Installation and operation manual
9
FWEC2
Advanced electronic controller
FC66002764
NON-SERIOUS ALARMS
■
Code
A03
= water sensor error
■
Code
A04
= remote humidity probe error (only if a remote
temperature probe is installed)
■
Code
A05
= internal humidity probe error
N.B.
: the alarm code is displayed only when the thermostat
is switched
off
MODBUS
The protocol implemented in the controller is Modbus RTU
(9600, N, 8, 2) on RS485
FUNCTIONS IMPLEMENTED
■
0x03 : Read Holding Registers
■
0x04 : Read Input Registers
■
0x10 : Write Multiple registers
EXCEPTIONS IMPLEMENTED
Exception Code 02: Invalidate data address
LIST OF SUPERVISION PARAMETERS
ADDRESS
REGISTER
TYPE
U.M.
0
Status
R
-
1
Speeds
R
-
2
Air temperature
R
[°C/10]
3
Humidity
R
%
4
Water temperature
R
[°C/10]
5
P00:
Con
fi
guration
R
-
6
P05:
Con
fi
g. DIN
R
-
7
T. Active setpoint
R
[°C/10]
8
T. User setpoint
R
[°C/10]
9
LCD version
R
-
50
Digital 1
R/W
-
51
-
R/W
-
52
Setpoint - Cooling
R/W
[°C/10]
53
Setpoint - Heating
R/W
[°C/10]
54
Minimum Setpoint – Cool.
R/W
[°C/10]
55
Maximum Setpoint – Cool.
R/W
[°C/10]
56
Minimum Setpoint – Heat.
R/W
[°C/10]
57
Maximum Setpoint – Heat.
R/W
[°C/10]
58
Speeds
R/W
-
59
Economy Correction
R/W
[°C/10]
DESCRIPTION OF READ-ONLY REGISTERS [R]
■
“Staus”
“REGISTER”
H
Bit 15
Bit 14
Bit 13
Bit 12
Bit 11
Bit 10
Bit 9
Bit 8
-
-
P04
Deum
P06
P07
DI2
DI1
L
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Vh
Vc
Alarm
MinT
Eco
P01
S/W
On/Off
-
On/Off
: unit status (0: Off, 1=On)
-
S/W
: operation mode (0: S=cooling,1:W=heating)
-
P01
: “on unit/wall-mounted” parameter
-
Eco
: Economy logic active
-
Min.T
: Minimum Temperature logic selected
-
Alarm
: general alarm indication (activated when any of
the managed alarms is triggered)
-
Vc
: status of digital output Vc
-
Vh
: status of digital output Vh
-
DI1
: logical value of dig. input 1 (the physical status of the
input depends on the associated logic)
-
DI2
: logical value of dig. input 2 (the physical status of the
input depends on the associated logic)
-
P07
: “DIN 2 Logic” parameter
-
P06
: “DIN 1 Logic” parameter
-
Dehum
: dehumidi
fi
cation ON (0:no, 1:yes)
-
P04
: “water probe present” parameter
■
“SPEED” REGISTER
: current operating speed of the
indoor unit
- 0: fan OFF
- 1: extra-low speed
- 2: low speed
- 3: medium speed
- 4: high speed
■
“AIR TEMPERATURE” REGISTER
: room temperature
read by the controller and shown on the display (N.B.:
this temperature corresponds to the reading of the remote
probe if the controller is located on the unit, or the read-
ing of the internal probe in the case of a wall-mounted
controller and remote probe disconnected)
■
“HUMIDITY” REGISTER
: room humidity read by the
controller via the probe associated with the temperature
probe used
■
“WATER TEMPERATURE” REGISTER
: value read by the
water probe (SW)
■
“P00”
Register: “Controller con
fi
guration” parameter
■
“T. ACTIVE SETPOINT”
Register: setpoint used for tem-
perature control
■
“T. USER SETPOINT”
Register: setpoint programmed by
the user (it may differ from the active setpoint due to cor-
rections based on economy logics,…or use of the setpoint
imposed by the supervision software)
■
“LCD VERSION”
Register : de
fi
nes the controller type and
software version installed (0xHHSS: HH: ASCII character,
SS:sw version)
Thermostat OFF
Thermostat ON
Summary of Contents for FWEC2
Page 2: ...1 2 5 3 4...
Page 3: ...8 9 6 7...
Page 4: ...NOTES...
Page 27: ......
Page 39: ......
Page 51: ......
Page 63: ......
Page 75: ......
Page 87: ......
Page 99: ......
Page 111: ......
Page 123: ......
Page 125: ...NOTES...
Page 126: ......
Page 127: ...FC66002557 UT66000887 3 4...
Page 128: ...UT66000888 UT66000889 5 6...
Page 129: ......
Page 130: ......
Page 131: ......
Page 132: ...Zandvoordestraat 300 B 8400 Oostende Belgium FC66002764...