background image

 

Installation and operation manual

5

25M9V3B9

VRV System air conditioners

3P468515-3  – 12.2016

Complete system example (3 systems)

When using 1 remote controller for 1 indoor unit (Normal
operation) 

(See figure 8)

For group control or use with 2 remote controllers 

(See

figure 10)

When including BS unit 

(See figure 12)

Precautions

1.

A single switch can be used to supply power to units on the
same system. However, branch switches and branch circuit
breakers must be selected carefully.

2.

For a group control remote controller, choose the remote
controller that suits the indoor unit which has the most functions.

3.

Do not ground the equipment on gas pipes, water pipes,  light-
ning rods or crossground with telephones. Improper grounding
could result in electric shock.

F

IELD

 

SETTING

Field setting must be made on the remote controller in function of the
installation condition.

Setting can be made by changing the "Mode number", "First
code No." and "Second code No.".

For setting and operation, refer to the "Field settings" in the
installation manual of the remote controller.

Summary of field settings

Control by 2 Remote Controllers (Controlling 1 indoor 
unit by 2 remote controllers)

When using 2 remote controllers, one must be set to "MAIN" and
the other to "SUB".

1

Outdoor unit

2

Indoor unit

3

Remote controller (Optional accessories)

4

Most downstream indoor unit

5

For use with 2 remote controllers

6

BS unit

NOTE

It is not necessary to designate indoor unit address
when using group control. The address is automatically
set when the power is activated.

Mode 

No.

(Note 1)

First 

code 

No.

Description of setting

Second code No. (Note 2)

01

02

03

04

10 

(20)

0

Filter contamination 
- Heavy/Light
= Setting to define 
time between 2 filter 
cleaning display 
indications. (When 
contamination is 
high, setting can be 
changed to half the 
time inbetween 2 
filter cleaning 
display indications.)

Ultra-long-
life filter

Light

±10,000 hrs.

Hea

vy

±5,000 hrs.

Long-life 
filter

±2,500 hrs.

±1,250 hrs.

Standard 
filter

±200 hrs.

±100 hrs.

2

Thermostat sensor selection

Use both the 
unit sensor (or 
remote sensor if 
installed) AND 
the remote 
controller 
sensor. 
(See note 5+6)

Use unit sensor 
only (or remote 
sensor if 
installed). 
(See note 5+6)

Use remote 
controller 
sensor only. 
(See note 5+6)

3

Setting for display of time 
between 2 filter cleaning display 
indications

Display

Do not display

6

Thermostat sensor in group 
control

Use unit sensor 
only (or remote 
sensor if 
installed). 
(See note 6)

Use both the 
unit senor (or 
remote sensor if 
installed) AND 
the remote 
controller 
sensor. (See 
note 4+5+6)

12 

(22)

0

Output signal X1-X2 of the 
optional KRP1B PCB kit

Thermostat-on 
+ compressor 
run

Operation

Mal-
function

1

ON/OFF input from outside 
(T1/T2 input) = Setting when 
forced ON/OFF is to be 
operated from outside.

Forced OFF

ON/OFF
operation

3

Fan setting during thermostat 
OFF at heating operation

LL

Set speed

OFF 
(See note 3)

4

Differential automatic 
changeover

0°C

1°C

2°C

3°C
(See 
note 7)

5

Auto-restart after power failure

Disabled

Enabled

9

Fixed cool/heat master

Disabled

Enabled

13 

(23)

6

Setting the external static 
pressure 
(To be set in function of the 
connected duct resistance)

Normal

High static 
pressure

Low static 
pressure

15 

(25)

3

Drain pump ope 
humidifier interlock

Equipped

Not equipped

Note 1 :

Setting is carried out in the group mode, however, if the mode number inside parentheses is selected, 
indoor units can also be set individually.

Note 2 :

Factory settings of the Second code No. are marked in grey backgrounds.

Note 3 :

Only use in combination with optional remote sensor or when setting 10-2-03 is used.

Note 4 :

If group control is selected and remocon sensor is to be used, then set 10-6-02 & 10-2-03.

Note 5 :

If setting 10-6-02 + 10-2-01 or 10-2-02 or 10-2-03 are set at the same time, then setting 10-2-01, 
10-2-02 or 10-2-03 have priority.

Note 6 :

If setting 10-6-01 + 10-2-01 or 10-2-02 or 10-2-03 are set at the same time, then setting for group 
connection, 10-6-01 has priority and for individual connection, 10-2-01, 10-2-02 or 10-2-03 have 
priority.

Note 7 :

More settings for Differential automatic change over temperatures are:
Second code No.

05

4°C

06

5°C

07

6°C

08

7°C

Summary of Contents for FXDQ20M9V3B9

Page 1: ...INSTALLATION AND OPERATION MANUAL FXDQ20M9V3B9 FXDQ25M9V3B9 System air conditioners...

Page 2: ...1 1 7 7 2 2 4 4 3 3 1 2 3 5a 5a 6 6 5b 5b...

Page 3: ...il Certi cato C 07 A B C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acordo com o Certi cado C 09 A B C 10 Bem rk som anf rt i A og positivt vurderet af B i henhold til Certi k...

Page 4: ...ect a remote controller according to customers request and install in an appropriate place Refer to catalogues and technical literature for selecting a suitable remote controller Wiring adaptor for el...

Page 5: ...N 1 Relation of ceiling opening to unit and suspension bolt position See gure 1 2 Make the wall hole to the outdoor side for the electric wiring the refrigerant and drain piping The hole must slope do...

Page 6: ...the drain piping and never put the end of the hose into water See gure 2 If you extend the drain hose always insulate it up to the outdoor side with polyethylene foam insulation material eld supply To...

Page 7: ...less than 12 A Branch the line outside the terminal board of the unit in accordance with electrical equipment standards when using two power wiring of a gauge greater than 2 mm2 1 6 The branch must be...

Page 8: ...ter 200 hrs 100 hrs 2 Thermostat sensor selection Use both the unit sensor or remotesensorif installed AND the remote controller sensor See note 5 6 Use unit sensor only or remote sensor if installed...

Page 9: ...ion forced off at factory set See gure 17 Centralized control For centralized control it is necessary to designate the group No For details refer to the manual of each optional controller for centrali...

Page 10: ...ter using a vacuum cleaner and gently rinse them in cool water Do not use detergent or hot water to avoid lter shrinking or deformation After cleaning dry them in the shade 3 Replacing the air lter Re...

Page 11: ...NETIC RELAY J1EH F1U F2U FUSE 250 V 5 A X1A X2A CONNECTOR WIRING ADAPTOR X1M TERMINAL STRIP CONNECTOR FOR OPTIONAL PARTS X16A CONNECTOR WIRING ADAPTOR X18A CONNECTOR WIRING ADAPTOR FOR ELECTRICAL APPE...

Page 12: ......

Page 13: ......

Page 14: ......

Page 15: ...7 3 4 1 2 5 6 9 8 12 12 IN D OUT D F1 F2 F1 F2 Control box IN D OUT D F1 F2 F1 F2 Control box L N P1 P2 LN P1 P2 F1 F2 T1 T2 1 3 6 2 9 9 10 10 L N IN D OUT D F1 F2 F1 F2 Control box LN P1 P2 P1 P2 F1...

Page 16: ...3P468515 3 12 2016 Copyright 2016 Daikin...

Reviews: