Installation and operation manual
2
FWEC2
Advanced electronic controller
FC66002764
ACTIVE KEY COMBINATIONS
With
OFF
thermostat: access to the parameter con
fi
guration
procedure
With
ON
thermostat: display of current water temperature
Selection of Minimum air temperature function
Selection of dehumidify option
BOARD CONFIGURATION
The board can be con
fi
gured according to the type of unit/
system to be governed by changing some parameters.
PARAMETER LIST
■
P00
= controller configuration (see “Available
con
fi
gurations”) to select the type of unit to be managed.
■
P01
= type of controller installation
-
000
: on the unit
-
001
: wall mounted
■
P02
= Modbus address (in order for the change in this
parameter to become active (excepting in the case of
internal transfer between values, it is necessary to switch the
power off and back on again at the end of programming)
-
0
: serial communication disabled
-
1-247
: slave
-
255
: master
■
P03
= neutral zone [20-50°C/10]; parameter used in case of
con
fi
gurations with automatic cooling/heating changeover
according to air temperature.
■
P04
= water sensor
-
0
: not available
-
1
: available
Based on the set value, the sensor alarm and the electrical
heater functions will be controlled
■
P05
= Con
fi
guration logic for use of digital inputs 1 and
2:
-
0
: DIN1 = -
DIN2 = -
-
1
: DIN1 = -
DIN2 = OnOff
-
2
: DIN1 = Sum/Win DIN2 = -
-
3
: DIN1 = Eco
DIN2 = -
-
4
: DIN1 = Sum/Win DIN2 = On/Off
-
5
: DIN1 = Eco
DIN2 = On/Off
-
6
: DIN1 = Sum/Win DIN2 = Eco
■
P06
= logic for use of digital input 1:
-
0
: [open/closed] = [Cooling/Heating] = [-/ECO]
-
1
: [open/closed] = [Heating/Cooling] = [ECO/-]
■
P07
= logic for use of digital input 2:
-
0
: [open/closed] = [OFF/ON] = [-/ECO]
-
1
: [open/closed] = [On/Off] = [ECO/-]
■
P08
= Remote humidity sensor
-
0
: not available
-
1
: available
Based on the set value, the associated probe alarm will
be triggered accordingly.
PARAMETER CONFIGURATION PROCEDURE
■
Switch the thermostat
OFF
■
Push the
keys at the same time
■
Use keys
to modify the display value up to the
password value “
10
”, and press
.
If it is correct, you will have access to the parameters
■
Use keys
to scroll the various parameters (see
“Parameter list” described above)
■
Press
to con
fi
rm the parameter change (the value will
start
fl
ashing)
■
use keys
to change the value
■
Press
to save the new value setting or
to cancel
the modi
fi
cation
■
After completing the modi
fi
cation of the parameters con-
cerned press key
to exit the procedure
N.B.
: the parameter con
fi
guration phase is of limited duration.
Once a certain time has elapsed (around 2 minutes) the
thermostat will switch back into the
Off
status and only
the saved changes will be retained.
level indication :
002
= parameter
selection
Value of selected
parameter
Selected
parameter
P...
level indication:
003
= edit parameter
level indication:
001
= password entry
Summary of Contents for FWEC2
Page 2: ...1 2 5 3 4...
Page 3: ...8 9 6 7...
Page 4: ...NOTES...
Page 27: ......
Page 39: ......
Page 51: ......
Page 63: ......
Page 75: ......
Page 87: ......
Page 99: ......
Page 111: ......
Page 123: ......
Page 125: ...NOTES...
Page 126: ......
Page 127: ...FC66002557 UT66000887 3 4...
Page 128: ...UT66000888 UT66000889 5 6...
Page 129: ......
Page 130: ......
Page 131: ......
Page 132: ...Zandvoordestraat 300 B 8400 Oostende Belgium FC66002764...