background image

4

English

(length: mm)

(2) Make sure the range of the unit’s external static pres-

sure is not exceeded.

(See the technical documentation for the range of the 
external static pressure setting.)

(3) Open the installation hole. (Pre-set ceilings)

Once the installation hole is opened in the ceiling where 
the unit is to be installed, pass refrigerant piping, drain 
piping, transmission wiring, and remote controller wiring 
(It is not necessary if using a wireless remote controller) 
to the unit’s piping and wiring holes.
See “

6. REFRIGERANT PIPING WORK

”, “

7. DRAIN 

PIPING WORK

”, and “

10.

 

WIRING EXAMPLE

”.

After opening the ceiling hole, make sure ceiling is level if 
needed. It might be necessary to reinforce the ceiling 
frame to prevent shaking.
Consult an architect or carpenter for details.

(4) Install the suspension bolts. 

(Use W3/8 to M10 suspension bolts.)
Use a hole-in-anchor for existing ceilings, and a sunken 
insert, sunken anchor or other part to be procured in the 
field to reinforce the ceiling to bearing the weight of the unit 
for new ceiling. 

(Refer to Fig. 3)

(5) For bottom intake, replace the chamber lid in the pro-

cedure listed in Fig. 4.

(1) Remove the chamber lid. (7 locations)
(2) Reattached the removed chamber lid in the orientation 

shown in Fig. 4. (7 locations)

(3) Attach the air filter (accessory) in the manner shown in 

the diagram.
The four holes which cannot be covered by the air filter 
should be covered with commercially available tape.

Model

A

B

20 · 25 · 32 · 40 · 50 type

900

940

63 type

1100

1140

B

A

620

500

450×450

(Inspection

opening size)

Ceiling

620

A

Air outlet

Suspension

bolt pitch

(length : mm)

Air inlet

Control box

(Suspension

bolt

pitch

)

Allow view

Inspection door

(Ceiling opening)

Fig. 2

SERVICE SPACE

Drain pump

Note: All the above parts are field supplied.

Suspension bolt

Long nut or turn-buckle

Anchor bolt

Indoor unit

Ceiling slab

Fig. 3

Air inlet

(1)

(2)

Fig. 4

Air outlet

Air inlet

Air outlet

Chamber lid

Chamber lid

01_EN_3PN06588-2C.fm  Page 4  Tuesday, November 29, 2005  2:25 PM

Summary of Contents for FXDQ20NAVE

Page 1: ...IONE LEGGERE ATTENTAMENTE QUESTE ISTRUZIONI TENERE QUESTO MANUALE A PORTATA DI MANO PER RIFERIMENTI FUTURI LEES DEZE INSTRUCTIES ZORGVULDIG DOOR VOOR INSTALLATIE BEWAAR DEZE HAN DLEINDING WAAR U HEM K...

Page 2: ...0NAVE FXDQ50NAVE FXDQ63NAVE FXDQ20NVET FXDQ25NVET FXDQ32NVET FXDQ40NVET FXDQ50NVET FXDQ63NVET FXD20MVE FXD25MVE FXD32MVE FXD40MVE FXD50MVE FXD63MVE FXD20MVET FXD25MVET FXD32MVET FXD40MVET FXD50MVET FX...

Page 3: ...oper electrical construction may lead to electric shocks or fire Make sure that all wiring is secured the specified wires are used and no external forces act on the terminal connections or wires Impro...

Page 4: ...customers how to properly operate the unit operating different functions and adjusting the temper ature by having them carry out operations themselves while looking at the operation manual Do not inst...

Page 5: ...e of 1 m may not be sufficient enough to eliminate the noise If installing the wireless kit in a room with electronic fluo rescent lighting inverter or rapid start type the remote controller s transmi...

Page 6: ...nken insert sunken anchor or other part to be procured in the field to reinforce the ceiling to bearing the weight of the unit for new ceiling Refer to Fig 3 5 For bottom intake replace the chamber li...

Page 7: ...ign matter from infil trating the piping either pinch the end or cover it with tape Do not allow anything other than the designated refrigerant to get mixed into the refrigerant circuit such as air et...

Page 8: ...is finished make sure to check that there is no gas leak When you keep on tightening the flare nut with a spanner there is a point where the tightening torque suddenly increases From that position fur...

Page 9: ...djustable range 600mm or less Field supply 1 1 5m Fig 13 CAUTION The electric wiring work shall be performed by qualified electricians If workers not having the electrician qualification have performe...

Page 10: ...e earth wire should come in contact with gas pipes water pipes lightning rods or telephone earth wires Gas pipes gas leaks can cause explosions and fire Water pipes they cannot be grounded if hard vin...

Page 11: ...e and connect to the terminal block 3P Remote controller and transmission wiring Pull the wires into the unit through the wiring through hole and connect to the terminal block 6P Power supply wiring E...

Page 12: ...ase 50Hz 220 240V or single phase 60Hz 220V Power supply single phase 50Hz 220 240V or single phase 60Hz 220V Outdoor unit F T 1 L 1 1 1 P P 2 P N 1 2 P T F 2 F P F 1 2 2 2 P 1 N 2 P2 F IN D 1 OUT D 1...

Page 13: ...RUN Field settings may have to be performed using the remote controller depending on the type of installa tion 1 Make sure the control box lids are closed on the indoor and outdoor units 2 Depending...

Page 14: ...the point of trouble An explanation of malfunction codes and the correspond ing trouble is provided in CAUTION FOR SERVICING of the outdoor unit If the display shows any of the following there is a po...

Page 15: ...3PN06588 2C EM03A119D 0512 HT 00_CV_3PN06588 2C fm Page 2 Thursday November 17 2005 7 04 PM...

Reviews: