background image

6

English

(3) After checking for gas leaks, be sure to insulate the 

pipe connections referring to Fig. 8.

Insulate using the insulation for fitting (3) (4) included with 
the liquid and gas pipes. Besides, make sure the insula-
tion for fitting (3) (4) on the liquid and gas piping has its 
seams facing up.
(Tighten both edges with clamp (9).)

For the gas piping, wrap the mid. sealing pad (6) over the 
insulation for fitting (4) (flare nut part).

CAUTION

Be sure to insulate any field piping all the way to the piping 

connection inside the unit. Any exposed piping may cause 

condensation or burns if touched.

When brazing the refrigerant piping, perform nitrogen 
replacement first, or perform the brazing (CAUTION 2) while 
feeding nitrogen into the refrigerant piping (CAUTION 1), and 
finally connect the indoor unit using the flare connections. 

(Refer to  Fig. 9)

CAUTION

1. When brazing a pipe while feeding nitrogen inside the 

pipe, make sure to set the nitrogen pressure to 0.02 MPa  
using the pressure reducing valve.  
(This pressure is such that breeze is blown to your cheek.)

2. Do not use a flux when brazing the refrigerant pipe joints.  

Use phosphor copper brazer (BCuP-2: JIS Z 3264/B-Cu93P-
710/795: ISO 3677) which does not require flux.  (Using a flux 
containing chlorine may cause the piping to corrode.  Using a 
welding flux containing fluorine may cause the refrigerant lubri-
cant to deteriorate, and affect adversely the refrigerant piping 
system.)

Not recommendable but in case of emergency

You must use a torque wrench but if you are obliged to install the 
unit without a torque wrench, you may follow the installation 
method mentioned below.

After the work is finished, make sure to check that there is 
no gas leak.

When you keep on tightening the flare nut with a spanner, there 
is a point where the tightening torque  suddenly increases. From 
that position, further tighten the flare nut the angle shown below:
Table 2

7. DRAIN PIPING WORK

(1) Install the drain piping.

Make sure the drain works properly.

The diameter of the drain piping should be greater than or 
equal to the diameter of the connecting pipe (vinyl tube; pipe 
size: 20 mm; outer dimension: 26 mm). 
(not including the riser)

Keep the drain piping short and sloping downwards at a gra-
dient of at least 1/100 to prevent air pockets from forming.

(Refer to Fig. 10)

CAUTION

Water accumulating in the drain piping can cause the 
drain to clog.

Gas pipe

Piping insulation 

material (main unit)

Attach to base

Flare nut connection

Turn seams up

Mid. sealing pad (6)

Insulation for fitting (4)

Gas Piping Insulation Procedure

Liquid Piping Insulation Procedure

(accessory)

Clamp (9)

Piping insulation material

(Field supply)

Clamp (9) (accessory)

Flare nut connection

Turn seams up

Piping insulation material

(Field supply)

Piping insulation material 

(main unit)

Attach to base

Main unit

Fig. 8

Liquid pipe

Insulation for fitting (3)

(accessory)

(accessory)

(accessory)

Wrap over the top of 

the flare nut connection.

Main unit

Refrigerant piping

Part to be brazed

Taping

Pressure-reducing valve

hands 

valve

Nitrogen

Nitrogen

Fig. 9

Pipe size

Further tightening angle

Recommended arm 
length of tool

φ 

6.4 (1/4”)

60 to 90 degrees

Approx. 150mm

φ 

9.5 (3/8”)

60 to 90 degrees

Approx. 200mm

φ 

12.7 (1/2”)

30 to 60 degrees

Approx. 250mm

φ 

15.9 (5/8”)

30 to 60 degrees

Approx. 300mm

Drain pipe connection hole

Refrigerant pipes

Service drain hole
(with rubber cap)

100mm or

more

Central drain piping 

(with a slope of at least 1/100)

Fig. 10

01_EN_3PN06588-2C.fm  Page 6  Tuesday, November 29, 2005  2:25 PM

Summary of Contents for FXDQ20NAVE

Page 1: ...IONE LEGGERE ATTENTAMENTE QUESTE ISTRUZIONI TENERE QUESTO MANUALE A PORTATA DI MANO PER RIFERIMENTI FUTURI LEES DEZE INSTRUCTIES ZORGVULDIG DOOR VOOR INSTALLATIE BEWAAR DEZE HAN DLEINDING WAAR U HEM K...

Page 2: ...0NAVE FXDQ50NAVE FXDQ63NAVE FXDQ20NVET FXDQ25NVET FXDQ32NVET FXDQ40NVET FXDQ50NVET FXDQ63NVET FXD20MVE FXD25MVE FXD32MVE FXD40MVE FXD50MVE FXD63MVE FXD20MVET FXD25MVET FXD32MVET FXD40MVET FXD50MVET FX...

Page 3: ...oper electrical construction may lead to electric shocks or fire Make sure that all wiring is secured the specified wires are used and no external forces act on the terminal connections or wires Impro...

Page 4: ...customers how to properly operate the unit operating different functions and adjusting the temper ature by having them carry out operations themselves while looking at the operation manual Do not inst...

Page 5: ...e of 1 m may not be sufficient enough to eliminate the noise If installing the wireless kit in a room with electronic fluo rescent lighting inverter or rapid start type the remote controller s transmi...

Page 6: ...nken insert sunken anchor or other part to be procured in the field to reinforce the ceiling to bearing the weight of the unit for new ceiling Refer to Fig 3 5 For bottom intake replace the chamber li...

Page 7: ...ign matter from infil trating the piping either pinch the end or cover it with tape Do not allow anything other than the designated refrigerant to get mixed into the refrigerant circuit such as air et...

Page 8: ...is finished make sure to check that there is no gas leak When you keep on tightening the flare nut with a spanner there is a point where the tightening torque suddenly increases From that position fur...

Page 9: ...djustable range 600mm or less Field supply 1 1 5m Fig 13 CAUTION The electric wiring work shall be performed by qualified electricians If workers not having the electrician qualification have performe...

Page 10: ...e earth wire should come in contact with gas pipes water pipes lightning rods or telephone earth wires Gas pipes gas leaks can cause explosions and fire Water pipes they cannot be grounded if hard vin...

Page 11: ...e and connect to the terminal block 3P Remote controller and transmission wiring Pull the wires into the unit through the wiring through hole and connect to the terminal block 6P Power supply wiring E...

Page 12: ...ase 50Hz 220 240V or single phase 60Hz 220V Power supply single phase 50Hz 220 240V or single phase 60Hz 220V Outdoor unit F T 1 L 1 1 1 P P 2 P N 1 2 P T F 2 F P F 1 2 2 2 P 1 N 2 P2 F IN D 1 OUT D 1...

Page 13: ...RUN Field settings may have to be performed using the remote controller depending on the type of installa tion 1 Make sure the control box lids are closed on the indoor and outdoor units 2 Depending...

Page 14: ...the point of trouble An explanation of malfunction codes and the correspond ing trouble is provided in CAUTION FOR SERVICING of the outdoor unit If the display shows any of the following there is a po...

Page 15: ...3PN06588 2C EM03A119D 0512 HT 00_CV_3PN06588 2C fm Page 2 Thursday November 17 2005 7 04 PM...

Reviews: