background image

11 

English

Remove the front panel (upper).

(1) 

Top panel

High-voltage 
hole

Low-voltage 
hole

Remove the electric component box cover.

(2) 

Terminal block

Terminal block

Pass the power supply wiring and the ground wire 

(3) 

through the top panel’s high-voltage hole (requires use of 
conduit) and pass the remote controller wiring and trans-
mission wiring through the top panel’s low-voltage hole.

Pass the included insulation tube through the hole in the 

• 

panel before connecting the electric wires and the 
ground wire to the terminal block shown in Fig. 8.
Pass the included insulation tube through the hole in the 

• 

panel before connecting the remote controller wiring 
and transmission wires to the terminal block shown in 
Fig. 8.
Then secure them in place with the included Clamp 

• 

material (1) as shown in Fig. 8 to protect them from 
external force from outside the unit.
If the power supply voltage is 208V, change the trans-

• 

former wire connection from the 240V terminal to the 
208V terminal. 

(Refer to Fig. 9)

Transformer

Fig. 8

<FTQ18,24,30,36PBVJU models>

<FTQ42PBVJU model>

Terminal block

Terminal block

Transformer

Changing the transformer wire connection

208V

COM

240V

240V

208V

COM

Wire (Red)

Cap

Fig. 9

(Change the 
connection.)

(Connect the wire to the 208V terminal. 
Be sure to insert the wire securely until 
a clicking sound is produced.)

Connector

Wire 
(Red)

Cap

Connector

Ÿ

230V power supply (factory set)

®

Ÿ

208V power suppy

®

01_EN_3P250363-4C.indd   11

01_EN_3P250363-4C.indd   11

12/28/2011   11:51:51 AM

12/28/2011   11:51:51 AM

Summary of Contents for FTQ18PBVJU

Page 1: ...with the equipment owner Lire soigneusement ces instructions avant l installation Conserver ce manuel port e de main pour r f rence ult rieure Ce manuel doit tre donn au propri taire de l quipement Le...

Page 2: ...installation ventilate the area immediately Refrigerant gas may produce toxic gas if it comes in contact with fire Exposure to this gas could cause severe injury or death After completing the install...

Page 3: ...ant pipes may be hot or cold depending on the condition of the refrigerant flowing through the refrigerant piping compressor and other refrigerant cycle parts Your hands may suffer burns or frostbite...

Page 4: ...t an air filter part to be procured in the field in the suction air passage in order to prevent water leaking etc The accessories needed for installation must be retained in your custody until the ins...

Page 5: ...ual along with the installation manual to the customer Did you explain the customer the handling and cleaning methods of the field supplies e g the air filter air inlet grilles and air outlet grille D...

Page 6: ...art type the remote controller s transmission distance may be short ened Indoor units should be installed as far away from fluorescent lighting as possible DANGER Do not install unit in an area where...

Page 7: ...burns And be sure to use the insulation which can withstand such temperatures of 248 F or more for the gas piping Reinforce the insulation on the refrigerant piping accord ing to the installation env...

Page 8: ...cks Refer to Fig 5 Heat insulation procedure for gas piping Insulation material for piping on unit side Insulation material for piping field supply Make sure that the seam faces upward Clamp material...

Page 9: ...sure all water is out before making the duct connection Install drain piping as described Fig 7 1 Secondary drain piping connection hole Primary drain piping connection hole In case of vertical insta...

Page 10: ...in the manner described below INSTALLING THE DUCT 7 Exercise care regarding the following when performing duct work Verify that duct work does not exceed the unit s setting range of external static pr...

Page 11: ...1 8 36 type 2 8 2 2 42 type 3 6 400 2 8 MCA Minimum Circuit Amps A MOP Max Overcurrent Protective Device A HP Fan motor output W FLA Full Load Amps A WIRING EXAMPLE 9 HOW TO CONNECT WIRINGS 9 1 Preca...

Page 12: ...wiring and transmission wires to the terminal block shown in Fig 8 Then secure them in place with the included Clamp material 1 as shown in Fig 8 to protect them from external force from outside the...

Page 13: ...neat and does not cause the electric front panel to stick up then close the panel firmly When attaching the front panel make sure you do not pinch any wires Outside the air conditioners separate the l...

Page 14: ...mote controller 2 SUB Remote controller 1 MAIN 1 P 2 P 1 F 2 F 1 T 2 T FORCED OFF REMOTE CONTRL TRANSMISSION WIRING REMOTE CONTROL FORCED OFF AND ON 9 3 OFF OPERATION Connect input lines from the outs...

Page 15: ...rohibited Unit operated by changing input A from off to on Input A off to allow remote controller Unit stopped by changing input A from on to off SETTING THE FILTER SIGN DISPLAY INTERVAL 10 3 Explain...

Page 16: ...the wires to the terminal block 10P of the product The terminal Nos for wire connection are shown below Refer to the information as needed Terminal Nos are indicated on the name plate for the termina...

Page 17: ...the wiring was done incorrectly or that the power is not on so check again Remote controller display Contents A8 lit Error in power supply voltage to indoor unit C1 lit Fan driver PCB of indoor unit...

Page 18: ...363 4C EM11A011 1201 HT 1645 Wallace Drive Suite 110 Carrollton TX 75006 USA info daikinac com www daikinac com 00_CV_3P250363 4C indd 2 00_CV_3P250363 4C indd 2 11 18 2011 9 10 36 PM 11 18 2011 9 10...

Reviews: