background image

 

Installation and operation manual

9

FXFQ20~125AVEB

VRV System air conditioners

3P320142-1A – 2012.10

Control by 2 Remote Controllers (Controlling 1 indoor 
unit by 2 remote controllers)

When using 2 remote controllers, one must be set to "MAIN" and the
other to "SUB".

Main/sub changeover

1.

Insert a wedge-head screwdriver into the recess between the
upper and lower part of the remote controller and, working from
the 2 positions, pry off the upper part. 

(See figure 19)

(The remote controller PC board is attached to the upper part of
the remote controller.)

2.

Turn the main/sub changeover switch on one of the two remote
controller PC boards to "S". 

(See figure 20)

(Leave the switch of the other remote controller set to "M".)

Computerised control (forced off and on/off operation)

1.

Wire specifications and how to perform wiring.

Connect input from outside to terminals T1 and T2 of the terminal
block (remote controller to transmission wiring).

See 

figure 18

.

2.

Actuation

The following table explains "forced off" and "on/off operations" in
response to input A.

3.

How to select forced off and on/off operation

Turn the power on and then use the remote controller to select
operation.

Set the remote controller to the field set mode. For details, refer
to the chapter "How to set in the field", in the remote controller
manual.

When in the field set mode, select mode No. 12, then set the first
code (switch) No. to "1". Then set second code (position) No. to
"01" for forced off and to "02" for on/off operation. (forced off at
factory set.) 

(See figure 16)

Centralized control

For centralized control, it is necessary to designate the group No. For
details, refer to the manual of each optional controller for centralized
control.

T

EST

 

OPERATION

Refer to the installation manual of the outdoor unit.

The operation lamp of the remote controller will flash when an error
occurs. Check the error code on the liquid crystal display to identify
the trouble. Refer to the installation manual attached to the outdoor
unit or contact your dealer. See 

figure 22

.

M

AINTENANCE

Only a qualified service person is allowed to perform
maintenance.

Before obtaining access to terminal devices, all power supply
circuits must be interrupted.

To clean the air conditioner, be sure to stop operation and turn
the power switch off.
Otherwise, an electric shock and injury may result.

Do not wash the air conditioner with water.
Doing so may result in an electric shock.

Be careful with scaffoldings.
Caution must be exercised when working in high places.

After a long use, check the unit stand and fitting for damage. If
damaged, the unit may fall and cause injury.

Do not touch the heat exchanger fins.
The fins are sharp and could result in cutting injuries.

When cleaning the heat exchanger, be sure to remove the
control box, fan motor, drain pump and float switch. Water or
detergent may deteriorate the insulation of electronic
components and result in burn-out of these components.

How to clean the air filter

Clean the air filter when the display shows "

" (TIME TO CLEAN

AIR FILTER).

Increase the frequency of cleaning if the unit is installed in a room
where the air is extremely contaminated.

(As a yardstick for yourself, consider cleaning the filter once a half
year.)

If dirt becomes impossible to clean, change the air filter. (Air filter for
exchange is optional.)

1

Remote controller PC board

2

Factory setting

3

Only one remote controller needs to be changed

Wire specification

Sheathed vinyl cord or cable (2 wire)

Gauge

0.75-1.25 mm

2

Length

Max. 100 m

External terminal

Contact that can ensure the minimum applicable load 

of 15 V DC, 1 mA

1

Input A

Forced off

on/off operation

Input "on" stops operation

input off 

 on: turns on the unit 

(impossible by remote controllers)

Input "off" enables control

input on 

 off: turns off the unit 

(by remote controller)

1

Second code No.

2

Mode No.

3

First code No.

4

Field set mode

NOTE

When performing field settings or test operation
without attaching the decoration panel, do not touch
the drain pump. This may cause electric shock.

1

Drain pumping device (built-in) drain water is removed from the 
room during cooling

2

Air flow flap (at air outlet)

3

Air outlet

4

Remote controller

5

Suction grille

6

Air filter (inside suction grille)

CAUTION

NOTE

Do not wash the air filter with hot water of more than
50°C. Doing so may result in discoloration and/or
deformation.

Do not expose the unit to fire. Doing so may result in
burning.

Summary of Contents for FXFQ20AVEB

Page 1: ...VRV System air conditioners INSTALLATION AND OPERATION MANUAL FXFQ20AVEB FXFQ25AVEB FXFQ32AVEB FXFQ40AVEB FXFQ50AVEB FXFQ63AVEB FXFQ80AVEB FXFQ100AVEB FXFQ125AVEB System air conditioners...

Page 2: ...4 2 1 950 950 860 910 840 780 860 910 4 125 130 0 3 3 1 1 840 910 840 910 1 1 5 35 35 3 5 0 75 675 850 175 300 mm 1 1 5 m 2 3 1 5 6 100 mm 1 0 675 mm 1 3 3 1 2 4 100 4 3 5 1 2 2 2 1 4 70 90 mm 0 15 m...

Page 3: ...es valorado positivamente por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o pare...

Page 4: ...ms or for commercial use by lay persons Do not install or operate the unit in rooms mentioned below Places with mineral oil or filled with oil vapour or spray like in kitchens Plastic parts may deteri...

Page 5: ...ke adequate measures Keep indoor unit outdoor unit inter unit wiring and remote controller at least 1 meter away from televisions and radios This is to prevent image interference and noise in those el...

Page 6: ...ing ceilings and a sunken insert sunken anchors or other field supplied parts for new ceilings to reinforce the ceiling in order to bear the weight of the unit Adjust clearance from the ceiling before...

Page 7: ...piping Otherwise this can sometimes result in water leakage Before rigging tubes check which type of refrigerant is used Use a pipe cutter and flare suitable for the used refrigerant To prevent dust m...

Page 8: ...ket between drain hose and unit body Wrap the supplied large sealing pad over the metal clamp and drain hose to insulate and fix it with clamps Insulate the complete drain piping inside the building f...

Page 9: ...er supply line A main switch or other means for disconnection having a contact separation in all poles must be incorporated in the fixed wiring in accordance with relevant local and national legislati...

Page 10: ...material field supply thus to prevent small animals or dirt from entering the unit from outside and causing short circuits in the control box 2 Keep total current of crossover wiring between indoor u...

Page 11: ...aning display indications Long life filter Light 2 500 hrs Heavy 1 250 hrs 2 Thermostat sensor selection Use both the unit sensor or remotesensorif installed AND the remote controller sensor See note...

Page 12: ...e obtaining access to terminal devices all power supply circuits must be interrupted To clean the air conditioner be sure to stop operation and turn the power switch off Otherwise an electric shock an...

Page 13: ...ration panel Hold the suction grille open at 45 degrees and lift it upward to unhook it from the decoration panel 3 Remove the air filter actions 2 to 4 in the illustration Refer to procedure step 2 i...

Page 14: ...adaptor for wiring X35A Connector group control adaptor X36A Connector self cleaning decoration panel X38A Connector multi tenant Notes 1 Terminal block Connector Field wiring 2 In case of using a cen...

Page 15: ...IN D OUT D F1 F2 F1 F2 Control box LN P1 P2 P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 1 4 2 3 5 IN D OUT D F1 F2 F1 F2 Control box LN P1 P2 P1 P2 F1...

Page 16: ...3P320142 1A 2012 10 Copyright 2012 Daikin...

Reviews: