To keep the drain piping from sagging, space hanging 
bracket every 1 to 1.5 m.

Use the drain hose (2) and the metal clamp (1). Insert the 
drain hose (2) fully into the drain pipe connection hole and 
firmly tighten the metal clamp (1) with the upper part of the 
tape on the hose end. Tighten the metal clamp (1) until the 
screw head is less than 4 mm from the hose. 

(Refer to Fig. 11, 12)

The two areas below should be insulated because conden-
sation may form there causing water to leak.

Drain piping passing indoors

Drain pipe connection hole

Referring the figure below, insulate the metal clamp (1) and 
drain hose (2) using the included large sealing pad (5).

(Refer to Fig. 12)

〈 〈 〈 〈 

PRECAUTIONS FOR DRAIN RAISING PIPE 

〉〉〉〉

Make sure the drain raising pipe height is no higher than 
600mm.

Place the drain raising pipe vertically and make sure it is no 
further than 300mm from the unit.

 (Refer to Fig. 13)

〈 〈 〈 〈 

PRECAUTIONS 

〉〉〉〉

Drain piping connections

Do not connect the drain piping directly to sewage pipes that 
smell of ammonia. The ammonia in the sewage might enter 
the indoor unit through the drain piping and corrode the heat 
exchanger.

Do not twist or bend the drain hose (2), so that excessive 
force is not applied to it. 
(This type of treatment may cause leaking.)

If you are using central drain piping, follow the procedure 
outlined in the figure 10.

Select central drain piping of proper size according to the 
capacity of the connected unit.

(2) After piping work is finished, check drainage flows 

smoothly.

Gradually insert approximately 1L of water into the drain 
pan to check drainage in the manner described below.

Metal clamp (1)

Drain hose (2)

Tape

Fig. 11

(accessory)

(accessory)

Fig. 12

4mm

Large sealing 
pad (5)

Metal clamp (1)

(accessory)

(accessory)

Drain raising pipe

Metal clamp (1) (accessory)

Drain hose (2) (accessory)

Ceiling slab

300 mm or less

Hanging bracket

Adjustable range
(600mm or less)

(Field supply)

1 – 1.5m

Fig. 13

CAUTION

The electric wiring work shall be performed by qualified 
electricians.

If workers not having the electrician qualification have 
performed the electric wiring work, the steps 3 to 7 shall 
be performed after the 

TEST RUN

.

1.

Remove the lid of the control box.  Connect the remote 
controller and power supply (single-phase, 50 Hz 
220-240 V or single-phase, 60Hz 220V) respectively to 
the terminal block and securely connect the earth 
also.(as shown in the figure below).

CAUTION

Securely clamp the cables with the clamps (9)(10) 

offered as accessories as shown in Fig. 14 so that ten-

sion will not be applied on the cable connection areas.

2.

Confirm that the lid of the control box is closed before 
turning on the power.

3.

Remove the inspection lid.

4.

Gradually pour approximately 1L of water from the 
inspection window into the drain pan to check drainage.

CAUTION

Be sure to prevent an external force from being 

exerted on the float switch. 

(This may cause breakage.)

5.

Attach the inspection lid.

6.

Perform the following operation using the remote control-
ler, and check drainage.

Select the inspection/test operation button “

” 

using the remote controller.  The unit will engage the 
test operation. Press the operation selector button 

”, and select FAN OPERATION “

”.

Press the ON/OFF button “

”.  (The indoor fan and 

drain pump will operate.)

CAUTION

The fan will turn also at the same time.  Take due care.

7.

Make sure to use the remote controller in finishing the 
operation.

TEST

TRANSMISSION

WIRING

REMOTE

CNTRL

T1

F1

FORCED

OFF

P2

F2

P1

T2

TRANSMISSION

WIRING

REMOTE

CNTRL

T1

F1

FORCED

OFF

P2

F2

P1

T2

L

N

N

L

L

N

Inspection window

Portable pump

Inspection lid

Refrigerant pipes

Bucket

Service drain hole

Drain outlet

(with rubber cap)

Indoor PCboard 

(ASSY)

Terminal block

Terminal block

Remote controller 
terminal connection 
method

Power supply: 
Single phase, 
50 Hz, 220 V~
240V
Single phase,
60Hz, 220 V
Power terminal 
connection 
method

01_EN_3PN06588-2C.fm  Page 7  Tuesday, November 29, 2005  2:25 PM

Summary of Contents for FXDQ20NAVE

Page 1: ...IONE LEGGERE ATTENTAMENTE QUESTE ISTRUZIONI TENERE QUESTO MANUALE A PORTATA DI MANO PER RIFERIMENTI FUTURI LEES DEZE INSTRUCTIES ZORGVULDIG DOOR VOOR INSTALLATIE BEWAAR DEZE HAN DLEINDING WAAR U HEM K...

Page 2: ...0NAVE FXDQ50NAVE FXDQ63NAVE FXDQ20NVET FXDQ25NVET FXDQ32NVET FXDQ40NVET FXDQ50NVET FXDQ63NVET FXD20MVE FXD25MVE FXD32MVE FXD40MVE FXD50MVE FXD63MVE FXD20MVET FXD25MVET FXD32MVET FXD40MVET FXD50MVET FX...

Page 3: ...oper electrical construction may lead to electric shocks or fire Make sure that all wiring is secured the specified wires are used and no external forces act on the terminal connections or wires Impro...

Page 4: ...customers how to properly operate the unit operating different functions and adjusting the temper ature by having them carry out operations themselves while looking at the operation manual Do not inst...

Page 5: ...e of 1 m may not be sufficient enough to eliminate the noise If installing the wireless kit in a room with electronic fluo rescent lighting inverter or rapid start type the remote controller s transmi...

Page 6: ...nken insert sunken anchor or other part to be procured in the field to reinforce the ceiling to bearing the weight of the unit for new ceiling Refer to Fig 3 5 For bottom intake replace the chamber li...

Page 7: ...ign matter from infil trating the piping either pinch the end or cover it with tape Do not allow anything other than the designated refrigerant to get mixed into the refrigerant circuit such as air et...

Page 8: ...is finished make sure to check that there is no gas leak When you keep on tightening the flare nut with a spanner there is a point where the tightening torque suddenly increases From that position fur...

Page 9: ...djustable range 600mm or less Field supply 1 1 5m Fig 13 CAUTION The electric wiring work shall be performed by qualified electricians If workers not having the electrician qualification have performe...

Page 10: ...e earth wire should come in contact with gas pipes water pipes lightning rods or telephone earth wires Gas pipes gas leaks can cause explosions and fire Water pipes they cannot be grounded if hard vin...

Page 11: ...e and connect to the terminal block 3P Remote controller and transmission wiring Pull the wires into the unit through the wiring through hole and connect to the terminal block 6P Power supply wiring E...

Page 12: ...ase 50Hz 220 240V or single phase 60Hz 220V Power supply single phase 50Hz 220 240V or single phase 60Hz 220V Outdoor unit F T 1 L 1 1 1 P P 2 P N 1 2 P T F 2 F P F 1 2 2 2 P 1 N 2 P2 F IN D 1 OUT D 1...

Page 13: ...RUN Field settings may have to be performed using the remote controller depending on the type of installa tion 1 Make sure the control box lids are closed on the indoor and outdoor units 2 Depending...

Page 14: ...the point of trouble An explanation of malfunction codes and the correspond ing trouble is provided in CAUTION FOR SERVICING of the outdoor unit If the display shows any of the following there is a po...

Page 15: ...3PN06588 2C EM03A119D 0512 HT 00_CV_3PN06588 2C fm Page 2 Thursday November 17 2005 7 04 PM...

Reviews: