Indoor Unit
SiBE01-829
60
Removal Procedure
1. Indoor Unit
1.1
Removal of
Air Filter
Procedure
Warning
Be sure to wait 10 minutes or more after turning off all power
supplies before disassembling work.
Step
Procedure
Points
1. Appearance feature
Warning
Dangerous: High voltage
A high voltage is applied to
all the electric circuits of this
product including
thermistors.
When a signal from the
remote controller is
received, the receiving tone
sounds and the operation
lamp flickers immediately to
confirm the signal reception.
2. Removing the
air filter
1
Put your fingers on the
right and left projections
of the front panel, and
open the panel to the
position where it will
stop.
2
Slightly push up the
knob at the center of
the air filter.
The air filter is not marked
for difference between the
right and left sides.
The air filter can be set
easily by inserting it along
the guides.
Insert the air filter with the
“FRONT”-marked face up.
Be sure to insert the hooks
(at 2 lower positions) when
mounting the air filter.
Room temperature thermistor
(R8566)
Signal receiver
ON/OFF switch
(Test run switch)
Operation
lamp
TIMER
lamp
(R8567)
(R8568)
Hooks
(R8569)
Summary of Contents for FTY25GXV1
Page 1: ...SiBE01 829 Applied Models Non Inverter Pair Heat Pump SPLIT Pair Wall Mounted Type G Series ...
Page 5: ...SiBE01 829 iv Table of Contents Index i Drawings Flow Charts iii ...
Page 11: ...Introduction SiBE01 829 x ...
Page 12: ...SiBE01 829 List of Function 1 Part 1 List of Function 1 Functions 2 ...
Page 15: ...Functions SiBE01 829 4 List of Function ...
Page 16: ...SiBE01 829 Specifications 5 Part 2 Specifications 1 Specifications 6 ...
Page 19: ...Specifications SiBE01 829 8 Specifications ...
Page 49: ...Instructions SiBE01 829 38 Operation Manual ...
Page 69: ...Check SiBE01 829 58 Service Diagnosis ...
Page 111: ...Outdoor Unit SiBE01 829 100 Removal Procedure ...
Page 119: ...Wiring Diagrams SiBE01 829 108 Appendix ...