INDOOR UNIT INSTALLATION
1
INSTALLATION DIAGRAM
Indoor Unit
Outdoor Unit
Air Discharge
Air Intake
Air Intake
Wrap the insulated pipe with the
finishing tape from bottom to top
Figure A
Air Discharge Louver
Indicator Lights
Air Intake Grille
Air Filters
(Inside Air Intake Grille)
Signal Receiver
2
INSTALLATION CLEARANCE
Standard Mounting
Ensure that the overhead supports are strong enough to hold the weight of the unit. Position the hanger rods (wall
mounting bracket for floor standing), and check for its alignment.
Also, check that the hangers are secured and the base of the fan coil unit is leveled in both horizontal directions.
Figure B
50mm or more
50mm or more
Please ensure that the following steps are taken:
– The drain pipe slope shall be kept at least 1:100.
– Provide clearance for easy servicing and optimal air flow as shown in Figure B.
– The indoor unit must be installed such that there is no short circuit of the cool discharge air with the warm return
air.
– Do not install the indoor unit where there is direct sunlight shining on the unit. The location should be suitable for
piping and drainage installation. The unit must be a large distance away from the door.
1-IMOM-FS-FVFC-RZFC-DAIKIN-EN.indd 9
1-IMOM-FS-FVFC-RZFC-DAIKIN-EN.indd 9
5/14/2020 5:54:00 PM
5/14/2020 5:54:00 PM
Summary of Contents for FVFC71AV16
Page 43: ...41...
Page 44: ...42...
Page 45: ...43...
Page 46: ...44...
Page 47: ...45...
Page 48: ...46...
Page 49: ...47 RZVF100BSV16 RZMF140BSV16 RZVF100BSV16 RZMF140BSV16...
Page 50: ...48...
Page 51: ...49...
Page 52: ...50 RZVF100BSV16 RZVF100BSV16 RZMF140BSV16 RZMF140BSV16...
Page 53: ...51 3...
Page 54: ...52 RZVF100BSV16 RZMF140BSV16...
Page 55: ...53 RZVF100BSV16 RZMF140BSV16 RZVF100BSV16 RZMF140BSV16 V V V...
Page 56: ...54...
Page 58: ...56 RZVF100BSV16 RZMF140BSV16...
Page 59: ...57...
Page 60: ...58 RZVF100BSV16 RZMF140BSV16...
Page 63: ......