Refrigerant Piping Work

2.

Refrigerant piping

 CAUTION

• Use the flare nut fixed to the main unit. (To prevent cracking of the flare nut by aged deterioration.)
• To prevent gas leakage, apply refrigeration oil only to the inner surface of the flare. (Use refrigeration oil for R32 or R410A.)
• Use torque wrenches when tightening the flare nuts to prevent damage to the flare nuts and gas leakage.

Align the centres of both flares and tighten the flare nuts 3 or 4 turns by hand. Then tighten them fully with the torque wrenches. 

2-1. Caution on piping handling

1) Protect the open end of the pipe against dust and moisture.
2) All pipe bends should be as gentle as possible. Use a pipe bender 

for bending.

2-2. Selection of copper and heat insulation materials

• When using commercial copper pipes and fittings, observe the following:
1) Insulation material: Polyethylene foam

Heat transfer rate: 0.041 to 0.052W/mK (0.035 to 0.045kcal/mh°C)
Refrigerant gas pipe’s surface temperature reaches 110°C max.
Choose heat insulation materials that will withstand this temperature.

2) Be sure to insulate both the gas and liquid piping and to provide insulation 

dimensions as below.

3) Use separate thermal insulation for gas and liquid refrigerant pipes.

Gas side

Liquid side

Gas pipe thermal 

insulation

Liquid pipe thermal 

insulation

35,42 class

50 class

O.D. 6.4mm

I.D. 12-15mm

I.D. 8-10mm

O.D. 9.5mm

O.D. 12.7mm

Minimum bend radius

Thickness 10mm Min.

30mm or more

Thickness 0.8mm (C1220T-O)

Do not apply refrigeration 
oil to the outer surface.

Flare nut

Apply refrigeration oil to 
the inner surface of the 
flare.

Do not apply refrigeration oil to 
the flare nut to avoid tightening 
with excessive torque.

[Apply oil]

Piping union

Flare nut

Spanner

[Tighten]

3/8 inch

1/4 inch

35, 42 class

1/2 inch

50 class

Torque wrench

Flare nut tightening torque

Gas side

32.7-39.9N • m

(330-407kgf • cm)

49.5-60.3N • m

(505-615kgf • cm)

14.2-17.2N • m

(144-175kgf • cm)

Liquid side

Wall

If no flare cap is 
available, cover the 
flare mouth with 
tape to keep dirt 
or water out.

Be sure to 
place a cap.

Rain

Gas pipe

Inter-unit wire

Liquid pipe

Drain hose

Finishing tape

Gas pipe 

insulation

Liquid pipe 

insulation

3PEN387973-3D.book  Page 12  Monday, November 30, 2015  4:18 PM

Summary of Contents for FTXM-K

Page 1: ...TIONER INSTALLATION MANUAL R32 Split Series English Deutsch Fran ais Nederlands Espa ol Italiano E Portugues Pycc T rk e MODELS FTXM35K3V1B FTXM42K3V1B FTXM50K3V1B 3PEN387973 3D book Page 1 Monday Nov...

Page 2: ...nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acordo com o Certificado C 09 A B C 10 Bem rk som anf rt i A...

Page 3: ...erheating electric shocks or fire Make sure that all wiring is secured the specified wires are used and that there is no strain on the terminal connections or wires Improper connections or securing of...

Page 4: ...controller signals are properly received by the indoor unit within 7m CAUTION Do not install the air conditioner at any place where there is a danger of flammable gas leakage In the event of a gas le...

Page 5: ...ks Lightly pull the front grille toward you with one hand and push down on the hooks with the fingers of your other hand When there is no work space because the unit is close to ceiling CAUTION Be sur...

Page 6: ...The service lid is removable 1 Remove the service lid screw 2 Pull out the service lid diagonally down in the direction of the arrow 3 Pull down The mounting plate should be installed on a wall which...

Page 7: ...ver into wall pipe 4 After completing refrigerant piping wiring and drain piping caulk pipe hole gap with putty 3 Installing the indoor unit In the case of bending or curing refrigerant pipes keep the...

Page 8: ...gs at the top of the indoor unit as a guide 4 Open the front panel then open the service lid Refer to preparation before installation 5 Pass the inter unit wire from the outdoor unit through the feed...

Page 9: ...the insulation fixing screw on the right and remove the drain hose 2 Remove the drain plug on the left side and attach it to the right side 3 Insert the drain hose and tighten with included insulatio...

Page 10: ...ECEIVER Signal receiver BZ Buzzer C101 C102 Capacitor FG Frame ground F1U Fuse 3 15A H1P H3P Pilot lamp MR10 Magnetic relay M1F Fan motor M1S M3S Swing motor PCB1 PCB4 Printed circuit board R1T R2T Th...

Page 11: ...indoor unit Doing so may cause electric shock or fire 5 When connecting to an HA system Wired remote controller central remote controller etc 1 Remove the metal plate electrical wiring cover Refer to...

Page 12: ...below 1 Lean the metal plate electrical wiring cover as shown in the figure and attach tab 1 on the lower side to the electrical wiring box 2 Attach tab 2 on the lower side of the metal plate electric...

Page 13: ...on flared part Prevent mineral oil from getting into the system as this would reduce the lifetime of the units Never use piping which has been used for previous installations Only use parts which are...

Page 14: ...insulation materials that will withstand this temperature 2 Be sure to insulate both the gas and liquid piping and to provide insulation dimensions as below 3 Use separate thermal insulation for gas a...

Page 15: ...l operation mode when the circuit breaker is opened again 2 Test items If the is not displayed make sure not to cut the switching jumper J8 for cooling operation when cutting the address jumper If it...

Page 16: ...3P387973 3D 2015 11 Copyright 2014 Daikin 3PEN387973 3D book Page 1 Monday November 30 2015 4 18 PM...

Reviews: