is automatically
set when the power is activated.

Mode 

No.

(Note 1)

First 

code 

No.

Description of setting

Second code No. (Note 2)

01

02

03

04

10 

(20)

0

Filter contamination 
- Heavy/Light

= Setting to define 

time between 2 filter 

cleaning display 

indications. (When 

contamination is 

high, setting can be 

changed to half the 

time inbetween 2 

filter cleaning 

display indications.)

Long-life 
filter

Light ±2,500 hrs.

Hea

vy

±1,250 hrs.

2

Thermostat sensor selection

Use both the 
unit sensor (or 
remote sensor if 
installed) AND 
the remote 
controller 
sensor. 
(See note 5+6)

Use unit sensor 
only (or remote 
sensor if 
installed). 
(See note 5+6)

Use remote 
controller 
sensor only.
(See note 5+6)

3

Setting for display of time 
between 2 filter cleaning display 
indications

Display

Do not display

5

Information to I-manager, 
I-touch controller

Only unit sensor 
value (or remote 
sensor value if 
installed).

Sensor value as 
set by 10-2-0X 
or 10-6-0X.

6

Thermostat sensor in group 
control

Use unit sensor 
only (or remote 
sensor if 
installed). 
(See note 6)

Use both the 
unit senor (or 
remote sensor if 
installed) AND 
the remote 
controller 
sensor. (See 
note 4+5+6)

12 

(22)

0

Output signal X1-X2 of the 
optional KRP1B PCB kit

Thermostat-on 
+ compressor 
run

Operation

Mal-
function

1

ON/OFF input from outside 
(T1/T2 input) = Setting when 
forced ON/OFF is to be 
operated from outside.

Forced OFF

ON/OFF
operation

2

Thermostat differential 
changeover = Setting when 
remote sensor is used.

1°C

0.5°C

3

Fan setting during thermostat 
OFF at heating operation

LL

Set speed

OFF 
(See note 3)

4

Differential automatic 
changeover

0°C

1°C

2°C

3°C
(See 
note 7)

5

Auto-restart after power failure

Disabled

Enabled

13 

(23)

0

Setting for air outlet 
velocity 
This setting is to be 
changed in function 
of ceiling height.

other 
models

2.7 m

>2.7 

3.0 m

>3.0 

3.5 m

FXFQ125 
only

3.2 m

>3.2 

3.6 m

>3.6 

4.2 m

1

Selection for air flow direction
This setting is to be changed 
when blocking pad optional kit 
is used.

4-way flow

3-way flow

4

Airflow direction range setting
This setting is to be changed 
when range of swing flap 
movement needs to be 
changed.

Upper

Medium

Lower

Note 1 :

Setting is carried out in the group mode, however, if the mode number inside parentheses is selected, 
indoor units can also be set individually.

Note 2 :

Factory settings of the Second code No. are marked in grey backgrounds.

Note 3 :

Only use in combination with optional remote sensor or when setting 10-2-03 is used.

Note 4 :

If group control is selected and remocon sensor is to be used, then set 10-6-02 & 10-2-03.

Note 5 :

If setting 10-6-02 + 10-2-01 or 10-2-02 or 10-2-03 are set at the same time, then setting 10-2-01, 
10-2-02 or 10-2-03 have priority.

Note 6 :

If setting 10-6-01 + 10-2-01 or 10-2-02 or 10-2-03 are set at the same time, then setting for group 
connection, 10-6-01 has priority and for individual connection, 10-2-01, 10-2-02 or 10-2-03 have 
priority.

Note 7 :

More settings for Differential automatic change over temperatures are:
Second code No.

05

4°C

06

5°C

07

6°C

08

7°C

Summary of Contents for FXFQ20AVEB

Page 1: ...VRV System air conditioners INSTALLATION AND OPERATION MANUAL FXFQ20AVEB FXFQ25AVEB FXFQ32AVEB FXFQ40AVEB FXFQ50AVEB FXFQ63AVEB FXFQ80AVEB FXFQ100AVEB FXFQ125AVEB System air conditioners...

Page 2: ...4 2 1 950 950 860 910 840 780 860 910 4 125 130 0 3 3 1 1 840 910 840 910 1 1 5 35 35 3 5 0 75 675 850 175 300 mm 1 1 5 m 2 3 1 5 6 100 mm 1 0 675 mm 1 3 3 1 2 4 100 4 3 5 1 2 2 2 1 4 70 90 mm 0 15 m...

Page 3: ...es valorado positivamente por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o pare...

Page 4: ...ms or for commercial use by lay persons Do not install or operate the unit in rooms mentioned below Places with mineral oil or filled with oil vapour or spray like in kitchens Plastic parts may deteri...

Page 5: ...ke adequate measures Keep indoor unit outdoor unit inter unit wiring and remote controller at least 1 meter away from televisions and radios This is to prevent image interference and noise in those el...

Page 6: ...ing ceilings and a sunken insert sunken anchors or other field supplied parts for new ceilings to reinforce the ceiling in order to bear the weight of the unit Adjust clearance from the ceiling before...

Page 7: ...piping Otherwise this can sometimes result in water leakage Before rigging tubes check which type of refrigerant is used Use a pipe cutter and flare suitable for the used refrigerant To prevent dust m...

Page 8: ...ket between drain hose and unit body Wrap the supplied large sealing pad over the metal clamp and drain hose to insulate and fix it with clamps Insulate the complete drain piping inside the building f...

Page 9: ...er supply line A main switch or other means for disconnection having a contact separation in all poles must be incorporated in the fixed wiring in accordance with relevant local and national legislati...

Page 10: ...material field supply thus to prevent small animals or dirt from entering the unit from outside and causing short circuits in the control box 2 Keep total current of crossover wiring between indoor u...

Page 11: ...aning display indications Long life filter Light 2 500 hrs Heavy 1 250 hrs 2 Thermostat sensor selection Use both the unit sensor or remotesensorif installed AND the remote controller sensor See note...

Page 12: ...e obtaining access to terminal devices all power supply circuits must be interrupted To clean the air conditioner be sure to stop operation and turn the power switch off Otherwise an electric shock an...

Page 13: ...ration panel Hold the suction grille open at 45 degrees and lift it upward to unhook it from the decoration panel 3 Remove the air filter actions 2 to 4 in the illustration Refer to procedure step 2 i...

Page 14: ...adaptor for wiring X35A Connector group control adaptor X36A Connector self cleaning decoration panel X38A Connector multi tenant Notes 1 Terminal block Connector Field wiring 2 In case of using a cen...

Page 15: ...IN D OUT D F1 F2 F1 F2 Control box LN P1 P2 P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 1 4 2 3 5 IN D OUT D F1 F2 F1 F2 Control box LN P1 P2 P1 P2 F1...

Page 16: ...3P320142 1A 2012 10 Copyright 2012 Daikin...

Reviews: