background image

4

 

WARNING

•  

During pump down, stop the compressor before removing the refrigerant piping. If the compressor is still running and
stop valve is open during pump-down, air will be sucked in when the refrigerant piping is removed, causing abnormal
pressure in refrigeration cycle, which may result equipment damage and even injury.

•  

During installation, attach the refrigerant piping securely before running the compressor. If the refrigerant pipes are not attached
and the stop valve is open when compressor is running, air will be sucked in when the refrigerant piping is removed, causing
abnormal pressure in refrigeration cycle, which may result equipment damage and even injury.

• Be sure to earth the air conditioner.

Do not earth the unit to a utility pipe, lightning conductor or telephone earth lead. Imperfect earthing may result in
electric shocks.

• Be sure to install an earth leakage breaker. Failure to install an earth leakage breaker may result in electrical shocks, or fi re.

• All electrical wiring must not touch the water piping or any moving parts of the fan motors.

• Confi rm that the unit has been switched OFF before installing or servicing the unit.

• Disconnect from the main power supply before servicing the air conditioner unit.

• DO NOT pull out the power cord when the power is ON.

This may cause serious electrical shocks which may result in fi re hazards.

• Keep the indoor and outdoor units, power cable and transmission wiring, at least 1m from TVs and radios, to prevent distorted

pictures and static.
Depending on the type and source of the electrical waves, static may be heard even when more than 1m away.

• Do not use means to accelerate the defrosting process (if applicable) or to clean, other than those recommended by the

manufacturer.

• The appliance must be stored in a room without continuously operating ignition sources (for example: open fl ames, an

operating gas appliance or an operating electric heater).

• Do not pierce or burn.

• Be aware that refrigerants may not contain an odour.

• The appliance must be installed, operated and stored in a room with a fl oor area larger than Xm

2

 (refer to “Special Precaution

when dealing with R32 Unit”). In case it is not satisfy minimum fl oor area, it requires to install at good ventilation room.

• NOTE: The manufacturer may provide other suitable examples or may provide additional information about the refrigerant

odour.

 

CAUTION

• While following the instructions in this installation manual, install drain piping to ensure proper drainage and insulate piping to

prevent condensation. Improper drain piping may result in indoor water leakage and property damage.

• Tighten the fl are nut according to specifi ed method such as with a torque wrench. If the fl are nut is too tight, it may crack after

prolonged use, causing refrigerant leakage.

• Do not overcharge the unit.

Overcharge will cause over-current or damage to the compressor.

• Ensure that the unit’s panel is closed after service or installation.

Unsecured panels will cause the unit to operate noisily.

• Sharp edges and coil surfaces are potential locations which may cause injury hazards.

Avoid from being in contact with these places.

• Before turning off the power supply set the remote controller’s ON/OFF switch to the “OFF” position to prevent the nuisance

tripping of the unit. If this is not done, the unit’s fans will start turning automatically when power resumes, posing a hazard to
service personnel or the user.

• Make sure to provide for adequate measure in order to prevent the outdoor unit be used as a shelter by small animals. Small

animal making contact with electrical parts can cause malfunctions, smoke or fi re. Please instruct the customer to keep the
area around the unit clean.

• The temperature of refrigerant circuit will be high, please keep the inter-unit wiring away from copper pipes that are not

thermally insulated.

• Only qualifi ed personnel can handle, fi ll, purge and dispose of the refrigerant.

• Do not install the air conditioner in places such as the following:

a. Where there is mist of oil, oil spray or vapour for example a kitchen. Resin parts may deteriorate, and cause them to fall out or

water to leak.

b. Where corrosive gas, such as sulfurous acid gas, is produced. Corrosion of copper pipings or brazed parts may cause the

refrigerant to leak.

c. Where there is machinery which emits electromagnetic waves. Electromagnetic waves may disturb the control system, and

cause malfunction of the equipment.

d. Where fl ammable gases may leak, where carbon fi bre or ignitable dust is suspended in the air or where volatile fl ammables,

such as thinner or gasoline, are handled. If the gas should leak and remained around the air conditioner, it may cause ignition
and a fi re to break out.

• Do not install in places fi lled with smoke, gas, chemicals, etc. There is a possibility that the sensors inside the indoor unit could

detect these and display a refrigerant leak abnormality (only for R32 refrigerant).

• This unit is equipped with a refrigerant leak detector for safety. To be effective, the unit must be electrically powered at all times

after installation, other than short service intervals (only for R32 refrigerant).

1-IMOM-FS-FVFC-RZFC-DAIKIN-EN.indd 6

1-IMOM-FS-FVFC-RZFC-DAIKIN-EN.indd   6

5/14/2020   5:54:00 PM

5/14/2020   5:54:00 PM

Summary of Contents for FVFC71AV16

Page 1: ...or Standing type INDOOR FVFC71AV16 FVFC100AV16 FVFC140AV16 OUTDOOR RZVF71BSV16 RZVF100BSV16 RZMF140BSV16 Page No Installation Manual IDU 01 23 Installation Manual ODU 24 60 R 32 Split Type Air Conditi...

Page 2: ...CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 5 14 2020 5 56 46 PM 5 14 2020 5 56 46 PM...

Page 3: ...ELECTRICAL WIRING CONNECTION 13 6 REFRIGERANT PIPING WORK 14 ABOUT OPERATION 1 CONTROLLER PART NAMES AND FUNCTIONS 18 2 OPERATING INSTRUCTION 19 3 INDICATOR LIGHTS 20 4 TROUBLESHOOTING 21 5 OVERALL C...

Page 4: ...I J K H L G Dimension Model A B C D E F G H I J K L 71A 514 254 1850 676 859 600 270 242 73 77 31 34 100 140A 514 254 1850 676 859 600 350 322 73 77 115 34 1 IMOM FS FVFC RZFC DAIKIN EN indd 2 1 IMOM...

Page 5: ...ithstand the weight of the unit A foundation of insufficient strength may result in the equipment falling and causing injury Electrical work must be performed in accordance with relevant local and nat...

Page 6: ...nsation Improper drain piping may result in indoor water leakage and property damage Tighten the flare nut according to specified method such as with a torque wrench If the flare nut is too tight it m...

Page 7: ...r may drip Does the power supply voltage correspond to that shown on the name plate The unit may malfunction or the component burn out Are wiring and piping correct The unit may malfunction or the com...

Page 8: ...unit or use in room where mineral oil oil vapour or oil steam exist this may cause plastic part to melt or deform as a result of excessive heat or chemical reaction When the unit is used in kitchen k...

Page 9: ...s are secured and the base of the fan coil unit is leveled in both horizontal directions Figure B 50mm or more 50mm or more Please ensure that the following steps are taken The drain pipe slope shall...

Page 10: ...you and 2 lift upward and out Refer Figure C Figure C M4 x 12 Screw Front Panel Grille stopper Intake grille 2 Install the indoor units Method 1 Fix the bracket with the attached screws to the top pa...

Page 11: ...2 during installation Piping and Drain Hose Installation Detach the pipe retainer In case of left or right piping 1 Open the holes on the Right Left side panel Refer to Figure F 2 Pass refrigerant pip...

Page 12: ...pipes and unit wiring through the hole on the bottom frame Figure G Bottom panel Insulation for fitting Pipe retainer Rear panel Knock out hole Drain hose inside the unit Fix using the cable tie Cut h...

Page 13: ...k from the unit Therefore definitely insulate the hose in at least the below two places All hose in the room and inside the unit At connection between the unit s drain hose and building drain pipe 2 A...

Page 14: ...eps below shall be followed 1 Confirm that the unit had been switched off before servicing the unit 2 Use screwdriver to unlock the screw on the intake grille 3 Install the intake grille and screw the...

Page 15: ...nal for connecting wires to the power supply terminal block Connect the wires by matching to the indication on terminal block Refer to the wiring diagram attached on the unit Attach insulation sleeve...

Page 16: ...of the flare Use refrigeration oil for R32 3 Use torque wrenches when tightening the flare nuts to prevent damage to the flare nuts and gas leakage CAUTION Align the centres of both flares and tighte...

Page 17: ...are illegible shall be corrected refrigeration pipe or components are installed in a position where they are unlikely to be exposed to any substance which may corrode refrigerant containing components...

Page 18: ...en charging is complete if not already Extreme care shall be taken not to overfill the refrigeration system Prior to recharging the system it shall be pressure tested with OFN The system shall be leak...

Page 19: ...ll be available and in good working order Hoses shall be complete with leak free disconnect couplings and in good condition Before using the recovery machine check that it is in satisfactory working o...

Page 20: ...6 FAN SPEED CONTROL BUTTON Press the button to active deactivate TURBO function Press the button to select fan speed High Medium Low of your choice 3 SWING BUTTON 7 ON OFF BUTTON Press the button to a...

Page 21: ...limit is set to 20 C to 30 C 68 F to 86 F Pressing both keys simultaneously will toggle the temperature setting between C and F No temperature setting is allowed during FAN mode No set temp display T...

Page 22: ...CH ERROR H6 COMPRESSOR FEEDBACK DETECTION ERROR H7 FAN MOTOR OVERLOADED OVERCURRENT SENSOR ABNORMAL H8 AC CURRENT SENSOR ERROR H9 OUTDOOR AIR THERMISTOR SHORT OPEN J1 PRESSURE SENSOR ERROR J3 COMPRESS...

Page 23: ...rsist after all these verifications please contact the air conditioner unit installer 3 The air flow is too low The air filter is dirty The doors or windows are open The air suction and discharge are...

Page 24: ...a vacuum cleaner or wash in lukewarm water below 40 C with a neutral cleaning detergent 2 Rinse the filter well and dry before placing it back onto the unit 3 Do not use gasoline volatile substances o...

Page 25: ...g 2 4 12 Nakazaki Nishi Kita ku Osaka 530 8323 Japan Tokyo office JR Shinagawa East Bldg 2 18 1 Konan Minato ku Tokyo 108 0075 Japan http www daikin com global Lot 60334 Persiaran Bukit Rahman Putra 3...

Page 26: ...CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 5 14 2020 5 56 46 PM 5 14 2020 5 56 46 PM 24 RZVF71BSV16 RZVF71BSV16 24 26 26 27 30 30 33 34 35 38 39...

Page 27: ...CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 5 14 2020 5 56 46 PM 5 14 2020 5 56 46 PM 25 RZVF71BSV16...

Page 28: ...CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 5 14 2020 5 56 46 PM 5 14 2020 5 56 46 PM 26 RZVF71BSV16...

Page 29: ...CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 5 14 2020 5 56 46 PM 5 14 2020 5 56 46 PM 27...

Page 30: ...CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 5 14 2020 5 56 46 PM 5 14 2020 5 56 46 PM 28...

Page 31: ...CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 5 14 2020 5 56 46 PM 5 14 2020 5 56 46 PM 29...

Page 32: ...CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 5 14 2020 5 56 46 PM 5 14 2020 5 56 46 PM 30 RZVF71BSV16...

Page 33: ...CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 5 14 2020 5 56 46 PM 5 14 2020 5 56 46 PM 31 RZVF71BSV16...

Page 34: ...CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 5 14 2020 5 56 46 PM 5 14 2020 5 56 46 PM 32...

Page 35: ...CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 5 14 2020 5 56 46 PM 5 14 2020 5 56 46 PM 33...

Page 36: ...CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 5 14 2020 5 56 46 PM 5 14 2020 5 56 46 PM 34 RZVF71BSV16 RZVF71BSV16...

Page 37: ...CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 5 14 2020 5 56 46 PM 5 14 2020 5 56 46 PM 35...

Page 38: ...CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 5 14 2020 5 56 46 PM 5 14 2020 5 56 46 PM 36 RZVF71BSV16 RZVF71BSV16...

Page 39: ...CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 5 14 2020 5 56 46 PM 5 14 2020 5 56 46 PM 37 RZVF71BSV16 RZVF71BSV16...

Page 40: ...CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 5 14 2020 5 56 46 PM 5 14 2020 5 56 46 PM 38...

Page 41: ...CVR IMOM FS FVFC RZFC DAIKIN EN indd 3 CVR IMOM FS FVFC RZFC DAIKIN EN indd 3 5 14 2020 5 56 46 PM 5 14 2020 5 56 46 PM 39...

Page 42: ...40 RZVF100BSV16 RZMF140BSV16 RZVF100BSV16 Outdoor Unit High Low 4 15 3 30 UNPACKING PACKING INSTRUCTION OF OUTDOOR UNIT RZMF140BSV16 Design Pressure...

Page 43: ...41...

Page 44: ...42...

Page 45: ...43...

Page 46: ...44...

Page 47: ...45...

Page 48: ...46...

Page 49: ...47 RZVF100BSV16 RZMF140BSV16 RZVF100BSV16 RZMF140BSV16...

Page 50: ...48...

Page 51: ...49...

Page 52: ...50 RZVF100BSV16 RZVF100BSV16 RZMF140BSV16 RZMF140BSV16...

Page 53: ...51 3...

Page 54: ...52 RZVF100BSV16 RZMF140BSV16...

Page 55: ...53 RZVF100BSV16 RZMF140BSV16 RZVF100BSV16 RZMF140BSV16 V V V...

Page 56: ...54...

Page 57: ...will take place for about 3 to 5 minutes Thereafter it will change to heating operation but this is not abnormal In this case the remote controller display will continue to display heating operation T...

Page 58: ...56 RZVF100BSV16 RZMF140BSV16...

Page 59: ...57...

Page 60: ...58 RZVF100BSV16 RZMF140BSV16...

Page 61: ...kid d with EPS by pulling the unit up then remove the polythene product cover by pulling it up 14 Unpacking Packing of the Outdoor Unit 14 1 Unpacking Remove the Top corrugated cardboard sheet with EP...

Page 62: ...unit as shown in figure Fix the straps a on the unit with help of strap fixing machine f as shown in figure Use marked reference for placing straps a b c Strap Starp Cutter Top corrugated cardboard s...

Page 63: ......

Page 64: ...DAIKIN AIRCONDITIONING IND A PVT LTD 12th Floor Building No 9 Tower A DLF Cyber City DLF Phase Ill Gurgaon 122002 Haryana India Tel 91 0124 4555444 Fax 91 0124 4555333 3P754599 1...

Reviews: