background image

English

Tape section

VP25 side

Metal clamp (4)

(accessory)

Drain hose (5)

(accessory)

Tightening 
section

Bend the end to avoid 
tearing the Sealing 
pad (large) (9).

Approx. 90°

Main unit

<When bending the end>

Refer to the following fi gure and check the drain. Then, 

• 

use the included Sealing pad (large) (9) to thermally 
insulate the Metal clamp (4) and the Drain hose (5).

Do not make any gap

Drain hose (5)

Sealing pad 
(large) (9)

Sealing pad
(large) (9)

<Drain socket thermal insulation work>

(accessory)

(accessory)

(accessory)

Wrap the sealing 
material around so 
that the side with the 
edge of the flat band is 
doubly wrapped.

Start wrapping 
from near the 
tightening 
section of the 
Metal clamp (4)

The drain pan has connections for a primary and sec-

• 

ondary drain.
The diameter of the drain piping should be greater than 

• 

or equal to the diameter of the connecting pipe (vinyl 
tube; pipe size : 25/32 in. ; outer dimension : 1-1/32 in.).
(not including a riser)
Keep piping runs short with a downward slope of at 

• 

least 1/100 to prevent air pocket from forming.
Be sure to install a drain trap at the drain outlet since 

• 

the inside of the unit is at negative pressure relative to 
atmospheric pressure during operation. 
To keep the piping from becoming clogged with dirt, 

• 

avoid bends where possible and install so that traps can 
be cleaned.

Air handler

At least 
4 in.

At least 
3 in.

Observe the following guidelines when installing con-

• 

centrated drain piping. Select the thickness of the 
concentrated drain piping to refl ect the capacity of the 
machine to which it will be connected.

 CAUTION

Water accumulating in the drain piping can cause the drain 

 

to clog.

PRECAUTIONS

Drain piping connections

Do not connect the drain piping directly to sewage piping 

• 

that smell of ammonia. The ammonia in the sewage might 
enter the indoor unit through the drain piping and corrode 
the heat exchanger.
Do not twist or bend the drain hose, as excessive force may 

• 

cause it to leak.

After piping work is fi nished, check drainage fl ows 

(2) 

smoothly.

Gradually insert approximately 1 quart of water into the 

• 

drain pan to check drainage in the manner described 
below.

INSTALLING THE  DUCT

7. 

Exercise care regarding the following when performing duct work.

Verify that duct work does not exceed the unit’s setting range 

• 

of external static pressure (up to 0.5 Wg at “HH” speed).
Install canvas ducts at air outlets and inlets so that vibrations 

• 

from the main unit are not transmitted to ducts or the fl oor. 
Additionally, line the duct with sound-absorbing material 
(heat insulation material) as necessary.
Be sure to install an air fi lter to the product’s air inlet or to a 

• 

fi eld-supplied air inlet inside the air passage on the suction 
side.
Perform the curing and other work during duct welding so 

• 

that the inside of the product is not exposed to spatter.
If the metal duct passes through a metal lath, wire lath, or 

• 

metal plate of a wooden structure, isolate the duct from the 
wall electrically.
Be sure to heat-insulate the duct to prevent the formation of 

• 

condensation. (Material: Glass wool or polyethylene foam; 
thickness: 1 inch.)
Explain to the customer how to operate and clean fi eld-

• 

supplied components such as air fi lters, air inlet grilles, air 
outlet grilles.
To prevent drafts, locate the air outlet grille on the indoor 

• 

side so that warm air from the outlet does not come into 
direct contact with room occupants.
When an electric heater (optional) is installed, use metal 

• 

duct and wrap the duct with a glass-wool insulation material.

ELECTRIC WIRING WORK

8. 

GENERAL INSTRUCTIONS

8-1 

Shut off the power before doing any work.

• 

All fi eld supplied parts and materials, electric works must 

• 

conform to local codes.
Use copper conductors only.

• 

See also the “Wiring Diagram Label” located inside the unit’s 

• 

front cover.
For details on hooking up the remote controller, refer to the 

• 

“REMOTE CONTROLLER INSTALLATION MANUAL”.
All wiring must be performed by an authorized electrician.

• 

Install a wiring interrupter or ground-fault circuit interrupter 

• 

for the power wiring.
Make sure the ground resistance is no greater than 100

• 

Ω

.

To avoid short circuiting the power supply wire, be sure to 

• 

use insulated terminals.
Do not turn on the power supply (wiring interrupter or 

• 

ground-fault circuit interrupter) until all other work is done.

01_EN_3P250363-4C.indd   9

01_EN_3P250363-4C.indd   9

12/28/2011   11:51:50 AM

12/28/2011   11:51:50 AM

Summary of Contents for FTQ18PBVJU

Page 1: ...with the equipment owner Lire soigneusement ces instructions avant l installation Conserver ce manuel port e de main pour r f rence ult rieure Ce manuel doit tre donn au propri taire de l quipement Le...

Page 2: ...installation ventilate the area immediately Refrigerant gas may produce toxic gas if it comes in contact with fire Exposure to this gas could cause severe injury or death After completing the install...

Page 3: ...ant pipes may be hot or cold depending on the condition of the refrigerant flowing through the refrigerant piping compressor and other refrigerant cycle parts Your hands may suffer burns or frostbite...

Page 4: ...t an air filter part to be procured in the field in the suction air passage in order to prevent water leaking etc The accessories needed for installation must be retained in your custody until the ins...

Page 5: ...ual along with the installation manual to the customer Did you explain the customer the handling and cleaning methods of the field supplies e g the air filter air inlet grilles and air outlet grille D...

Page 6: ...art type the remote controller s transmission distance may be short ened Indoor units should be installed as far away from fluorescent lighting as possible DANGER Do not install unit in an area where...

Page 7: ...burns And be sure to use the insulation which can withstand such temperatures of 248 F or more for the gas piping Reinforce the insulation on the refrigerant piping accord ing to the installation env...

Page 8: ...cks Refer to Fig 5 Heat insulation procedure for gas piping Insulation material for piping on unit side Insulation material for piping field supply Make sure that the seam faces upward Clamp material...

Page 9: ...sure all water is out before making the duct connection Install drain piping as described Fig 7 1 Secondary drain piping connection hole Primary drain piping connection hole In case of vertical insta...

Page 10: ...in the manner described below INSTALLING THE DUCT 7 Exercise care regarding the following when performing duct work Verify that duct work does not exceed the unit s setting range of external static pr...

Page 11: ...1 8 36 type 2 8 2 2 42 type 3 6 400 2 8 MCA Minimum Circuit Amps A MOP Max Overcurrent Protective Device A HP Fan motor output W FLA Full Load Amps A WIRING EXAMPLE 9 HOW TO CONNECT WIRINGS 9 1 Preca...

Page 12: ...wiring and transmission wires to the terminal block shown in Fig 8 Then secure them in place with the included Clamp material 1 as shown in Fig 8 to protect them from external force from outside the...

Page 13: ...neat and does not cause the electric front panel to stick up then close the panel firmly When attaching the front panel make sure you do not pinch any wires Outside the air conditioners separate the l...

Page 14: ...mote controller 2 SUB Remote controller 1 MAIN 1 P 2 P 1 F 2 F 1 T 2 T FORCED OFF REMOTE CONTRL TRANSMISSION WIRING REMOTE CONTROL FORCED OFF AND ON 9 3 OFF OPERATION Connect input lines from the outs...

Page 15: ...rohibited Unit operated by changing input A from off to on Input A off to allow remote controller Unit stopped by changing input A from on to off SETTING THE FILTER SIGN DISPLAY INTERVAL 10 3 Explain...

Page 16: ...the wires to the terminal block 10P of the product The terminal Nos for wire connection are shown below Refer to the information as needed Terminal Nos are indicated on the name plate for the termina...

Page 17: ...the wiring was done incorrectly or that the power is not on so check again Remote controller display Contents A8 lit Error in power supply voltage to indoor unit C1 lit Fan driver PCB of indoor unit...

Page 18: ...363 4C EM11A011 1201 HT 1645 Wallace Drive Suite 110 Carrollton TX 75006 USA info daikinac com www daikinac com 00_CV_3P250363 4C indd 2 00_CV_3P250363 4C indd 2 11 18 2011 9 10 36 PM 11 18 2011 9 10...

Reviews: