6 Piping installation

Installation manual

7

FTXTJ-A(W)(B)
Daikin room air conditioner
3P695637-3C – 2023.03

6

Piping installation

6.1

Preparing refrigerant piping

6.1.1

Refrigerant piping requirements

CAUTION

Piping  and  joints  of  a  split  system  shall  be  made  with
permanent  joints  when  inside  an  occupied  space  except
joints directly connecting the piping to the indoor units.

NOTICE

The  piping  and  other  pressure-containing  parts  shall  be
suitable  for  refrigerant.  Use  phosphoric  acid  deoxidised
seamless copper for refrigerant piping.

▪ Foreign materials inside pipes (including oils for fabrication) must

be ≤30 mg/10 m.

Refrigerant piping diameter

Use the same diameters as the connections on the outdoor units:

Liquid piping

Gas piping

Ø6.4 mm

Ø9.5 mm

Refrigerant piping material

Piping material:

 phosphoric acid deoxidised seamless copper

Flare connections:

 Only use annealed material.

Piping temper grade and thickness:

Outer diameter

(Ø)

Temper grade

Thickness (t)

(a)

6.4 mm (1/4")

Annealed (O)

≥0.8 mm

t

Ø

9.5 mm (3/8")

Annealed (O)

(a)

Depending on the applicable legislation and the maximum
working pressure of the unit (see "PS High" on the unit name
plate), larger piping thickness might be required.

6.1.2

Refrigerant piping insulation

▪ Use polyethylene foam as insulation material:

▪ with a heat transfer rate between 0.041 and 0.052 W/mK (0.035

and 0.045 kcal/mh°C)

▪ with a heat resistance of at least 120°C

▪ Insulation thickness

Pipe outer diameter

p

)

Insulation inner

diameter (Ø

i

)

Insulation thickness

(t)

6.4 mm (1/4")

8~10 mm

≥10 mm

9.5 mm (3/8")

10~14 mm

≥13 mm

Ø

i

Ø

i

t

Ø

p

Ø

p

If  the  temperature  is  higher  than  30°C  and  the  humidity  is  higher
than RH 80%, the thickness of the insulation materials should be at
least  20  mm  to  prevent  condensation  on  the  surface  of  the
insulation.

6.2

Connecting the refrigerant piping

DANGER: RISK OF BURNING/SCALDING

6.2.1

To connect the refrigerant piping to the
indoor unit

WARNING: MILDLY FLAMMABLE MATERIAL

The refrigerant inside this unit is mildly flammable.

Pipe length

. Keep refrigerant piping as short as possible.

1

Connect refrigerant piping to the unit using 

flare connections

.

2

Wrap  the  refrigerant  piping  connection  using  vinyl  tape,
overlapping  at  least  half  the  width  of  the  tape  with  each  turn.
Keep  the  slit  of  the  heat  insulation  pipe  cover  up.  Avoid
wrapping the tape too tight.

b

a

c d

e

f

e

a

Heat insulation pipe cover (on the indoor unit side)

b

Flare connections

c

Liquid pipe (with insulation) (field supply)

d

Gas pipe (with insulation) (field supply)

e

Slit on heat insulation pipe cover facing up

f

Vinyl tape (field supply)

3

Insulate 

the  refrigerant  piping,  interconnection  cable  and  drain

hose  on  the  indoor  unit:  See 

"8.1  To  insulate  the  drain  piping,

refrigerant piping and interconnection cable"

 [

4

 9].

NOTICE

Make  sure  to  insulate  all  refrigerant  piping.  Any  exposed
piping might cause condensation.

6.2.2

To check refrigerant piping joints for leaks
after charging refrigerant

1

Perform  the  leak  tests  according  to  instructions  in  the  outdoor
unit installation manual.

2

Charge refrigerant.

3

Check for refrigerant leaks after charging (see below).

Tightness test of field-made refrigerant joints indoors

1

Use a leakage test method with a minimum sensitivity of 5 g of
refrigerant/year.  Test  leaks  using  a  pressure  of  at  least  0.25
times  the  maximum  working  pressure  (see  "PS  High"  on  the
unit nameplate).

If a leak is detected

1

Recover the refrigerant, repair the joint, and repeat the test.

7

Electrical installation

DANGER: RISK OF ELECTROCUTION

WARNING

ALWAYS use multicore cable for power supply cables.

WARNING

Use  an  all-pole  disconnection  type  breaker  with  at  least
3  mm  between  the  contact  point  gaps  that  provides  full
disconnection under overvoltage category III.

Summary of Contents for FTXTJ30A2V1BW

Page 1: ...Installation manual Daikin room air conditioner English Installation manual Daikin room air conditioner FTXTJ30A2V1BW FTXTJ30A2V1BB...

Page 2: ...olving problems based on error codes 11 12 Disposal 11 13 Technical data 12 13 1 Wiring diagram 12 13 1 1 Unified wiring diagram legend 12 1 About the documentation 1 1 About this document WARNING Mak...

Page 3: ...ST comply with the applicable legislation WARNING If the power supply has a missing or wrong N phase equipment might break down Establish proper earthing Do NOT earth the unit to a utility pipe surge...

Page 4: ...g persons using cardiac pacemakers or defibrillators This product may cause electromagnetic interference Auto control equipment E g automatic doors or fire alarm equipment This product may cause faul...

Page 5: ...a a a 605 mm a Recommended mounting plate fixing spots h Position for tape measure at symbol b Pocket for the pipe port cover i Drain hose c Use tape measure as shown j Liquid pipe d Tabs for placing...

Page 6: ...port cover here for right side piping b Remove the pipe port cover here for right bottom piping 5 3 2 To connect the piping on left side left back or left bottom INFORMATION The factory default is ri...

Page 7: ...on 6 2 Connecting the refrigerant piping DANGER RISK OF BURNING SCALDING 6 2 1 To connect the refrigerant piping to the indoor unit WARNING MILDLY FLAMMABLE MATERIAL The refrigerant inside this unit i...

Page 8: ...cause malfunctions smoke or fire NOTICE Keep the power line and transmission line apart from each other Transmission wiring and power supply wiring may cross but may NOT run parallel In order to avoid...

Page 9: ...as pipe e Drain pipe f Interconnection wire g Insulation tape h Vinyl tape 1 After the drain piping refrigerant piping and the electrical wiring are finished Wrap refrigerant piping interconnection ca...

Page 10: ...e sure drainage flows smoothly Possible consequence Condensate water might drip The system is properly earthed and the earth terminals are tightened The fuses or locally installed protection devices a...

Page 11: ...select channels of the indoor unit infrared receiver 11 Troubleshooting 11 1 Solving problems based on error codes Fault diagnosis by the wireless remote control If the unit runs into a problem you ca...

Page 12: ...E HA HE HL HN HR MR _A MR _B S U V W X A K R_ NE Connection connector D V D Diode DB Diode bridge DS DIP switch E H Heater FU F U for characteristics refer to PCB inside your unit Fuse FG Connector f...

Page 13: ...manual 13 FTXTJ A W B Daikin room air conditioner 3P695637 3C 2023 03 Symbol Meaning X Terminal X M Terminal strip block Y E Electronic expansion valve coil Y R Y S Reversing solenoid valve coil Z C F...

Page 14: ......

Page 15: ......

Page 16: ...3P695637 3C 2023 03 Copyright 2023 Daikin Verantwortung f r Energie und Umwelt...

Reviews: