11

Indoor Unit Installation

6.

Drain piping

1) Connect the drain hose, as described right.

2) Remove the air filters and pour some water into the drain pan to check the water flows 

smoothly.

3) If drain hose extension or embedded drain piping is required, use appropriate parts that match the hose front end.

[Figure of hose front end]

4) When extending the drain hose, use a commercially 

available extension hose with an inner diameter of 
16mm. Be sure to thermally insulate the indoor section of 
the extension hose.

5) When connecting a rigid polyvinyl chloride pipe 

(nominal diameter 13mm) directly to the drain 
hose attached to the indoor unit as with 
embedded piping work, use any commercially 
available drain socket (nominal diameter 13mm) 
as a joint.

Refrigerant Piping Work

1.

Flaring the pipe end 

1) Cut the pipe end with a pipe cutter.
2) Remove burrs with the cut surface facing 

downward so that the chips do not enter the pipe.

3) Put the flare nut on the pipe.
4) Flare the pipe.
5) Check that the flaring is properly made.

 WARNING

• Do not use mineral oil on flared part.
• Prevent mineral oil from getting into the system as this would reduce the lifetime of the units.
• Never use piping which has been used for previous installations. Only use parts which are delivered with the unit.
• Never install a dryer to this R32 unit in order to guarantee its lifetime.
• The drying material may dissolve and damage the system.
• Incomplete flaring may cause refrigerant gas leakage.

The drain hose should 
be inclined downward.

No trap is permitted.

Do not put the end 
of the hose in water.

Indoor unit 
drain hose

Extension drain hose

Heat insulation tube 
(field supply)

Drain hose supplied 
with the indoor unit

Commercially available drain 
socket 
(nominal diameter 13mm)

Commercially available rigid 
polyvinyl chloride pipe
(nominal diameter 13mm)

Drain hose supplied 
with the indoor unit

A

A

(Cut exactly at 
right angles.)

 

Remove burrs.

Flaring

Set exactly at the position shown below.

Die

0-0.5mm

Clutch-type

Flare tool for 

R410A or R32

1.0-1.5mm

Clutch-type

(Rigid-type)

1.5-2.0mm

Wing-nut type

(Imperial-type)

Conventional flare tool

Flare’s inner surface 
must be flaw-free.

The pipe end must 
be evenly flared in a 
perfect circle.

Make sure that the 
flare nut is fitted.

Check

3PEN387973-3D.book  Page 11  Monday, November 30, 2015  4:18 PM

Summary of Contents for FTXM-K

Page 1: ...TIONER INSTALLATION MANUAL R32 Split Series English Deutsch Fran ais Nederlands Espa ol Italiano E Portugues Pycc T rk e MODELS FTXM35K3V1B FTXM42K3V1B FTXM50K3V1B 3PEN387973 3D book Page 1 Monday Nov...

Page 2: ...nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acordo com o Certificado C 09 A B C 10 Bem rk som anf rt i A...

Page 3: ...erheating electric shocks or fire Make sure that all wiring is secured the specified wires are used and that there is no strain on the terminal connections or wires Improper connections or securing of...

Page 4: ...controller signals are properly received by the indoor unit within 7m CAUTION Do not install the air conditioner at any place where there is a danger of flammable gas leakage In the event of a gas le...

Page 5: ...ks Lightly pull the front grille toward you with one hand and push down on the hooks with the fingers of your other hand When there is no work space because the unit is close to ceiling CAUTION Be sur...

Page 6: ...The service lid is removable 1 Remove the service lid screw 2 Pull out the service lid diagonally down in the direction of the arrow 3 Pull down The mounting plate should be installed on a wall which...

Page 7: ...ver into wall pipe 4 After completing refrigerant piping wiring and drain piping caulk pipe hole gap with putty 3 Installing the indoor unit In the case of bending or curing refrigerant pipes keep the...

Page 8: ...gs at the top of the indoor unit as a guide 4 Open the front panel then open the service lid Refer to preparation before installation 5 Pass the inter unit wire from the outdoor unit through the feed...

Page 9: ...the insulation fixing screw on the right and remove the drain hose 2 Remove the drain plug on the left side and attach it to the right side 3 Insert the drain hose and tighten with included insulatio...

Page 10: ...ECEIVER Signal receiver BZ Buzzer C101 C102 Capacitor FG Frame ground F1U Fuse 3 15A H1P H3P Pilot lamp MR10 Magnetic relay M1F Fan motor M1S M3S Swing motor PCB1 PCB4 Printed circuit board R1T R2T Th...

Page 11: ...indoor unit Doing so may cause electric shock or fire 5 When connecting to an HA system Wired remote controller central remote controller etc 1 Remove the metal plate electrical wiring cover Refer to...

Page 12: ...below 1 Lean the metal plate electrical wiring cover as shown in the figure and attach tab 1 on the lower side to the electrical wiring box 2 Attach tab 2 on the lower side of the metal plate electric...

Page 13: ...on flared part Prevent mineral oil from getting into the system as this would reduce the lifetime of the units Never use piping which has been used for previous installations Only use parts which are...

Page 14: ...insulation materials that will withstand this temperature 2 Be sure to insulate both the gas and liquid piping and to provide insulation dimensions as below 3 Use separate thermal insulation for gas a...

Page 15: ...l operation mode when the circuit breaker is opened again 2 Test items If the is not displayed make sure not to cut the switching jumper J8 for cooling operation when cutting the address jumper If it...

Page 16: ...3P387973 3D 2015 11 Copyright 2014 Daikin 3PEN387973 3D book Page 1 Monday November 30 2015 4 18 PM...

Reviews: