5 Unit installation

Installation manual

5

FTXTJ-A(W)(B)
Daikin room air conditioner
3P695637-3C – 2023.03

(mm)

50

30

50

Note: 

Make  sure  that  there  are  no  obstacles  within  500  mm  under

the  infrared  signal  receiver.  They  may  influence  reception
performance of the wireless remote control.

5.2

Mounting the indoor unit

5.2.1

To install the mounting plate

1

Install the mounting plate temporarily.

2

Level the mounting plate.

3

Mark  the  centres  of  the  drilling  points  on  the  wall  using  a  tape
measure. Position the end of tape measure at symbol " ".

4

Finish the installation by securing the mounting plate on the wall
using M4×25L screws (field supply).

INFORMATION

The removed pipe port cover can be kept in the mounting
plate pocket.

 605

17

Ø 65

Ø 65

150

155

44.5

44.5

 l: 779

101

290

± 555 mm

±  610 mm

m: 900

60.5

60.5

b

c

a

a

f

f

a

h

e

d

d

a

k

g

i j

a

a

a

a

±  605 mm

a

Recommended mounting plate fixing spots

h

Position for tape measure at symbol " "

b

Pocket for the pipe port cover

i

Drain hose

c

Use tape measure as shown

j

Liquid pipe

d

Tabs for placing a spirit level

k

Gas pipe

e

Unit center

l

Outline of the unit back side

f

Hole for embedded piping Ø65 mm

m

Outline of the unit front panel

g

Value for tape measure

5.2.2

To drill a wall hole

CAUTION

For walls containing a metal frame or a metal board, use a
wall  embedded  pipe  and  wall  cover  in  the  feed-through
hole to prevent possible heat, electrical shock, or fire.

NOTICE

Be  sure  to  seal  the  gaps  around  the  pipes  with  sealing
material (field supply), in order to prevent water leakage.

1

Bore  a  65  mm  large  feed-through  hole  in  the  wall  with  a
downward slope towards the outside.

2

Insert a wall embedded pipe into the hole.

3

Insert a wall cover into the wall pipe.

Ø65

a b

c

a

Wall embedded pipe

b

Putty

c

Wall hole cover

4

After  completing  wiring,  refrigerant  piping  and  drain  piping,  do
NOT forget to seal the gap with putty.

Summary of Contents for FTXTJ30A2V1BW

Page 1: ...Installation manual Daikin room air conditioner English Installation manual Daikin room air conditioner FTXTJ30A2V1BW FTXTJ30A2V1BB...

Page 2: ...olving problems based on error codes 11 12 Disposal 11 13 Technical data 12 13 1 Wiring diagram 12 13 1 1 Unified wiring diagram legend 12 1 About the documentation 1 1 About this document WARNING Mak...

Page 3: ...ST comply with the applicable legislation WARNING If the power supply has a missing or wrong N phase equipment might break down Establish proper earthing Do NOT earth the unit to a utility pipe surge...

Page 4: ...g persons using cardiac pacemakers or defibrillators This product may cause electromagnetic interference Auto control equipment E g automatic doors or fire alarm equipment This product may cause faul...

Page 5: ...a a a 605 mm a Recommended mounting plate fixing spots h Position for tape measure at symbol b Pocket for the pipe port cover i Drain hose c Use tape measure as shown j Liquid pipe d Tabs for placing...

Page 6: ...port cover here for right side piping b Remove the pipe port cover here for right bottom piping 5 3 2 To connect the piping on left side left back or left bottom INFORMATION The factory default is ri...

Page 7: ...on 6 2 Connecting the refrigerant piping DANGER RISK OF BURNING SCALDING 6 2 1 To connect the refrigerant piping to the indoor unit WARNING MILDLY FLAMMABLE MATERIAL The refrigerant inside this unit i...

Page 8: ...cause malfunctions smoke or fire NOTICE Keep the power line and transmission line apart from each other Transmission wiring and power supply wiring may cross but may NOT run parallel In order to avoid...

Page 9: ...as pipe e Drain pipe f Interconnection wire g Insulation tape h Vinyl tape 1 After the drain piping refrigerant piping and the electrical wiring are finished Wrap refrigerant piping interconnection ca...

Page 10: ...e sure drainage flows smoothly Possible consequence Condensate water might drip The system is properly earthed and the earth terminals are tightened The fuses or locally installed protection devices a...

Page 11: ...select channels of the indoor unit infrared receiver 11 Troubleshooting 11 1 Solving problems based on error codes Fault diagnosis by the wireless remote control If the unit runs into a problem you ca...

Page 12: ...E HA HE HL HN HR MR _A MR _B S U V W X A K R_ NE Connection connector D V D Diode DB Diode bridge DS DIP switch E H Heater FU F U for characteristics refer to PCB inside your unit Fuse FG Connector f...

Page 13: ...manual 13 FTXTJ A W B Daikin room air conditioner 3P695637 3C 2023 03 Symbol Meaning X Terminal X M Terminal strip block Y E Electronic expansion valve coil Y R Y S Reversing solenoid valve coil Z C F...

Page 14: ......

Page 15: ......

Page 16: ...3P695637 3C 2023 03 Copyright 2023 Daikin Verantwortung f r Energie und Umwelt...

Reviews: