25M9V3B9
VRV System air conditioners
3P468515-3  – 12.2016

Installation and operation manual

4

Next, press the inspection/test operation button 

 on the

remote controller. The unit will engage the test operation mode.

Press the operation mode selector button 

 until selecting

fan operation 

. Then, press the on/off button 

. The indoor

unit fan and drain pump will start up. Check that the water has

drained from the unit. Press 

 to go back to the first mode.

E

LECTRIC

 

WIRING

 

WORK

General instructions

All field supplied parts and materials and electric works must
conform to local codes.

Use copper wire only.

Follow the "Wiring diagram" attached to the switch box cover to
wire the outdoor unit, indoor units and the remote controller. For
details on hooking up the remote controller, refer to the
"Installation manual of the remote controller".

All wiring must be performed by an authorized electrician.

A circuit breaker capable of shutting down power supply to the
entire system must be installed.

This system consists of multiple indoor units. Mark each indoor
unit as unit A, unit B..., and be sure the terminal board wiring to
the outdoor unit and BS unit are properly matched. If wiring and
piping between the outdoor unit and an indoor unit are
mismatched, the system may cause a malfunction.

Electrical characteristics

MCA: Min. circuit Amps (A)
MFA: Max. Fuse Amps (A)
KW: Fan Motor Rated Output (kW)
FLA: Full Load Amps (A)

Specifications for field supplied fuses and wire

W

IRING

 

EXAMPLE

 

AND

 

HOW

 

TO

 

SET

 

THE

 

REMOTE

 

CONTROLLER

How to connect wiring

Open the switch box cover, as shown in 

figure 7

, to make

connections.

Precautions

1.

Observe the notes mentioned below when wiring to the power
supply terminal board.

Do not connect wires of different gauge to the same power
supply terminal. (Looseness in the connection may cause
overheating.)

When connecting wires of the same gauge, connect them
according to the figure.

2.

Keep total current of crossover wiring between indoor units less
than 12 A. Branch the line outside the terminal board of the unit
in accordance with electrical equipment standards, when using

two power wiring of a gauge greater than 2 mm

2

 (Ø1.6).

The branch must be sheathed in order to provide an equal or
greater degree of insulation as power supply wiring itself.

3.

Do not connect wires of different gauge to the same grounding
terminal. Looseness in the connection may deteriorate the
protection.

4.

Remote controller cords and wires connecting the units should
be located at least 50 mm away from power supply wiring. Not
following this guideline may result in malfunction due to electrical
noise.

5.

For the remote controller wiring, refer to the "Installation manual
of the remote controller" supplied with the remote controller.

6.

Never connect the power supply wiring to the terminal board for
transmission wiring. This mistake could damage the entire
system.

7.

Use only specified wires and tightly connect wires to the
terminals. Be careful that wires do not place external stress on
the terminals. Keep wiring in neat order so that they do not
obstruct other equipment such as popping open the service
cover. Make sure the cover closes tight. Incomplete connections
could result in overheating, and in the worse case, electric shock
or fire. 

W

IRING

 

EXAMPLE

Fit the power supply wiring of each unit with a switch and fuse as
shown in 

figure 16

.

Model

Hz

Volts

Voltage range

25

50

230

min. 198–max. 264

Power supply

Fan motor

Model

MCA

MFA

KW

FLA

25

0.2

16 A

0.01

0.1

NOTE

For details, refer to "Electrical data".

Power supply wiring

Model

Field fuses

Wire

Size

25

16 A

H05VV-U3G

Local codes

Model

Wire

Size

25

Sheathed wire (2)

0.75–1.25 mm

2

NOTE

For details, refer to the chapter "Wiring example".

Allowable length of transmission wiring between
indoor and outdoor units, and between the indoor
unit and the remote controller is as follows:

Outdoor unit - indoor unit: max. 1000 m 
(total wiring length: 2000 m)

Indoor unit - remote controller: max 500 m

TEST

TEST

1

Power supply

2

Main switch

3

Power supply wiring

4

Transmission wiring

5

Switch

6

Fuse

7

BS unit REYQ only

8

Indoor unit

9

Remote controller

Summary of Contents for FXDQ20M9V3B9

Page 1: ...INSTALLATION AND OPERATION MANUAL FXDQ20M9V3B9 FXDQ25M9V3B9 System air conditioners...

Page 2: ...1 1 7 7 2 2 4 4 3 3 1 2 3 5a 5a 6 6 5b 5b...

Page 3: ...il Certi cato C 07 A B C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acordo com o Certi cado C 09 A B C 10 Bem rk som anf rt i A og positivt vurderet af B i henhold til Certi k...

Page 4: ...ect a remote controller according to customers request and install in an appropriate place Refer to catalogues and technical literature for selecting a suitable remote controller Wiring adaptor for el...

Page 5: ...N 1 Relation of ceiling opening to unit and suspension bolt position See gure 1 2 Make the wall hole to the outdoor side for the electric wiring the refrigerant and drain piping The hole must slope do...

Page 6: ...the drain piping and never put the end of the hose into water See gure 2 If you extend the drain hose always insulate it up to the outdoor side with polyethylene foam insulation material eld supply To...

Page 7: ...less than 12 A Branch the line outside the terminal board of the unit in accordance with electrical equipment standards when using two power wiring of a gauge greater than 2 mm2 1 6 The branch must be...

Page 8: ...ter 200 hrs 100 hrs 2 Thermostat sensor selection Use both the unit sensor or remotesensorif installed AND the remote controller sensor See note 5 6 Use unit sensor only or remote sensor if installed...

Page 9: ...ion forced off at factory set See gure 17 Centralized control For centralized control it is necessary to designate the group No For details refer to the manual of each optional controller for centrali...

Page 10: ...ter using a vacuum cleaner and gently rinse them in cool water Do not use detergent or hot water to avoid lter shrinking or deformation After cleaning dry them in the shade 3 Replacing the air lter Re...

Page 11: ...NETIC RELAY J1EH F1U F2U FUSE 250 V 5 A X1A X2A CONNECTOR WIRING ADAPTOR X1M TERMINAL STRIP CONNECTOR FOR OPTIONAL PARTS X16A CONNECTOR WIRING ADAPTOR X18A CONNECTOR WIRING ADAPTOR FOR ELECTRICAL APPE...

Page 12: ......

Page 13: ......

Page 14: ......

Page 15: ...7 3 4 1 2 5 6 9 8 12 12 IN D OUT D F1 F2 F1 F2 Control box IN D OUT D F1 F2 F1 F2 Control box L N P1 P2 LN P1 P2 F1 F2 T1 T2 1 3 6 2 9 9 10 10 L N IN D OUT D F1 F2 F1 F2 Control box LN P1 P2 P1 P2 F1...

Page 16: ...3P468515 3 12 2016 Copyright 2016 Daikin...

Reviews: