Installation and operation manual
8
FWEC2
Advanced electronic controller
FC66002764
When temperature exceeds 10°C the thermostat will resume
the
Off
status.
N.B.
: Any
Off
command from digital input will disable this
logic
DISPLAY
The display shows the following information
■
Minimum temperature control selected: symbol
■
Minimum temperature control enabled:
DEFR
DEHUMIDIFICATION
The dehumidi
fi
cation function, enabled only in the cooling
mode, activates operation of the indoor unit in order to achieve
a 10% reduction in the level of humidity present in the room
at the time the function itself was selected.
SELECTION
Dehumidi
fi
cation can be selected/unselected in the Cooling
mode by simultaneously pressing the
buttons. If
the water probe (
P04
=0) or the remote humidity probe is not
available, in cases where the controller is installed directly
on the unit (
P08
=0), selection will not be enabled. If selected,
the dead band for automatic switching on the air side will be
brought to 5°
LOGIC
Once selected, the dehumidi
fi
cation logic sets the target hu-
midity level as the humidity present at the time the function
was selected minus 10%. Where the room humidity is less
than 40% the target level will be set at 30%.
The fan will be forced to run at low speed or, if the temperature
is much higher than the setpoint, at medium speed.
In order to bring the humidity to the set value, the fan (and
valve, if present) will be activated even if the room temperature
has already reached the programmed setpoint (indicated on
the display by the symbol 3). Should the room temperature
fall too far below this threshold, the logic will be temporarily
inhibited.
WATER CONTROL
Enabling of the dehumidi
fi
cation function is tied to the water
temperature. The related enabling logic is described below
If enabling conditions do not exist, the dehumidi
fi
cation func-
tion will be temporarily inhibited.
The same will occur in the event that the probe is discon-
nected.
N.B.
: once the target level of humidity is reached or the
controller is switched
off
, the dehumidify option will be
unselected
DISPLAY
The display shows the following information:
■
Dehumidifi cation ON:
symbol lit
■
Dehumidifi cation temporarily inhibited
:
fl
ashing symbol
ALARMS
This control manages two types of alarms:
■
Serious Alarms
: cause the forced switching off of the
thermostat
■
Non-serious Alarms
: do not cause the forced switching
off of the thermostat, but disable possible critical func-
tions
SERIOUS ALARMS
■
Code
A01
= error of external air temperature sensor (in case
of on-board thermostat)
■
Code
A02
= error of internal air temperature sensor (in case
of wall mounted thermostat and disconnected external air
temperature sensor)
Min. speed
Med. speed
Air temp.
Inhibited
Water temp.
Alarm code
Summary of Contents for FWEC2
Page 2: ...1 2 5 3 4...
Page 3: ...8 9 6 7...
Page 4: ...NOTES...
Page 27: ......
Page 39: ......
Page 51: ......
Page 63: ......
Page 75: ......
Page 87: ......
Page 99: ......
Page 111: ......
Page 123: ......
Page 125: ...NOTES...
Page 126: ......
Page 127: ...FC66002557 UT66000887 3 4...
Page 128: ...UT66000888 UT66000889 5 6...
Page 129: ......
Page 130: ......
Page 131: ......
Page 132: ...Zandvoordestraat 300 B 8400 Oostende Belgium FC66002764...