background image

13 

English

When using 2 remote controllers for 1 indoor unit.

2. 

For use with 2
remote controllers

Remote 
controller
(option)

(SUB)

(MAIN)

1

P

2

P

1

P

2

P

L

1

L

2

IN/D OUT/D

F1 F2 F1 F2

P

1

P

2

F

1

F

2

T

1

T

2

Power supply

208/230V

~

60Hz

Control box

Outdoor unit

Indoor unit

L

1

L

2

 NOTE

A single switch can be used to supply power to units on the 

1. 

same system. However, branch switches and branch circuit 
breakers must be selected carefully.
Do not ground the equipment on gas piping, water piping or 

2. 

lightning rods, or crossground with telephones. Improper 
grounding could result in electric shock.

CONTROL BY 2 REMOTE CONTROLLERS (Con-

9-2 

trolling 1 indoor unit by 2 remote controllers)

When using 2 remote controllers, one must be set to “MAIN” 

• 

and the other to “SUB”.
If the remote controller to be used is Model BRC1E71, read 

• 

the installation manual supplied with the remote controller.

MAIN/SUB CHANGEOVER

Press and hold the operation switch button of the 

(1) 

remote controller for one of the two units for four 
seconds or more.  When the LCD display changes 
from the display as the main remote controller to the 
display as the sub remote controller, the setting is 
complete.

Remove the front panel.

(2) 

Add remote controller 2 (SUB) to the terminal block 

(3) 

for remote controller (P¹, P²) in the electric component 
box. (There is no polarity.)

Remote controller wiring 
terminal block

Remote 
controller 2
(SUB)

Remote 
controller 1
(MAIN)

1

P

2

P

1

F

2

F

1

T

2

T

FORCED

OFF

REMOTE
CONTRL

TRANSMISSION

WIRING

REMOTE CONTROL (FORCED OFF AND ON/

9-3 

OFF OPERATION)

Connect input lines from the outside to the terminals T

• 

¹ and 

T² on the terminal block (6P) for remote controller to achieve 
remote control.
See the “

• 

10. FIELD SETTING AND TEST RUN

” for details 

on operation.

Input A

1

P

2

P

1

F

2

F

1

T

2

T

FORCED

OFF

REMOTE

CONTRL

TRANSMISSION

WIRING

Wire specifi cation

Sheathed vinyl cord or cable (2 wires)

Gauge

AWG18 – 16

Length

Max. 328 ft.

External terminal

Contact that can ensure the minimum 
applicable load of 15 V DC, 1 mA.

FIELD SETTING AND TEST RUN

10. 

Field settings may have to be performed using the re-

mote controller, depending on the type of installation.

Make sure the control box covers are closed on the 

(1) 

indoor and outdoor units.

Depending on the type of installation, make the fi eld 

(2) 

settings from the remote controller after the power is 
turned on, following the “Field Settings” manual which 
came with the remote controller.

The settings can select “Mode No.”, “FIRST CODE NO.” 

• 

and “SECOND CODE NO.”.
The “Field Settings” included with the remote controller 

• 

lists the order of the settings and method of operation.

Unit No

0

1–01
5–––
9–––

2–02
6–––
a–––

3–01
7–––
b–––

Field Settings

0–

01

4–––
8–––

Setting

Mode

20

SECOND CODE NO.

FIRST CODE NO.

Mode No.

FIELD SET MODE

Lastly, make sure the customer keeps the “Field Settings” 

• 

manual, along with the operating manual, in a safe place.

01_EN_3P250363-4C.indd   13

01_EN_3P250363-4C.indd   13

12/28/2011   11:51:57 AM

12/28/2011   11:51:57 AM

Summary of Contents for FTQ18PBVJU

Page 1: ...with the equipment owner Lire soigneusement ces instructions avant l installation Conserver ce manuel port e de main pour r f rence ult rieure Ce manuel doit tre donn au propri taire de l quipement Le...

Page 2: ...installation ventilate the area immediately Refrigerant gas may produce toxic gas if it comes in contact with fire Exposure to this gas could cause severe injury or death After completing the install...

Page 3: ...ant pipes may be hot or cold depending on the condition of the refrigerant flowing through the refrigerant piping compressor and other refrigerant cycle parts Your hands may suffer burns or frostbite...

Page 4: ...t an air filter part to be procured in the field in the suction air passage in order to prevent water leaking etc The accessories needed for installation must be retained in your custody until the ins...

Page 5: ...ual along with the installation manual to the customer Did you explain the customer the handling and cleaning methods of the field supplies e g the air filter air inlet grilles and air outlet grille D...

Page 6: ...art type the remote controller s transmission distance may be short ened Indoor units should be installed as far away from fluorescent lighting as possible DANGER Do not install unit in an area where...

Page 7: ...burns And be sure to use the insulation which can withstand such temperatures of 248 F or more for the gas piping Reinforce the insulation on the refrigerant piping accord ing to the installation env...

Page 8: ...cks Refer to Fig 5 Heat insulation procedure for gas piping Insulation material for piping on unit side Insulation material for piping field supply Make sure that the seam faces upward Clamp material...

Page 9: ...sure all water is out before making the duct connection Install drain piping as described Fig 7 1 Secondary drain piping connection hole Primary drain piping connection hole In case of vertical insta...

Page 10: ...in the manner described below INSTALLING THE DUCT 7 Exercise care regarding the following when performing duct work Verify that duct work does not exceed the unit s setting range of external static pr...

Page 11: ...1 8 36 type 2 8 2 2 42 type 3 6 400 2 8 MCA Minimum Circuit Amps A MOP Max Overcurrent Protective Device A HP Fan motor output W FLA Full Load Amps A WIRING EXAMPLE 9 HOW TO CONNECT WIRINGS 9 1 Preca...

Page 12: ...wiring and transmission wires to the terminal block shown in Fig 8 Then secure them in place with the included Clamp material 1 as shown in Fig 8 to protect them from external force from outside the...

Page 13: ...neat and does not cause the electric front panel to stick up then close the panel firmly When attaching the front panel make sure you do not pinch any wires Outside the air conditioners separate the l...

Page 14: ...mote controller 2 SUB Remote controller 1 MAIN 1 P 2 P 1 F 2 F 1 T 2 T FORCED OFF REMOTE CONTRL TRANSMISSION WIRING REMOTE CONTROL FORCED OFF AND ON 9 3 OFF OPERATION Connect input lines from the outs...

Page 15: ...rohibited Unit operated by changing input A from off to on Input A off to allow remote controller Unit stopped by changing input A from on to off SETTING THE FILTER SIGN DISPLAY INTERVAL 10 3 Explain...

Page 16: ...the wires to the terminal block 10P of the product The terminal Nos for wire connection are shown below Refer to the information as needed Terminal Nos are indicated on the name plate for the termina...

Page 17: ...the wiring was done incorrectly or that the power is not on so check again Remote controller display Contents A8 lit Error in power supply voltage to indoor unit C1 lit Fan driver PCB of indoor unit...

Page 18: ...363 4C EM11A011 1201 HT 1645 Wallace Drive Suite 110 Carrollton TX 75006 USA info daikinac com www daikinac com 00_CV_3P250363 4C indd 2 00_CV_3P250363 4C indd 2 11 18 2011 9 10 36 PM 11 18 2011 9 10...

Reviews: