background image

3

DAIKIN AIR CONDITIONER

INSTALLATION MANUAL

Read the precautions in this manual 
carefully before operating the unit.

This appliance is filled with R32.

• The precautions described herein are classifi ed as WARNING and CAUTION.

They both contain important information regarding safety. Be sure to observe all precautions without fail.

• Meaning of WARNING and CAUTION notices.

WARNING

Failure to follow these instructions properly may result in personal injury or loss of life.

CAUTION

Failure to observe these instructions properly may result in property damage or personal injury, 
which may be serious depending on the circumstances.

• The safety marks shown in this manual have the following meanings:

Be sure to follow the instructions.

Be sure to establish an earth connection.

Never attempt.

• After completing installation, conduct a trial operation to check for faults and explain to the customer how to operate

the air conditioner and take care of it with the aid of operation manual.

 

WARNING

Ask your dealer or qualifi ed person to carry out installation work. Do not attempt to install the air conditioner yourself. Improper
installation may result in water leakage, electric shocks or fi re.

• This appliance is intended to be used by expert or trained users in shops, in light industry and on farms, or for commercial use

by lay persons.

• This appliance is not intended for use by persons, including children, with reduced physical, sensory or mental capabilities, or

lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by
a person responsible for their safety.

• Children should be supervised to ensure that they do not play with the appliance.

• Install the air conditioner according to the instructions given in this manual. Incomplete installation may cause water leakage,

electrical shock, or fi re.

• Be sure to use only the specifi ed accessories and parts for installation work. Failure to use the specifi ed parts may result in the

unit falling, water leakage, electric shocks or fi re.

• Install the air conditioner on a foundation strong enough to withstand the weight of the unit. A foundation of insuffi cient

strength may result in the equipment falling and causing injury.

• Electrical work must be performed in accordance with relevant local and national regulations and with instructions in this

installation manual. Be sure to use a dedicated power supply circuit only. Insuffi ciency of power circuit capacity and improper
workmanship may result in electric shocks or fi re.

• Be sure to use a dedicated power circuit. Never use a power supply shared by another appliance.

• Use a cable of suitable length. Do not use tapped wires or an extension lead, as this may cause overheating, electric shocks

or fi re.

• Make sure that all wiring is secured, the specifi ed wires are used, and that there is no strain on the terminal connections or

wires. Improper connections or securing of wires may result in abnormal heat build-up or fi re.

• When wiring the power supply and connecting the wiring between the indoor and outdoor units, position the wires so that

the control box lid can be securely fastened. Improper positoning of the control box lid may result in electric shocks, fi re or
overheating terminals.

• After connecting interconnecting and supply wiring, be sure to shape the cables so that they do not put undue force on the

electrical covers or panels. Install covers over the wires. Incomplete cover installation may cause terminal overheating,
electrical shocks, or fi re.

• When installing or relocating the air conditioner, be sure to bleed the refrigerant circuit to ensure it is free of air, and use only

the specifi ed refrigerant (R32). The presence of air or other foreign matter in the refrigerant circuit cause abnormal pressure
rise, which may result equipment damage and even injury.

• If refrigerant gas leaks during installation, ventilate the area immediately.

Toxic gas may be produced if the refrigerant comes into contact with fi re.

• After completing installation, check for refrigerant gas leakage.

Toxic gas may be produced if the refrigerant gas leaks into the room and comes into contact with a source of fi re,
such as a fan heater, stove or cooker.

• Be sure to switch off the unit before touching any electrical parts.

SAFETY PRECAUTIONS

1-IMOM-FS-FVFC-RZFC-DAIKIN-EN.indd 5

1-IMOM-FS-FVFC-RZFC-DAIKIN-EN.indd   5

5/14/2020   5:53:59 PM

5/14/2020   5:53:59 PM

Summary of Contents for FVFC71AV16

Page 1: ...or Standing type INDOOR FVFC71AV16 FVFC100AV16 FVFC140AV16 OUTDOOR RZVF71BSV16 RZVF100BSV16 RZMF140BSV16 Page No Installation Manual IDU 01 23 Installation Manual ODU 24 60 R 32 Split Type Air Conditi...

Page 2: ...CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 5 14 2020 5 56 46 PM 5 14 2020 5 56 46 PM...

Page 3: ...ELECTRICAL WIRING CONNECTION 13 6 REFRIGERANT PIPING WORK 14 ABOUT OPERATION 1 CONTROLLER PART NAMES AND FUNCTIONS 18 2 OPERATING INSTRUCTION 19 3 INDICATOR LIGHTS 20 4 TROUBLESHOOTING 21 5 OVERALL C...

Page 4: ...I J K H L G Dimension Model A B C D E F G H I J K L 71A 514 254 1850 676 859 600 270 242 73 77 31 34 100 140A 514 254 1850 676 859 600 350 322 73 77 115 34 1 IMOM FS FVFC RZFC DAIKIN EN indd 2 1 IMOM...

Page 5: ...ithstand the weight of the unit A foundation of insufficient strength may result in the equipment falling and causing injury Electrical work must be performed in accordance with relevant local and nat...

Page 6: ...nsation Improper drain piping may result in indoor water leakage and property damage Tighten the flare nut according to specified method such as with a torque wrench If the flare nut is too tight it m...

Page 7: ...r may drip Does the power supply voltage correspond to that shown on the name plate The unit may malfunction or the component burn out Are wiring and piping correct The unit may malfunction or the com...

Page 8: ...unit or use in room where mineral oil oil vapour or oil steam exist this may cause plastic part to melt or deform as a result of excessive heat or chemical reaction When the unit is used in kitchen k...

Page 9: ...s are secured and the base of the fan coil unit is leveled in both horizontal directions Figure B 50mm or more 50mm or more Please ensure that the following steps are taken The drain pipe slope shall...

Page 10: ...you and 2 lift upward and out Refer Figure C Figure C M4 x 12 Screw Front Panel Grille stopper Intake grille 2 Install the indoor units Method 1 Fix the bracket with the attached screws to the top pa...

Page 11: ...2 during installation Piping and Drain Hose Installation Detach the pipe retainer In case of left or right piping 1 Open the holes on the Right Left side panel Refer to Figure F 2 Pass refrigerant pip...

Page 12: ...pipes and unit wiring through the hole on the bottom frame Figure G Bottom panel Insulation for fitting Pipe retainer Rear panel Knock out hole Drain hose inside the unit Fix using the cable tie Cut h...

Page 13: ...k from the unit Therefore definitely insulate the hose in at least the below two places All hose in the room and inside the unit At connection between the unit s drain hose and building drain pipe 2 A...

Page 14: ...eps below shall be followed 1 Confirm that the unit had been switched off before servicing the unit 2 Use screwdriver to unlock the screw on the intake grille 3 Install the intake grille and screw the...

Page 15: ...nal for connecting wires to the power supply terminal block Connect the wires by matching to the indication on terminal block Refer to the wiring diagram attached on the unit Attach insulation sleeve...

Page 16: ...of the flare Use refrigeration oil for R32 3 Use torque wrenches when tightening the flare nuts to prevent damage to the flare nuts and gas leakage CAUTION Align the centres of both flares and tighte...

Page 17: ...are illegible shall be corrected refrigeration pipe or components are installed in a position where they are unlikely to be exposed to any substance which may corrode refrigerant containing components...

Page 18: ...en charging is complete if not already Extreme care shall be taken not to overfill the refrigeration system Prior to recharging the system it shall be pressure tested with OFN The system shall be leak...

Page 19: ...ll be available and in good working order Hoses shall be complete with leak free disconnect couplings and in good condition Before using the recovery machine check that it is in satisfactory working o...

Page 20: ...6 FAN SPEED CONTROL BUTTON Press the button to active deactivate TURBO function Press the button to select fan speed High Medium Low of your choice 3 SWING BUTTON 7 ON OFF BUTTON Press the button to a...

Page 21: ...limit is set to 20 C to 30 C 68 F to 86 F Pressing both keys simultaneously will toggle the temperature setting between C and F No temperature setting is allowed during FAN mode No set temp display T...

Page 22: ...CH ERROR H6 COMPRESSOR FEEDBACK DETECTION ERROR H7 FAN MOTOR OVERLOADED OVERCURRENT SENSOR ABNORMAL H8 AC CURRENT SENSOR ERROR H9 OUTDOOR AIR THERMISTOR SHORT OPEN J1 PRESSURE SENSOR ERROR J3 COMPRESS...

Page 23: ...rsist after all these verifications please contact the air conditioner unit installer 3 The air flow is too low The air filter is dirty The doors or windows are open The air suction and discharge are...

Page 24: ...a vacuum cleaner or wash in lukewarm water below 40 C with a neutral cleaning detergent 2 Rinse the filter well and dry before placing it back onto the unit 3 Do not use gasoline volatile substances o...

Page 25: ...g 2 4 12 Nakazaki Nishi Kita ku Osaka 530 8323 Japan Tokyo office JR Shinagawa East Bldg 2 18 1 Konan Minato ku Tokyo 108 0075 Japan http www daikin com global Lot 60334 Persiaran Bukit Rahman Putra 3...

Page 26: ...CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 5 14 2020 5 56 46 PM 5 14 2020 5 56 46 PM 24 RZVF71BSV16 RZVF71BSV16 24 26 26 27 30 30 33 34 35 38 39...

Page 27: ...CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 5 14 2020 5 56 46 PM 5 14 2020 5 56 46 PM 25 RZVF71BSV16...

Page 28: ...CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 5 14 2020 5 56 46 PM 5 14 2020 5 56 46 PM 26 RZVF71BSV16...

Page 29: ...CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 5 14 2020 5 56 46 PM 5 14 2020 5 56 46 PM 27...

Page 30: ...CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 5 14 2020 5 56 46 PM 5 14 2020 5 56 46 PM 28...

Page 31: ...CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 5 14 2020 5 56 46 PM 5 14 2020 5 56 46 PM 29...

Page 32: ...CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 5 14 2020 5 56 46 PM 5 14 2020 5 56 46 PM 30 RZVF71BSV16...

Page 33: ...CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 5 14 2020 5 56 46 PM 5 14 2020 5 56 46 PM 31 RZVF71BSV16...

Page 34: ...CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 5 14 2020 5 56 46 PM 5 14 2020 5 56 46 PM 32...

Page 35: ...CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 5 14 2020 5 56 46 PM 5 14 2020 5 56 46 PM 33...

Page 36: ...CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 5 14 2020 5 56 46 PM 5 14 2020 5 56 46 PM 34 RZVF71BSV16 RZVF71BSV16...

Page 37: ...CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 5 14 2020 5 56 46 PM 5 14 2020 5 56 46 PM 35...

Page 38: ...CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 5 14 2020 5 56 46 PM 5 14 2020 5 56 46 PM 36 RZVF71BSV16 RZVF71BSV16...

Page 39: ...CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 5 14 2020 5 56 46 PM 5 14 2020 5 56 46 PM 37 RZVF71BSV16 RZVF71BSV16...

Page 40: ...CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 CVR IMOM FS FVFC RZFC DAIKIN EN indd 2 5 14 2020 5 56 46 PM 5 14 2020 5 56 46 PM 38...

Page 41: ...CVR IMOM FS FVFC RZFC DAIKIN EN indd 3 CVR IMOM FS FVFC RZFC DAIKIN EN indd 3 5 14 2020 5 56 46 PM 5 14 2020 5 56 46 PM 39...

Page 42: ...40 RZVF100BSV16 RZMF140BSV16 RZVF100BSV16 Outdoor Unit High Low 4 15 3 30 UNPACKING PACKING INSTRUCTION OF OUTDOOR UNIT RZMF140BSV16 Design Pressure...

Page 43: ...41...

Page 44: ...42...

Page 45: ...43...

Page 46: ...44...

Page 47: ...45...

Page 48: ...46...

Page 49: ...47 RZVF100BSV16 RZMF140BSV16 RZVF100BSV16 RZMF140BSV16...

Page 50: ...48...

Page 51: ...49...

Page 52: ...50 RZVF100BSV16 RZVF100BSV16 RZMF140BSV16 RZMF140BSV16...

Page 53: ...51 3...

Page 54: ...52 RZVF100BSV16 RZMF140BSV16...

Page 55: ...53 RZVF100BSV16 RZMF140BSV16 RZVF100BSV16 RZMF140BSV16 V V V...

Page 56: ...54...

Page 57: ...will take place for about 3 to 5 minutes Thereafter it will change to heating operation but this is not abnormal In this case the remote controller display will continue to display heating operation T...

Page 58: ...56 RZVF100BSV16 RZMF140BSV16...

Page 59: ...57...

Page 60: ...58 RZVF100BSV16 RZMF140BSV16...

Page 61: ...kid d with EPS by pulling the unit up then remove the polythene product cover by pulling it up 14 Unpacking Packing of the Outdoor Unit 14 1 Unpacking Remove the Top corrugated cardboard sheet with EP...

Page 62: ...unit as shown in figure Fix the straps a on the unit with help of strap fixing machine f as shown in figure Use marked reference for placing straps a b c Strap Starp Cutter Top corrugated cardboard s...

Page 63: ......

Page 64: ...DAIKIN AIRCONDITIONING IND A PVT LTD 12th Floor Building No 9 Tower A DLF Cyber City DLF Phase Ill Gurgaon 122002 Haryana India Tel 91 0124 4555444 Fax 91 0124 4555333 3P754599 1...

Reviews: