Indoor Unit Installation

1.

Installing the mounting plate

• The mounting plate should be installed on a wall which can support the weight of the indoor unit.
1) Temporarily secure the mounting plate to the wall, make sure that the panel is completely level, and mark the boring points 

on the wall.

2) Secure the mounting plate to the wall with screws.

Recommended mounting plate retention spots and dimensions

2.

Boring a wall hole and installing wall embedded pipe

• For walls containing metal frame or metal board, be sure to use a wall 

embedded pipe and wall cover in the feed-through hole to prevent possible 
heat, electrical shock, or fire.

• Be sure to caulk the gaps around the pipes with caulking material to 

prevent water leakage.

1) Bore a feed-through hole of 65mm in the wall so it has a down slope 

toward the outside.

2) Insert a wall pipe into the hole.
3) Insert a wall cover into wall pipe.
4) After completing refrigerant piping, wiring, and drain piping, caulk pipe hole gap with putty.

3.

Installing the indoor unit

• In the case of bending or curing refrigerant pipes, keep the following 

precautions in mind.
Abnormal sound may be generated if improper work is conducted.

1) Do not strongly press the refrigerant pipes onto the bottom frame.
2) Do not strongly press the refrigerant pipes on the front grille, either.

209

241

191.5

66

106

176

150

384

900

344

75.5

48

250

48

298

50

50

Use a tape measure 
as shown.

unit: mm

Removed pipe 
port cover 

Recommended mounting plate 
retention spots (5 spots in all)

Place a leveler 
on raised tab.

Drain hose position

Keep here the piece cut out 
from the unit for piping

Liquid pipe end

Gas pipe end

Mounting plate

* The removed pipe port cover can be 

kept in the mounting plate pocket.

Position the end of 
the tape measure at    .

Through-
the-wall 
hole  65mm

Inside

Outside

Caulking

Wall embedded pipe 
(field supply)

Wall hole cover
(field supply)

Wall embedded pipe 
(field supply)

65

3PEN387973-3D.book  Page 5  Monday, November 30, 2015  4:18 PM

Summary of Contents for FTXM-K

Page 1: ...TIONER INSTALLATION MANUAL R32 Split Series English Deutsch Fran ais Nederlands Espa ol Italiano E Portugues Pycc T rk e MODELS FTXM35K3V1B FTXM42K3V1B FTXM50K3V1B 3PEN387973 3D book Page 1 Monday Nov...

Page 2: ...nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acordo com o Certificado C 09 A B C 10 Bem rk som anf rt i A...

Page 3: ...erheating electric shocks or fire Make sure that all wiring is secured the specified wires are used and that there is no strain on the terminal connections or wires Improper connections or securing of...

Page 4: ...controller signals are properly received by the indoor unit within 7m CAUTION Do not install the air conditioner at any place where there is a danger of flammable gas leakage In the event of a gas le...

Page 5: ...ks Lightly pull the front grille toward you with one hand and push down on the hooks with the fingers of your other hand When there is no work space because the unit is close to ceiling CAUTION Be sur...

Page 6: ...The service lid is removable 1 Remove the service lid screw 2 Pull out the service lid diagonally down in the direction of the arrow 3 Pull down The mounting plate should be installed on a wall which...

Page 7: ...ver into wall pipe 4 After completing refrigerant piping wiring and drain piping caulk pipe hole gap with putty 3 Installing the indoor unit In the case of bending or curing refrigerant pipes keep the...

Page 8: ...gs at the top of the indoor unit as a guide 4 Open the front panel then open the service lid Refer to preparation before installation 5 Pass the inter unit wire from the outdoor unit through the feed...

Page 9: ...the insulation fixing screw on the right and remove the drain hose 2 Remove the drain plug on the left side and attach it to the right side 3 Insert the drain hose and tighten with included insulatio...

Page 10: ...ECEIVER Signal receiver BZ Buzzer C101 C102 Capacitor FG Frame ground F1U Fuse 3 15A H1P H3P Pilot lamp MR10 Magnetic relay M1F Fan motor M1S M3S Swing motor PCB1 PCB4 Printed circuit board R1T R2T Th...

Page 11: ...indoor unit Doing so may cause electric shock or fire 5 When connecting to an HA system Wired remote controller central remote controller etc 1 Remove the metal plate electrical wiring cover Refer to...

Page 12: ...below 1 Lean the metal plate electrical wiring cover as shown in the figure and attach tab 1 on the lower side to the electrical wiring box 2 Attach tab 2 on the lower side of the metal plate electric...

Page 13: ...on flared part Prevent mineral oil from getting into the system as this would reduce the lifetime of the units Never use piping which has been used for previous installations Only use parts which are...

Page 14: ...insulation materials that will withstand this temperature 2 Be sure to insulate both the gas and liquid piping and to provide insulation dimensions as below 3 Use separate thermal insulation for gas a...

Page 15: ...l operation mode when the circuit breaker is opened again 2 Test items If the is not displayed make sure not to cut the switching jumper J8 for cooling operation when cutting the address jumper If it...

Page 16: ...3P387973 3D 2015 11 Copyright 2014 Daikin 3PEN387973 3D book Page 1 Monday November 30 2015 4 18 PM...

Reviews: