background image

English

3

b. Items to be checked at time of delivery

c. Points for explanation about operations

3. SELECTING INSTALLATION SITE 

CAUTION

When moving the unit during or after unpacking, make sure 
to lift it by holding its lifting lugs.  Do not exert any pressure on 
other parts, especially the refrigerant piping, drain piping and 
flange parts.

If you think the humidity inside the ceiling might exceed 
30°C and RH80%, reinforce the insulation on the unit body.
Use glass wool or polyethylene foam as insulation so that 
the thickness is more than 10mm and fits inside the ceiling 
opening.

(1) Select an installation site where the following condi-

tions are fulfilled and that meets with your customer’s 
approval.

Where optimum air distribution can be ensured.

Where nothing blocks air passage.

Where condensate can be properly drained.

Where the ceiling is strong enough to bear the indoor unit 
weight.

Where the false ceiling is not noticeably on an incline.

Where there is no risk of flammable gas leakage.

Where sufficient clearance for maintenance and service 
can be ensured. 

(Refer to Fig. 1)

Where piping between indoor and outdoor units is possi-
ble within the allowable limit. (Refer to the installation 
manual for the outdoor unit.)

*H dimension means the minimum height of the unit.

Select the *H dimension such that a downward slope of at 
least 1/100 is ensured as indicated in “

7. DRAIN PIPING 

WORK

”.

The maintenance space marked with “*” is required when 
the installation box for adaptor PC board (KRP1BA101) 
sold separately is used.

[ PRECAUTION ]

Install the indoor and outdoor units, power supply wiring 
and connecting wires at least 1 m away from televisions 
or radios in order to prevent image interference or noise. 
(Depending on the radio waves, a distance of 1 m may 
not be sufficient enough to eliminate the noise.)

If installing the wireless kit in a room with electronic fluo-
rescent lighting (inverter or rapid start type), the remote 
controller’s transmission distance may be shortened. 
Indoor units should be installed as far away from fluores-
cent lighting as possible.

(2) Use suspension bolts for installation. Check whether 

the ceiling is strong enough to support the weight of 
the unit or not. If there is a risk, reinforce the ceiling 
before installing the unit.

(Installation pitch is marked on the carton box for installa-
tion. Refer to it to check for points requiring reinforcing.)

4. PREPARATIONS BEFORE INSTALLA-

TION

(1) Confirm the positional relationship between the unit 

and suspension bolts. (Refer to Fig. 2)

Install the inspection opening on the control box side where 
maintenance and inspection of the control box and drain 
pump are easy.  Install the inspection opening also in the 
lower part of the unit.

Items to be checked

Check

Did you explain about operations while showing the 
operation manual to your customer?
Did you hand the operation manual and warranty over to 
your customer?
Did you explain about the way of maintaining and cleaning 
local procurements (air filter, grille (both air outlet and suc-
tion grille), etc.) to your customer?
Did you hand manuals of local procurements (in case 
equipped) over to your customer?

The items with 

WARNING and 

CAUTION marks in 

the operation manual are the items pertaining to possibili-
ties for bodily injury and material damage in addition to the 
general usage of the product. Accordingly, it is necessary 
that you make a full explanation about the described con-
tents and also ask your customers to read the operation 
manual.

Control box

Maintenance

space

Maintenance

space

300

or more

*300

or

more

20 or more

2500

or

more

*H= 240

or

more

200

Ceiling

Floor surface

(length : mm)

Fig. 1

01_EN_3PN06588-2C.fm  Page 3  Tuesday, November 29, 2005  2:25 PM

Summary of Contents for FXDQ20NAVE

Page 1: ...IONE LEGGERE ATTENTAMENTE QUESTE ISTRUZIONI TENERE QUESTO MANUALE A PORTATA DI MANO PER RIFERIMENTI FUTURI LEES DEZE INSTRUCTIES ZORGVULDIG DOOR VOOR INSTALLATIE BEWAAR DEZE HAN DLEINDING WAAR U HEM K...

Page 2: ...0NAVE FXDQ50NAVE FXDQ63NAVE FXDQ20NVET FXDQ25NVET FXDQ32NVET FXDQ40NVET FXDQ50NVET FXDQ63NVET FXD20MVE FXD25MVE FXD32MVE FXD40MVE FXD50MVE FXD63MVE FXD20MVET FXD25MVET FXD32MVET FXD40MVET FXD50MVET FX...

Page 3: ...oper electrical construction may lead to electric shocks or fire Make sure that all wiring is secured the specified wires are used and no external forces act on the terminal connections or wires Impro...

Page 4: ...customers how to properly operate the unit operating different functions and adjusting the temper ature by having them carry out operations themselves while looking at the operation manual Do not inst...

Page 5: ...e of 1 m may not be sufficient enough to eliminate the noise If installing the wireless kit in a room with electronic fluo rescent lighting inverter or rapid start type the remote controller s transmi...

Page 6: ...nken insert sunken anchor or other part to be procured in the field to reinforce the ceiling to bearing the weight of the unit for new ceiling Refer to Fig 3 5 For bottom intake replace the chamber li...

Page 7: ...ign matter from infil trating the piping either pinch the end or cover it with tape Do not allow anything other than the designated refrigerant to get mixed into the refrigerant circuit such as air et...

Page 8: ...is finished make sure to check that there is no gas leak When you keep on tightening the flare nut with a spanner there is a point where the tightening torque suddenly increases From that position fur...

Page 9: ...djustable range 600mm or less Field supply 1 1 5m Fig 13 CAUTION The electric wiring work shall be performed by qualified electricians If workers not having the electrician qualification have performe...

Page 10: ...e earth wire should come in contact with gas pipes water pipes lightning rods or telephone earth wires Gas pipes gas leaks can cause explosions and fire Water pipes they cannot be grounded if hard vin...

Page 11: ...e and connect to the terminal block 3P Remote controller and transmission wiring Pull the wires into the unit through the wiring through hole and connect to the terminal block 6P Power supply wiring E...

Page 12: ...ase 50Hz 220 240V or single phase 60Hz 220V Power supply single phase 50Hz 220 240V or single phase 60Hz 220V Outdoor unit F T 1 L 1 1 1 P P 2 P N 1 2 P T F 2 F P F 1 2 2 2 P 1 N 2 P2 F IN D 1 OUT D 1...

Page 13: ...RUN Field settings may have to be performed using the remote controller depending on the type of installa tion 1 Make sure the control box lids are closed on the indoor and outdoor units 2 Depending...

Page 14: ...the point of trouble An explanation of malfunction codes and the correspond ing trouble is provided in CAUTION FOR SERVICING of the outdoor unit If the display shows any of the following there is a po...

Page 15: ...3PN06588 2C EM03A119D 0512 HT 00_CV_3PN06588 2C fm Page 2 Thursday November 17 2005 7 04 PM...

Reviews: