background image

 

Installation and operation manual

3

25M9V3B9

VRV System air conditioners

3P468515-3  – 12.2016

R

EFRIGERANT

 

PIPING

 

WORK

For refrigerant piping of outdoor unit, refer to the installation manual
supplied with the outdoor unit.
Before rigging tubes, check which type of refrigerant is used.

Use a pipe cutter and flare suitable for R410A.

Apply ether oil or ester oil around the flare portions before
connecting.

To prevent dust, moisture or other foreign matter from infiltrating
the tube, either pinch the end, or cover it with tape.

The outdoor unit is charged with refrigerant.

Be sure to use both a spanner and torque wrench together when
connecting or disconnecting pipes to/from the unit.

Refer to Table 1 for the dimensions of flare nut spaces and the
appropriate tightening torque. (Overtightening may damage the
flare and cause leaks.)

When connecting the flare nut, coat the flare both inside and
outside with ether oil or ester oil and initially tighten by hand 3 or
4 turns before tightening firmly. 
Coat here with ether oil or ester oil

Check the pipe connector for gas leaks.

Be sure to insulate the gas pipe and the liquid pipe separately
with polyethylene foam insulation material (thermal
conductivity = 0.041~0.052 W/mK).

Table 1

D

RAIN

 

PIPING

 

WORK

Rig the drain piping as shown in figure and take measures against
condensation. Improperly rigged piping could lead to leaks and
eventually wet furniture and belongings.

1.

Install the drain pipes.

Keep piping as short as possible and slope it downwards so
that air may not remain trapped inside the pipe. 

Keep pipe size equal to or greater than that of the connecting
pipe (Vinyl pipe of 25 mm nominal diameter and 32 mm outer
diameter).

Do not use a trap in the drain piping and never put the end of
the hose into water. 

(See figure 2)

If you extend the drain hose, always insulate it up to the
outdoor side with polyethylene foam insulation material (field
supply).

To ensure a downward slope of 1:100, install hanging bars
every 1 to 1.5 m.

If unifying multiple drain pipes, install the pipes as shown.

2.

After piping work is finished, check if drainage flows
smoothly.

Make sure that the drain hose is firmly connected.

Pour some water into the drain pan to check if the water flows
smoothly.

When electric wiring work is finished

Check drainage flow during COOL running, explained in chapter
"Test operation".

When electric wiring work is not finished

Remove the switch box lid and connect the power supply and
remote controller to the terminals. 

(See figure 7)

All field piping must be provided by a licensed refrigeration
technician and must comply with the relevant local and
national codes.

1

Torque wrench

2

Spanner

3

Piping union

4

Flare nut

Inside diameter

Wall thickness

Gas pipe insulation

12–15 mm

8–10 mm

Liquid pipe insulation

8–10 mm

7–10 mm

NOTE

For the gas pipe, use a polyethylene foam resistant to
a temperature of 110°C.

When inserting the refrigerant piping in the wall hole, take
care not to let dust or moisture come into the piping.
Protect the pipes with a cap or seal the pipe end
completely with tape.

Pipe gauge

Tightening torque

Flare dimension A 

(mm)

Flare shape

Ø6.4

14.2~17.2 N•m

(144~176 kgf•cm)

8.7~9.1

Ø12.7

49.5~60.3 N•m

(504~616 kgf•cm)

16.2~16.6

1

2

4

3

R=0.4~0.8

45

° ±

2

90

°±

2

A

1

Hanging bar

1

Drain hose fixed to the indoor unit

2

Indoor side extension drain hose

3

Wall

4

Polyethylene foam

1

Power supply wiring

2

Wiring port

3

Indoor PC board

4

Power supply terminal board

5

Transmission wiring between units

6

Remote controller wiring

7

Terminal board for unit transmission wiring

8

Electric parts box lid

9

Wiring diagram

10

Electric parts box

1-1.5 m

1

Summary of Contents for FXDQ20M9V3B9

Page 1: ...INSTALLATION AND OPERATION MANUAL FXDQ20M9V3B9 FXDQ25M9V3B9 System air conditioners...

Page 2: ...1 1 7 7 2 2 4 4 3 3 1 2 3 5a 5a 6 6 5b 5b...

Page 3: ...il Certi cato C 07 A B C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acordo com o Certi cado C 09 A B C 10 Bem rk som anf rt i A og positivt vurderet af B i henhold til Certi k...

Page 4: ...ect a remote controller according to customers request and install in an appropriate place Refer to catalogues and technical literature for selecting a suitable remote controller Wiring adaptor for el...

Page 5: ...N 1 Relation of ceiling opening to unit and suspension bolt position See gure 1 2 Make the wall hole to the outdoor side for the electric wiring the refrigerant and drain piping The hole must slope do...

Page 6: ...the drain piping and never put the end of the hose into water See gure 2 If you extend the drain hose always insulate it up to the outdoor side with polyethylene foam insulation material eld supply To...

Page 7: ...less than 12 A Branch the line outside the terminal board of the unit in accordance with electrical equipment standards when using two power wiring of a gauge greater than 2 mm2 1 6 The branch must be...

Page 8: ...ter 200 hrs 100 hrs 2 Thermostat sensor selection Use both the unit sensor or remotesensorif installed AND the remote controller sensor See note 5 6 Use unit sensor only or remote sensor if installed...

Page 9: ...ion forced off at factory set See gure 17 Centralized control For centralized control it is necessary to designate the group No For details refer to the manual of each optional controller for centrali...

Page 10: ...ter using a vacuum cleaner and gently rinse them in cool water Do not use detergent or hot water to avoid lter shrinking or deformation After cleaning dry them in the shade 3 Replacing the air lter Re...

Page 11: ...NETIC RELAY J1EH F1U F2U FUSE 250 V 5 A X1A X2A CONNECTOR WIRING ADAPTOR X1M TERMINAL STRIP CONNECTOR FOR OPTIONAL PARTS X16A CONNECTOR WIRING ADAPTOR X18A CONNECTOR WIRING ADAPTOR FOR ELECTRICAL APPE...

Page 12: ......

Page 13: ......

Page 14: ......

Page 15: ...7 3 4 1 2 5 6 9 8 12 12 IN D OUT D F1 F2 F1 F2 Control box IN D OUT D F1 F2 F1 F2 Control box L N P1 P2 LN P1 P2 F1 F2 T1 T2 1 3 6 2 9 9 10 10 L N IN D OUT D F1 F2 F1 F2 Control box LN P1 P2 P1 P2 F1...

Page 16: ...3P468515 3 12 2016 Copyright 2016 Daikin...

Reviews: