25M9V3B9
VRV System air conditioners
3P468515-3  – 12.2016

Installation and operation manual

2

I

MPORTANT

 

INFORMATION

 

REGARDING

 

THE

 

REFRIGERANT

 

USED

This product contains fluorinated greenhouse gases.

Refrigerant type:

R410A

GWP

(1)

 value:

2087.5

(1)

 GWP = global warming potential

Periodical inspections for refrigerant leaks may be required
depending on European or local legislation. Please contact your local
dealer for more information.

S

ELECTING

 

INSTALLATION

 

SITE

 

(See figure 1)

1.

Select an installation site where the following conditions
are fulfilled and that meets your customer's approval.

The units are designed for ceiling concealed installation with
an air discharge duct of 500 mm. 

(See figure 13)

Where optimum air distribution can be ensured.

Where nothing blocks air passage.

Where condensate water can be properly drained.

Where the false ceiling is not noticeably on an incline.

Where sufficient clearance for maintenance and service can
be ensured.

Where piping between indoor and outdoor units is possible
within the allowable limit. (Refer to the installation manual of
the outdoor unit.)

Make sure that no piping is passing through the hatched area
(

figure 6

). Condensation can drip on the switch box and pipes

can prevent you from opening the switch box smoothly.

This is a class A product. In a domestic environment this
product may cause radio interference in which case the user
may be required to take adequate measures.

Keep indoor unit, outdoor unit, power supply wiring and
transmission wiring at least 1 meter away from televisions
and radios. This is to prevent image interference and noise in
those electrical appliances.
(Noise may be generated depending on the conditions under
which the electric wave is generated, even if 1 meter is kept.)

2.

Use suspension bolts for installation. Check whether the
ceiling is strong enough to support the weight of the indoor
unit. If there is a risk, reinforce the ceiling before installing
the unit. 

(See figure 1)

P

REPARATIONS

 

BEFORE

 

INSTALLATION

1.

Relation of ceiling opening to unit and suspension bolt
position. 

(See figure 1)

2.

Make the wall hole to the outdoor side for the electric
wiring, the refrigerant and drain piping.

The hole must slope down toward the outdoor side.

The hole size must be just as large as to hold the protective
pipe (Ø7-8 cm) (field supply).

Use a wall hole cover (field supply) to hide the wall hole as
much as possible.

3.

The fan speed for this indoor unit is preset to provide
standard external static pressure.

If higher or lower external static pressure is required, reset the
external static pressure by changing the initial setting from the
remote controller.

4.

Install the suspension bolts. 

(See figure 4)

(Use M10 size bolt for the suspension bolt.) Use anchors for
existing ceilings, and a sunken insert, sunken anchors or other
field supplied parts for new ceilings to reinforce the ceiling in
order to bear the weight of the unit.

I

NDOOR

 

UNIT

 

INSTALLATION

When installing optional accessories, read also the installation
manual of the optional accessories. Depending on the field
conditions, it may be easier to install optional accessories before the
indoor unit is installed.

1.

Install the indoor unit temporarily. 

Attach the hanger bracket to the suspension bolt. Be sure to
fix it securely by using a nut and washer from the upper and
lower sides of the hanger bracket. 

(See figure 3)

2.

Check if the unit is horizontally levelled.

Do not install the unit tilted. 

Check if the unit is levelled at all four corners with a water
level or a water-filled vinyl tube as shown in 

figure 9

.

3.

Tighten the upper nut.

1

Service space 

300

2

Drain pipe

3

Power supply wiring port

4

Transmission wiring port

5

Gas pipe

6

Liquid pipe

7

Switch box

8

Switch box cover

9

Screw for opening the switch box cover

10

Suspension bolt pitch (x4)

11

Suspension bolt pitch distance

NOTE

For other installation than standard installation, contact
your Daikin dealer for details.

1

Protective pipe (field supply)

2

Wall hole cover 
(field supply)

1

Anchor

2

Ceiling slab

3

Long nut or turn-buckle

4

Suspension bolt

NOTE

All the above parts are field supplied.

1

Field procurement

2

Washer for hanger bracket

3

Tighten (double nut)

1

Water level

2

Vinyl tube

Ø7-8 cm

1

2

Summary of Contents for FXDQ20M9V3B9

Page 1: ...INSTALLATION AND OPERATION MANUAL FXDQ20M9V3B9 FXDQ25M9V3B9 System air conditioners...

Page 2: ...1 1 7 7 2 2 4 4 3 3 1 2 3 5a 5a 6 6 5b 5b...

Page 3: ...il Certi cato C 07 A B C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acordo com o Certi cado C 09 A B C 10 Bem rk som anf rt i A og positivt vurderet af B i henhold til Certi k...

Page 4: ...ect a remote controller according to customers request and install in an appropriate place Refer to catalogues and technical literature for selecting a suitable remote controller Wiring adaptor for el...

Page 5: ...N 1 Relation of ceiling opening to unit and suspension bolt position See gure 1 2 Make the wall hole to the outdoor side for the electric wiring the refrigerant and drain piping The hole must slope do...

Page 6: ...the drain piping and never put the end of the hose into water See gure 2 If you extend the drain hose always insulate it up to the outdoor side with polyethylene foam insulation material eld supply To...

Page 7: ...less than 12 A Branch the line outside the terminal board of the unit in accordance with electrical equipment standards when using two power wiring of a gauge greater than 2 mm2 1 6 The branch must be...

Page 8: ...ter 200 hrs 100 hrs 2 Thermostat sensor selection Use both the unit sensor or remotesensorif installed AND the remote controller sensor See note 5 6 Use unit sensor only or remote sensor if installed...

Page 9: ...ion forced off at factory set See gure 17 Centralized control For centralized control it is necessary to designate the group No For details refer to the manual of each optional controller for centrali...

Page 10: ...ter using a vacuum cleaner and gently rinse them in cool water Do not use detergent or hot water to avoid lter shrinking or deformation After cleaning dry them in the shade 3 Replacing the air lter Re...

Page 11: ...NETIC RELAY J1EH F1U F2U FUSE 250 V 5 A X1A X2A CONNECTOR WIRING ADAPTOR X1M TERMINAL STRIP CONNECTOR FOR OPTIONAL PARTS X16A CONNECTOR WIRING ADAPTOR X18A CONNECTOR WIRING ADAPTOR FOR ELECTRICAL APPE...

Page 12: ......

Page 13: ......

Page 14: ......

Page 15: ...7 3 4 1 2 5 6 9 8 12 12 IN D OUT D F1 F2 F1 F2 Control box IN D OUT D F1 F2 F1 F2 Control box L N P1 P2 LN P1 P2 F1 F2 T1 T2 1 3 6 2 9 9 10 10 L N IN D OUT D F1 F2 F1 F2 Control box LN P1 P2 P1 P2 F1...

Page 16: ...3P468515 3 12 2016 Copyright 2016 Daikin...

Reviews: