background image

English

5

5. INDOOR UNIT INSTALLATION

〈〈

〈〈

〈〈

〈〈

As for the parts to be used for installation work, be sure to 

use the provided accessories and specified parts desig-
nated by our company.

〉〉

〉〉

〉〉

〉〉

(1) Install the indoor unit temporarily.

Attach the hanger bracket to the suspension bolt. Be sure 
to fix it securely by using a nut and washer from the upper 
and lower sides of the hanger bracket. 

(Refer to Fig. 5)

[ PRECAUTION ]

Since the unit uses a plastic drain pan, prevent welding 
spatter and other foreign substances from the air outlet  
during installation.

(2) Adjust the height of the unit.

(3) Check the unit is level.

CAUTION

• Make sure the unit is installed level using a level or a 

plastic tube filled with water. (One thing to watch out for 
in particular is if the unit is installed so that the slope is 
not in the direction of the drain piping, this might cause 
leaking.)

(4) Tighten the upper nut.

6. REFRIGERANT PIPING WORK

〈〈〈〈

For refrigerant piping of outdoor units, see the installation 

manual attached to the outdoor unit.

〉〉〉〉

〈〈〈〈

Execute heat insulation work completely on both sides of 

the gas piping and the liquid piping. Otherwise, a water 
leakage can result sometimes.
Use insulation that can withstand temperatures of at least 
120°C. Reinforce the insulation on the refrigerant piping 
according to the installation environment. If it is not reinforced, 
condensation may form on the surface of the insulation.

〉〉〉〉

CAUTION

Follow the points at below.

Use a pipe cutter and flare suitable for the type of refrigerant.

Apply ester oil or ether oil to the flare section when using a 
flare connection.

Only use the flare nuts included with the unit. Using different 
flare nuts may cause the refrigerant to leak.

To prevent dust, moisture or other foreign matter from infil-
trating the piping, either pinch the end or cover it with tape.

Do not allow anything other than the designated refrigerant 
to get mixed into the refrigerant circuit, such as air, etc. If any 
refrigerant gas leaks while working on the unit, ventilate the 
room thoroughly right away.

(1) Connect the piping.

The outdoor unit is charged with refrigerant.

Be sure to use both a spanner and torque wrench together, 
as shown in the drawing, when connecting or disconnecting 
pipes to/from the unit. 

(Refer to Fig. 6)

Refer to the Table 1 for the dimensions of flare nut spaces.

Apply ester oil or ether oil to flare section (both inside and 
out) when using flare nut connections and then turn 3 or 4 
times by hand. 

(Refer to Fig. 7)

Refer to Table 1 for tightening torque.

Table 1

CAUTION

Overtightening may damage the flare and cause leaks.

Refer to Table 2 if no torque wrench is available.
Using a wrench to tighten flare nuts causes the tightening 
torque to suddenly grow much tighter after a certain point.
From there, tighten the nut further by the appropriate angle 
listed in Table 2.

(2) After the work is finished, make sure to check that 

there is no gas leak.

In case of bottom side

In case of back side

Filter

Force

Force

Main unit

(3)

Attach the filter to the 
main unit while pushing 
down on the bends.

Part to be procured 
in the field

[ Securing the hanger bracket ]

[ How to secure washers ]

Washer for 
hanging bracket (8)

Hanger 
bracket

Tighten
(double nut)

Fig. 5

Insert below washer

Washer fixing plate (11)

(accessory)

(accessory)

Vinyl tube

Level

Pipe 

size

Tightening torque

Flare dimen-

sion A (mm)

Flare shape

 φ

 6.4

(1/4”)

14.2 – 17.2 N·m 

8.7 – 9.1

 φ

 9.5

(3/8”)

32.7 – 39.9 N·m 

12.8 – 13.2

 φ

 12.7

(1/2”)

49.5 – 60.3 N·m 

16.2 – 16.6

 φ

 15.9

(5/8”)

61.8 – 75.4 N·m 

19.3 – 19.7

Torque wrench

Spanner

Ester oil or ether oil

Piping union

Flare nut

Fig. 6

Fig. 7

A

45

0

2

0

R0.4-0.8

90

0

2

0

01_EN_3PN06588-2C.fm  Page 5  Tuesday, November 29, 2005  2:25 PM

Summary of Contents for FXDQ20NAVE

Page 1: ...IONE LEGGERE ATTENTAMENTE QUESTE ISTRUZIONI TENERE QUESTO MANUALE A PORTATA DI MANO PER RIFERIMENTI FUTURI LEES DEZE INSTRUCTIES ZORGVULDIG DOOR VOOR INSTALLATIE BEWAAR DEZE HAN DLEINDING WAAR U HEM K...

Page 2: ...0NAVE FXDQ50NAVE FXDQ63NAVE FXDQ20NVET FXDQ25NVET FXDQ32NVET FXDQ40NVET FXDQ50NVET FXDQ63NVET FXD20MVE FXD25MVE FXD32MVE FXD40MVE FXD50MVE FXD63MVE FXD20MVET FXD25MVET FXD32MVET FXD40MVET FXD50MVET FX...

Page 3: ...oper electrical construction may lead to electric shocks or fire Make sure that all wiring is secured the specified wires are used and no external forces act on the terminal connections or wires Impro...

Page 4: ...customers how to properly operate the unit operating different functions and adjusting the temper ature by having them carry out operations themselves while looking at the operation manual Do not inst...

Page 5: ...e of 1 m may not be sufficient enough to eliminate the noise If installing the wireless kit in a room with electronic fluo rescent lighting inverter or rapid start type the remote controller s transmi...

Page 6: ...nken insert sunken anchor or other part to be procured in the field to reinforce the ceiling to bearing the weight of the unit for new ceiling Refer to Fig 3 5 For bottom intake replace the chamber li...

Page 7: ...ign matter from infil trating the piping either pinch the end or cover it with tape Do not allow anything other than the designated refrigerant to get mixed into the refrigerant circuit such as air et...

Page 8: ...is finished make sure to check that there is no gas leak When you keep on tightening the flare nut with a spanner there is a point where the tightening torque suddenly increases From that position fur...

Page 9: ...djustable range 600mm or less Field supply 1 1 5m Fig 13 CAUTION The electric wiring work shall be performed by qualified electricians If workers not having the electrician qualification have performe...

Page 10: ...e earth wire should come in contact with gas pipes water pipes lightning rods or telephone earth wires Gas pipes gas leaks can cause explosions and fire Water pipes they cannot be grounded if hard vin...

Page 11: ...e and connect to the terminal block 3P Remote controller and transmission wiring Pull the wires into the unit through the wiring through hole and connect to the terminal block 6P Power supply wiring E...

Page 12: ...ase 50Hz 220 240V or single phase 60Hz 220V Power supply single phase 50Hz 220 240V or single phase 60Hz 220V Outdoor unit F T 1 L 1 1 1 P P 2 P N 1 2 P T F 2 F P F 1 2 2 2 P 1 N 2 P2 F IN D 1 OUT D 1...

Page 13: ...RUN Field settings may have to be performed using the remote controller depending on the type of installa tion 1 Make sure the control box lids are closed on the indoor and outdoor units 2 Depending...

Page 14: ...the point of trouble An explanation of malfunction codes and the correspond ing trouble is provided in CAUTION FOR SERVICING of the outdoor unit If the display shows any of the following there is a po...

Page 15: ...3PN06588 2C EM03A119D 0512 HT 00_CV_3PN06588 2C fm Page 2 Thursday November 17 2005 7 04 PM...

Reviews: