25M9V3B9
VRV System air conditioners
3P468515-3  – 12.2016

Installation and operation manual

6

Main/sub changeover

1.

Insert a wedge-head screwdriver into the recess between the
upper and lower part of the remote controller and, working from
the 2 positions, pry off the upper part. 

(See figure 11)

(The remote controller PC board is attached to the upper part of
the remote controller.)

2.

Turn the main/sub changeover switch on one of the two remote
controller PC boards to "S". 

(See figure 15)

(Leave the switch of the other remote controller set to "M".)

Computerised control (forced off and on/off operation)

1.

Wire specifications and how to perform wiring.

Connect input from outside to terminals T1 and T2 of the
terminal board (remote controller to transmission wiring).

See 

figure 14

.

2.

Actuation

The following table explains "forced off" and "on/off
operations" in response to input A.

3.

How to select forced off and on/off operation

Turn the power on and then use the remote controller to
select operation.

Set the remote controller to the field set mode. For details,
refer to the chapter "How to set in the field", in the remote
controller manual.

When in the field set mode, select mode No. 12, then set the
first code (switch) No. to "1". Then set second code (position)
No. to "01" for forced off and to "02" for on/off operation.
(forced off at factory set.) 

(See figure 17)

Centralized control

For centralized control, it is necessary to designate the group
No. For details, refer to the manual of each optional controller for
centralized control.

T

EST

 

OPERATION

Refer to the installation manual of the outdoor unit.

The operation lamp of the remote controller will flash when an
error occurs. Check the error code on the liquid crystal display to
identify the trouble. An explanation of error codes and the
corresponding trouble is provided on "Caution for servicing"
sticker included in the accessory bag.

S

PECIAL

 

FEATURES

Air suction direction

This feature allows the user to choose the air suction direction.
By switching the plate from bottom to rear, the air suction
direction can be changed from the rear to the bottom side.

Drain pan outlet

The customer has the possibility to select either right or left
sided water drain outlet.

1

Remote controller PC board

2

Factory setting

3

Only one remote controller needs to be changed

Wire specification

Sheathed vinyl cord or cable (2 wire)

Gauge

0.75–1.25 mm

2

Length

Max. 100 m

External terminal

Contact that can ensure the minimum 
applicable load of 15 V DC, 10 mA

1

Input A

Forced off

on/off operation

Input "on" stops operation

input off 

 on: turns on the unit 

(impossible by remote controllers)

Input "off" enables control

input on 

 off: turns off the unit by 

remote controller

1

Second code No.

2

Mode No.

3

First code No.

4

Field set mode

1

Air inlet

2

Air outlet

3

Remote controller

Summary of Contents for FXDQ20M9V3B9

Page 1: ...INSTALLATION AND OPERATION MANUAL FXDQ20M9V3B9 FXDQ25M9V3B9 System air conditioners...

Page 2: ...1 1 7 7 2 2 4 4 3 3 1 2 3 5a 5a 6 6 5b 5b...

Page 3: ...il Certi cato C 07 A B C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acordo com o Certi cado C 09 A B C 10 Bem rk som anf rt i A og positivt vurderet af B i henhold til Certi k...

Page 4: ...ect a remote controller according to customers request and install in an appropriate place Refer to catalogues and technical literature for selecting a suitable remote controller Wiring adaptor for el...

Page 5: ...N 1 Relation of ceiling opening to unit and suspension bolt position See gure 1 2 Make the wall hole to the outdoor side for the electric wiring the refrigerant and drain piping The hole must slope do...

Page 6: ...the drain piping and never put the end of the hose into water See gure 2 If you extend the drain hose always insulate it up to the outdoor side with polyethylene foam insulation material eld supply To...

Page 7: ...less than 12 A Branch the line outside the terminal board of the unit in accordance with electrical equipment standards when using two power wiring of a gauge greater than 2 mm2 1 6 The branch must be...

Page 8: ...ter 200 hrs 100 hrs 2 Thermostat sensor selection Use both the unit sensor or remotesensorif installed AND the remote controller sensor See note 5 6 Use unit sensor only or remote sensor if installed...

Page 9: ...ion forced off at factory set See gure 17 Centralized control For centralized control it is necessary to designate the group No For details refer to the manual of each optional controller for centrali...

Page 10: ...ter using a vacuum cleaner and gently rinse them in cool water Do not use detergent or hot water to avoid lter shrinking or deformation After cleaning dry them in the shade 3 Replacing the air lter Re...

Page 11: ...NETIC RELAY J1EH F1U F2U FUSE 250 V 5 A X1A X2A CONNECTOR WIRING ADAPTOR X1M TERMINAL STRIP CONNECTOR FOR OPTIONAL PARTS X16A CONNECTOR WIRING ADAPTOR X18A CONNECTOR WIRING ADAPTOR FOR ELECTRICAL APPE...

Page 12: ......

Page 13: ......

Page 14: ......

Page 15: ...7 3 4 1 2 5 6 9 8 12 12 IN D OUT D F1 F2 F1 F2 Control box IN D OUT D F1 F2 F1 F2 Control box L N P1 P2 LN P1 P2 F1 F2 T1 T2 1 3 6 2 9 9 10 10 L N IN D OUT D F1 F2 F1 F2 Control box LN P1 P2 P1 P2 F1...

Page 16: ...3P468515 3 12 2016 Copyright 2016 Daikin...

Reviews: