Service Diagnosis
5.2
Installation Condition Check
Check No.07
Installation condition check
Normal
(R8508)
Abnormal
YES
YES
YES
NO
NO
NO
Is the heat exchanger
very dirty?
Check the
allowable dimensions
of the air suction and
discharge area.
Is the
airflow blocked by
obstacles or winds blowing
in the opposite
direction?
Does the
discharged air from
other outdoor unit cause an
increase of the suction
air temperature?
Change the position of the air
discharge grille or the
installation location.
Change the position of the air
discharge grille or the
installation location.
Change the installation
location or direction.
Check the outside air
temperature (temperature of air
taken in by the outdoor unit).
(The outside air temperature
shall be 46˚C or lower.)
Clean the heat exchanger.
Summary of Contents for FTY25GXV1
Page 1: ...SiBE01 829 Applied Models Non Inverter Pair Heat Pump SPLIT Pair Wall Mounted Type G Series ...
Page 5: ...SiBE01 829 iv Table of Contents Index i Drawings Flow Charts iii ...
Page 11: ...Introduction SiBE01 829 x ...
Page 12: ...SiBE01 829 List of Function 1 Part 1 List of Function 1 Functions 2 ...
Page 15: ...Functions SiBE01 829 4 List of Function ...
Page 16: ...SiBE01 829 Specifications 5 Part 2 Specifications 1 Specifications 6 ...
Page 19: ...Specifications SiBE01 829 8 Specifications ...
Page 49: ...Instructions SiBE01 829 38 Operation Manual ...
Page 69: ...Check SiBE01 829 58 Service Diagnosis ...
Page 111: ...Outdoor Unit SiBE01 829 100 Removal Procedure ...
Page 119: ...Wiring Diagrams SiBE01 829 108 Appendix ...