background image

English 

16

SETTINGS FOR SEPARATELY SOLD ACCES-

10-7 

SORIES

See the instruction manuals included with optional accesso-

• 

ries for the necessary settings.

When using a wireless remote controller

A wireless remote controller address needs to be set when 

• 

using a wireless remote controller. See the installation 
manual included with the wireless remote controller for 
details on how to make the settings.

Perform a test run according to the outdoor unit’s installa-
tion manual.

The operation lamp of the remote controller will fl ash when a 

• 

malfunction occurs. Check the malfunction code on the 
liquid crystal display to identify the point of trouble. An 
explanation of malfunction codes and the corresponding 
trouble is provided in “CAUTION FOR SERVICING” of the 
outdoor unit.
If the display shows any of the following, there is a possibility 
that the wiring was done incorrectly or that the power is not 
on, so check again.

Remote controller 

display

Contents

“ A8 ”  lit

Error in power supply voltage to indoor 

 

unit.

“ C1 ”  lit

Fan driver PCB of indoor unit 

 

 indoor 

control PCB transmission error.

“ C6 ”  lit

Improper combination of fan driver PCB 

 

of indoor unit or setting failure in control 
PCB type.

“ U3 ”  lit

Test operation of outdoor unit has not 

 

been fi nished.

“ 

 ” is lit up

There is a short circuit at the FORCED 

 

OFF terminals (T¹, T²)

“ U4 ” is lit up

“ UH ” is lit up

The power on the outdoor unit is off.

 

The outdoor unit has not been wired for 

 

power supply.
Incorrect wiring for the transmission 

 

wiring and / or FORCED OFF wiring.

No display

The power on the indoor unit is off.

 

The indoor unit has not been wired for 

 

power supply.
Incorrect wiring for the remote controller 

 

wiring, the transmission wiring and / or 
the FORCED OFF wiring.

 CAUTION

Always stop the test run using the remote controller to stop 

 

operation.

01_EN_3P250363-4C.indd   16

01_EN_3P250363-4C.indd   16

12/28/2011   11:51:58 AM

12/28/2011   11:51:58 AM

Summary of Contents for FTQ18PBVJU

Page 1: ...with the equipment owner Lire soigneusement ces instructions avant l installation Conserver ce manuel port e de main pour r f rence ult rieure Ce manuel doit tre donn au propri taire de l quipement Le...

Page 2: ...installation ventilate the area immediately Refrigerant gas may produce toxic gas if it comes in contact with fire Exposure to this gas could cause severe injury or death After completing the install...

Page 3: ...ant pipes may be hot or cold depending on the condition of the refrigerant flowing through the refrigerant piping compressor and other refrigerant cycle parts Your hands may suffer burns or frostbite...

Page 4: ...t an air filter part to be procured in the field in the suction air passage in order to prevent water leaking etc The accessories needed for installation must be retained in your custody until the ins...

Page 5: ...ual along with the installation manual to the customer Did you explain the customer the handling and cleaning methods of the field supplies e g the air filter air inlet grilles and air outlet grille D...

Page 6: ...art type the remote controller s transmission distance may be short ened Indoor units should be installed as far away from fluorescent lighting as possible DANGER Do not install unit in an area where...

Page 7: ...burns And be sure to use the insulation which can withstand such temperatures of 248 F or more for the gas piping Reinforce the insulation on the refrigerant piping accord ing to the installation env...

Page 8: ...cks Refer to Fig 5 Heat insulation procedure for gas piping Insulation material for piping on unit side Insulation material for piping field supply Make sure that the seam faces upward Clamp material...

Page 9: ...sure all water is out before making the duct connection Install drain piping as described Fig 7 1 Secondary drain piping connection hole Primary drain piping connection hole In case of vertical insta...

Page 10: ...in the manner described below INSTALLING THE DUCT 7 Exercise care regarding the following when performing duct work Verify that duct work does not exceed the unit s setting range of external static pr...

Page 11: ...1 8 36 type 2 8 2 2 42 type 3 6 400 2 8 MCA Minimum Circuit Amps A MOP Max Overcurrent Protective Device A HP Fan motor output W FLA Full Load Amps A WIRING EXAMPLE 9 HOW TO CONNECT WIRINGS 9 1 Preca...

Page 12: ...wiring and transmission wires to the terminal block shown in Fig 8 Then secure them in place with the included Clamp material 1 as shown in Fig 8 to protect them from external force from outside the...

Page 13: ...neat and does not cause the electric front panel to stick up then close the panel firmly When attaching the front panel make sure you do not pinch any wires Outside the air conditioners separate the l...

Page 14: ...mote controller 2 SUB Remote controller 1 MAIN 1 P 2 P 1 F 2 F 1 T 2 T FORCED OFF REMOTE CONTRL TRANSMISSION WIRING REMOTE CONTROL FORCED OFF AND ON 9 3 OFF OPERATION Connect input lines from the outs...

Page 15: ...rohibited Unit operated by changing input A from off to on Input A off to allow remote controller Unit stopped by changing input A from on to off SETTING THE FILTER SIGN DISPLAY INTERVAL 10 3 Explain...

Page 16: ...the wires to the terminal block 10P of the product The terminal Nos for wire connection are shown below Refer to the information as needed Terminal Nos are indicated on the name plate for the termina...

Page 17: ...the wiring was done incorrectly or that the power is not on so check again Remote controller display Contents A8 lit Error in power supply voltage to indoor unit C1 lit Fan driver PCB of indoor unit...

Page 18: ...363 4C EM11A011 1201 HT 1645 Wallace Drive Suite 110 Carrollton TX 75006 USA info daikinac com www daikinac com 00_CV_3P250363 4C indd 2 00_CV_3P250363 4C indd 2 11 18 2011 9 10 36 PM 11 18 2011 9 10...

Reviews: