Troubleshooting
SiUS041501E
69
Service Diagnosis
Troubleshooting
Check No.11
Refer to P.93
Check No.11
Check the power supply
waveform.
Check the voltage of the
connection wires on the indoor
terminal board between No. 1
and No. 3, and between No. 2
and No. 3.
YES
Blink
Replace the indoor unit PCB
(control PCB).
Locate the cause of the
disturbance of the power
supply waveform, and correct
it.
NO
(R21189)
Continuously ON or OFF
NO
YES
YES
NO
Caution
Correct the indoor unit -
outdoor unit connection wires.
Replace the outdoor unit PCB
(main PCB).
Replace the connection wires
between the indoor unit and
outdoor unit.
Is LED A blinking?
Properly insulated?
Is there any disturbance?
Is there any wiring error?
Check the indoor unit - outdoor
unit connection wires.
Check the LED A on the outdoor
unit PCB.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
∗
Before you check the LED A, cancel
the standby electricity saving
function by starting fan operation
with the remote controller.
∗
Wait at least for 7 sec. after turning
on the power.
NO
YES
Check the power supply voltage.
Correct the power supply.
YES
NO
Replace the outdoor fan motor
and the outdoor unit PCB
(main PCB).
Rotate the
outdoor fan by hand.
Does the outdoor fan rotate
smoothly?
Is the
voltage fluctuation
within ±10% from the
rated value?
Summary of Contents for FTKN09NMVJU
Page 12: ...SiUS041501E 1 List of Functions Part 1 List of Functions 1 Functions 2...
Page 59: ...SiUS041501E Remote Controller 48 Part 5 Remote Controller 1 Cooling Only 49 2 Heat Pump 51...
Page 65: ...SiUS041501E Service Diagnosis 54 5 13 Power Module Check 100...
Page 132: ...Revision History Month Year Version Revised contents 03 2015 SiUS041501E First edition...