Trial Operation and Testing

1.

Trial operation and testing

1-1 Measure the supply voltage and make sure that it falls in the specified range.
1-2 Trial operation should be carried out in either cooling or heating mode.

• In cooling mode, select the lowest programmable temperature; in heating mode, select the highest programmable 

temperature.
1) Trial operation may be disabled in either mode depending on the room temperature.

Use the remote controller for trial operation as described below.

2) After trial operation is complete, set the temperature to a normal level (26°C to 28°C in cooling mode, 20°C to 24°C 

in heating mode).

3) For protection, the system disables restart operation for 3 minutes after it is turned off.

1-3 Carry out the test operation in accordance with the operation manual to ensure that all functions and parts, 

such as louver movement, are working properly.

• The air conditioner requires a small amount of power in its standby mode.  If the system is not to be used for some 

time after installation, shut off the circuit breaker to eliminate unnecessary power consumption.

• If the circuit breaker trips to shut off the power to the air conditioner, the system will restore the original operation 

mode when the circuit breaker is opened again.

2.

Test items 

* If the 

 is not displayed, make sure not to cut the switching 

jumper (J8) for cooling operation when cutting the address 
jumper.
If it has been cut, replace the remote controller.

Trial operation from remote controller

1) Press “ON/OFF” button to turn on the system.
2) Press “TEMP” button (2 locations) and “MODE” button at the same time.
3) Press “TEMP” button and select “ ”.
4) Press “MODE” button.
5) Trial operation terminates in approx. 30 minutes and switches into normal mode. To quit a trial operation, press 

“ON/OFF” button.

Test items

Symptom

(diagnostic display on RC)

Check

Indoor and outdoor units are installed properly on solid bases.

Fall, vibration, noise

No refrigerant gas leaks.

Incomplete cooling/heating function

Refrigerant gas and liquid pipes and indoor drain hose extension are 
thermally insulated.

Water leakage

Draining line is properly installed.

Water leakage

System is properly earthed.

Electrical leakage

The specified wires are used for inter-unit wiring.

Inoperative or burn damage

Indoor or outdoor unit’s air inlet or air outlet has clear path of air.

Incomplete cooling/heating function

Stop valves are opened.

Incomplete cooling/heating function

Indoor unit properly receives remote control commands.

Inoperative

 will appear when the MODE button is pressed.*

No heating

Jumper (J8)

3PEN387973-3D.book  Page 13  Monday, November 30, 2015  4:18 PM

Summary of Contents for FTXM-K

Page 1: ...TIONER INSTALLATION MANUAL R32 Split Series English Deutsch Fran ais Nederlands Espa ol Italiano E Portugues Pycc T rk e MODELS FTXM35K3V1B FTXM42K3V1B FTXM50K3V1B 3PEN387973 3D book Page 1 Monday Nov...

Page 2: ...nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acordo com o Certificado C 09 A B C 10 Bem rk som anf rt i A...

Page 3: ...erheating electric shocks or fire Make sure that all wiring is secured the specified wires are used and that there is no strain on the terminal connections or wires Improper connections or securing of...

Page 4: ...controller signals are properly received by the indoor unit within 7m CAUTION Do not install the air conditioner at any place where there is a danger of flammable gas leakage In the event of a gas le...

Page 5: ...ks Lightly pull the front grille toward you with one hand and push down on the hooks with the fingers of your other hand When there is no work space because the unit is close to ceiling CAUTION Be sur...

Page 6: ...The service lid is removable 1 Remove the service lid screw 2 Pull out the service lid diagonally down in the direction of the arrow 3 Pull down The mounting plate should be installed on a wall which...

Page 7: ...ver into wall pipe 4 After completing refrigerant piping wiring and drain piping caulk pipe hole gap with putty 3 Installing the indoor unit In the case of bending or curing refrigerant pipes keep the...

Page 8: ...gs at the top of the indoor unit as a guide 4 Open the front panel then open the service lid Refer to preparation before installation 5 Pass the inter unit wire from the outdoor unit through the feed...

Page 9: ...the insulation fixing screw on the right and remove the drain hose 2 Remove the drain plug on the left side and attach it to the right side 3 Insert the drain hose and tighten with included insulatio...

Page 10: ...ECEIVER Signal receiver BZ Buzzer C101 C102 Capacitor FG Frame ground F1U Fuse 3 15A H1P H3P Pilot lamp MR10 Magnetic relay M1F Fan motor M1S M3S Swing motor PCB1 PCB4 Printed circuit board R1T R2T Th...

Page 11: ...indoor unit Doing so may cause electric shock or fire 5 When connecting to an HA system Wired remote controller central remote controller etc 1 Remove the metal plate electrical wiring cover Refer to...

Page 12: ...below 1 Lean the metal plate electrical wiring cover as shown in the figure and attach tab 1 on the lower side to the electrical wiring box 2 Attach tab 2 on the lower side of the metal plate electric...

Page 13: ...on flared part Prevent mineral oil from getting into the system as this would reduce the lifetime of the units Never use piping which has been used for previous installations Only use parts which are...

Page 14: ...insulation materials that will withstand this temperature 2 Be sure to insulate both the gas and liquid piping and to provide insulation dimensions as below 3 Use separate thermal insulation for gas a...

Page 15: ...l operation mode when the circuit breaker is opened again 2 Test items If the is not displayed make sure not to cut the switching jumper J8 for cooling operation when cutting the address jumper If it...

Page 16: ...3P387973 3D 2015 11 Copyright 2014 Daikin 3PEN387973 3D book Page 1 Monday November 30 2015 4 18 PM...

Reviews: