FXFQ20~125AVEB
VRV System air conditioners
3P320142-1A – 2012.10

Installation and operation manual

6

How to perform piping 

(See figure 7)

1

Connect the drain hose to the drain raising pipes, and insulate
them.

2

Connect the drain hose to the drain outlet on the indoor unit, and
tighten it with the clamp.

Precautions
-

Install the drain raising pipes at a height of less than 675 mm.

-

Install the drain raising pipes at a right angle to the indoor 
unit and no more than 300 mm from the unit.

-

To prevent air bubbles, install the drain hose level or slightly 
tilted up (

75 mm).

Testing of drain piping

After piping work is finished, check if drainage flows smoothly.

Add approximately 1 

l of water gradually through the air

discharge outlet.
Method of adding water. See 

figure 11

.

Check the drainage flow.

In case electric wiring work is finished

Check drainage flow during COOL running, explained in 

"Test

operation" on page 9

.

In case electric wiring work is not finished

-

Remove the control box lid. Connect the power supply
firmly to the terminal. See 

figure 10

.

-

Reattach the control box lid and turn on the power.

-

Do not touch the drain pump. It may result in electric
shock.

-

Confirm the drain operation looking at the drain socket.

-

After checking the drainage flow, turn off the power,
remove the control box lid and disconnect the power
supply from the terminal again.

-

Reattach the control box lid.

E

LECTRIC

 

WIRING

 

WORK

General instructions

All field supplied parts and materials and electric works must
conform to local codes.

Use copper wire only.

Follow the "Wiring diagram" attached to the unit body to wire the
outdoor unit, indoor units and the remote controller. For details
on hooking up the remote controller, refer to the "Installation
manual of the remote controller".

All wiring must be performed by an authorized electrician.

Attach the earth leakage circuit breaker and fuse to the power
supply line.

A main switch or other means for disconnection, having a
contact separation in all poles, must be incorporated in the fixed
wiring in accordance with relevant local and national legislation.
Note that the operation will restart automatically if the main
power supply is turned off and then turned back on again.

This system consists of multiple indoor units. Mark each indoor
unit as unit A, unit B..., and be sure the terminal block wiring to
the outdoor unit and BS unit are properly matched. If wiring and
piping between the outdoor unit and an indoor unit are
mismatched, the system may cause a malfunction.

Be sure to ground the air conditioner.

Do not connect the ground wire to:
-

gas pipes: might cause explosions or fire if gas leaks.

-

telephone ground wires or lightning rods: might cause 
abnormally high electric potential in the ground during 
lightning storms.

-

plumbing pipes: no grounding effect if hard vinyl piping is 
used.

1

Ceiling slab

2

Hanger bracket

3

Adjustable range

4

Drain raising pipe (nominal diameter of vinyl pipe = 25 mm)

5

Drain hose (supplied with the unit)

6

Clamp metal (supplied with the unit)

NOTE

The incline of attached drain hose should be
75 mm or less so that the drain socket does
not have to withstand additional force.

To ensure a downward slope of 1:100, install
hanging bars every 1 to 1.5 m.

When unifying multiple drain pipes, install the
pipes as shown in 

figure 9

. Select converging

drain pipes whose gauge is suitable for the
operating capacity of the unit. 

1

T-joint converging drain pipes

1

Plastic watering can (tube should be about 100 mm long)

2

Service drain outlet (with rubber plug) (Use this outlet to 
drain water from the drain pan)

3

Drain pump location

4

Drain pipe

5

Drain socket (water flow view point)

1

Control box lid

2

Power supply wiring

3

Power supply terminal block

4

Clamp (field supply)

5

Unit transmission wiring

6

Terminal block for transmission wiring

7

Opening for cables

8

Wiring diagram label
(on the back side of the control box lid)

9

Earth cable

10

Remote controller wiring

Power supply terminal block (3)

L

N

Summary of Contents for FXFQ20AVEB

Page 1: ...VRV System air conditioners INSTALLATION AND OPERATION MANUAL FXFQ20AVEB FXFQ25AVEB FXFQ32AVEB FXFQ40AVEB FXFQ50AVEB FXFQ63AVEB FXFQ80AVEB FXFQ100AVEB FXFQ125AVEB System air conditioners...

Page 2: ...4 2 1 950 950 860 910 840 780 860 910 4 125 130 0 3 3 1 1 840 910 840 910 1 1 5 35 35 3 5 0 75 675 850 175 300 mm 1 1 5 m 2 3 1 5 6 100 mm 1 0 675 mm 1 3 3 1 2 4 100 4 3 5 1 2 2 2 1 4 70 90 mm 0 15 m...

Page 3: ...es valorado positivamente por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o pare...

Page 4: ...ms or for commercial use by lay persons Do not install or operate the unit in rooms mentioned below Places with mineral oil or filled with oil vapour or spray like in kitchens Plastic parts may deteri...

Page 5: ...ke adequate measures Keep indoor unit outdoor unit inter unit wiring and remote controller at least 1 meter away from televisions and radios This is to prevent image interference and noise in those el...

Page 6: ...ing ceilings and a sunken insert sunken anchors or other field supplied parts for new ceilings to reinforce the ceiling in order to bear the weight of the unit Adjust clearance from the ceiling before...

Page 7: ...piping Otherwise this can sometimes result in water leakage Before rigging tubes check which type of refrigerant is used Use a pipe cutter and flare suitable for the used refrigerant To prevent dust m...

Page 8: ...ket between drain hose and unit body Wrap the supplied large sealing pad over the metal clamp and drain hose to insulate and fix it with clamps Insulate the complete drain piping inside the building f...

Page 9: ...er supply line A main switch or other means for disconnection having a contact separation in all poles must be incorporated in the fixed wiring in accordance with relevant local and national legislati...

Page 10: ...material field supply thus to prevent small animals or dirt from entering the unit from outside and causing short circuits in the control box 2 Keep total current of crossover wiring between indoor u...

Page 11: ...aning display indications Long life filter Light 2 500 hrs Heavy 1 250 hrs 2 Thermostat sensor selection Use both the unit sensor or remotesensorif installed AND the remote controller sensor See note...

Page 12: ...e obtaining access to terminal devices all power supply circuits must be interrupted To clean the air conditioner be sure to stop operation and turn the power switch off Otherwise an electric shock an...

Page 13: ...ration panel Hold the suction grille open at 45 degrees and lift it upward to unhook it from the decoration panel 3 Remove the air filter actions 2 to 4 in the illustration Refer to procedure step 2 i...

Page 14: ...adaptor for wiring X35A Connector group control adaptor X36A Connector self cleaning decoration panel X38A Connector multi tenant Notes 1 Terminal block Connector Field wiring 2 In case of using a cen...

Page 15: ...IN D OUT D F1 F2 F1 F2 Control box LN P1 P2 P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 1 4 2 3 5 IN D OUT D F1 F2 F1 F2 Control box LN P1 P2 P1 P2 F1...

Page 16: ...3P320142 1A 2012 10 Copyright 2012 Daikin...

Reviews: