![Daikin FTY25GXV1 Service Manual Download Page 62](http://html.mh-extra.com/html/daikin/fty25gxv1/fty25gxv1_service-manual_2459572062.webp)
SiBE01-829
Troubleshooting
Service Diagnosis
51
Troubleshooting
Check No.06
Refer to P.55
Check No.07
Refer to P.56
Check No.09
Refer to P.57
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Open the stop valve.
Check the stop valve.
YES
NO
Is it opened?
(R8506)
Replace the fan motor.
Repair the connector or fan
motor lead wires.
Replace the heat exchanger
thermistor.
Replace PCB.
Correct the connection.
Change the air outlet grille
position.
Clean the heat exchanger.
Change the installation
location.
Check the installation space.
Check the connector connection.
Abnormal
Normal
YES
Normal
Normal
Abnormal
NO
Abnormal
Is it normal?
Judgment
Check No. 09
Check the outdoor fan.
Check No. 07
Check the installation
condition.
Check No. 06
Check the heat exchanger
thermistor.
Summary of Contents for FTY25GXV1
Page 1: ...SiBE01 829 Applied Models Non Inverter Pair Heat Pump SPLIT Pair Wall Mounted Type G Series ...
Page 5: ...SiBE01 829 iv Table of Contents Index i Drawings Flow Charts iii ...
Page 11: ...Introduction SiBE01 829 x ...
Page 12: ...SiBE01 829 List of Function 1 Part 1 List of Function 1 Functions 2 ...
Page 15: ...Functions SiBE01 829 4 List of Function ...
Page 16: ...SiBE01 829 Specifications 5 Part 2 Specifications 1 Specifications 6 ...
Page 19: ...Specifications SiBE01 829 8 Specifications ...
Page 49: ...Instructions SiBE01 829 38 Operation Manual ...
Page 69: ...Check SiBE01 829 58 Service Diagnosis ...
Page 111: ...Outdoor Unit SiBE01 829 100 Removal Procedure ...
Page 119: ...Wiring Diagrams SiBE01 829 108 Appendix ...