Installation and operation manual

5

FMDQ50~125B7VEB

Air conditioning system

4PW48241-1

Cautions for brazing

Be sure to carry out a nitrogen blow when brazing.
Brazing without carrying out nitrogen replacement or releasing
nitrogen into the piping will create large quantities of oxidized
film on the inside of the pipes, adversely affecting valves and
compressors in the refrigerating system and preventing normal
operation.

When brazing while inserting nitrogen into the piping, nitrogen
must be set to 0.02 MPa with a pressure-reducing valve (=just
enough so that it can be felt on the skin).

D

RAIN

 

PIPING

 

WORK

Rig the drain piping as shown in the figure and take measures
against condensation. Improperly rigged piping could lead to leaks
and eventually wet furniture and belongings.

Install the drain pipes.
-

Keep piping as short as possible and slope it downwards at a 
gradient of at least 1/100 so that air may not remain trapped 
inside the pipe.

-

Keep pipe size equal to or greater than that of the connecting 
pipe (vinyl pipe of 25 mm nominal diameter and 32 mm outer 
diameter).

-

Push the supplied drain hose as far as possible over the 
drain socket.

-

Tighten the metal clamp until the screw head is less than 
4 mm from the metal clamp part as indicated in the 
illustration.

-

Wrap the supplied large sealing pad over the metal clamp 
and drain hose to insulate and fix it with clamps.

-

Insulate the complete drain piping inside the building (field 
supply).

-

If the drain hose cannot be sufficiently set on a slope, fit the 
hose with drain raising piping (field supply).

How to perform drain piping 

(See figure 10)

1

Connect the drain hose to the drain raising pipes, and insulate
them.

2

Connect the drain hose to the drain outlet on the indoor unit, and
tighten it with the clamp.

Precautions
-

Install the drain raising pipes at a height of less than 625 mm.

-

Install the drain raising pipes at a right angle to the indoor 
unit and no more than 300 mm from the unit.

-

To prevent air bubbles, install the drain hose level or slightly 
tilted up (

75 mm).

Testing of drain piping

After piping work is finished, check if drainage flows smoothly.

Add approximately 1 

l of water gradually through the air

discharge outlet. Check for water leaks.
Method of adding water. See 

figure 8

.

1

Refrigerant piping

2

Part to be brazed

3

Taping

4

Hands valve

5

Pressure-reducing valve

6

Nitrogen

1

Hanging bar

1

Drain socket (attached to the unit)

2

Drain hose (supplied with the unit)

3

Metal clamp (supplied with the unit)

4

Drain piping (field supply)

5

Large sealing pad (supplied with the unit)

1

2

3

4

5

6

6

1-1.5 m

1

1

2

3

5

4 mm

3

5

2

A

A'

A'

A-A'

1

4

A

A'

1

Ceiling slab

2

Hanger bracket

3

Adjustable range

4

Drain raising pipe

5

Drain hose (supplied with the unit)

6

Clamp metal (supplied with the unit)

Installation

A (mm)

Rear suction installation

231

When canvas duct is installed

350-530

When air inlet panel is directly installed

231

NOTE

The incline of attached drain hose should be
75 mm or less so that the drain socket does
not have to withstand additional force.

To  ensure a downward slope of 1:100, install
hanging bars every 1 to 1.5 m.

When unifying multiple drain pipes, install the
pipes as shown in 

figure 11

. Select converging

drain pipes whose gauge is suitable for the
operating capacity of the unit. 

1

T-joint converging drain pipes

1

Water inlet

2

Portable pump

3

Water inlet cover

4

Bucket (adding water through water inlet)

5

Drain outlet for maintenance (with rubber drain plug)

6

Refrigerant pipes

Summary of Contents for FMDQ50B7VEB

Page 1: ...INSTALLATION AND OPERATION MANUAL FMDQ50B7VEB FMDQ60B7VEB FMDQ71B7VEB FMDQ100B7VEB FMDQ125B7VEB Air conditioning system...

Page 2: ...680 1 5 3 4 2 7 180 460 160 160 300 425 1 3 2 180 460 350 1 2 2 3 5 0 75 625 A 300 mm 1 1 5 m 2 3 1 4 100 mm 1 0 625 mm 1 1 2 4 5 3 6a 7a 7b 7c 6b 6c 8 9 10 11 2 1 3 5 4 700 630 A B 4 3 2 1 1 1 2 4 5...

Page 3: ...12 gitt i henhold til bestemmelsene i 13 noudattaen m r yksi 14 za dodr en ustanoven p edpisu 15 prema odredbama 16 k veti a z 17 zgodnie z postanowieniami Dyrektyw 18 n urma prevederilor 19 ob upo t...

Page 4: ...ontrol system may malfunction Where the air contains high levels of salt such as air near the ocean and where voltage fluctuates a lot e g in factories Also in vehicles or vessels Do not install acces...

Page 5: ...remote controller and indoor unit might be shorter if there are fluorescent lights who are electrically started in the room The indoor unit must be installed as far as possible away from fluorescent...

Page 6: ...Ceiling opening 3 Service access panel optional accessory 4 Air filter 5 Air inlet duct 6 Duct service opening 7 Interchangeable plate NOTE Before installation of the unit in case of installation wit...

Page 7: ...frigerant such as air etc inside the refrigerant circuit Use annealed material only for flare connections Refer to Table 1 for the dimensions of flare nut spaces and the appropriate tightening torque...

Page 8: ...rain raising pipes and insulate them 2 Connect the drain hose to the drain outlet on the indoor unit and tighten it with the clamp Precautions Install the drain raising pipes at a height of less than...

Page 9: ...ant local and national legislation Note that the operation will restart automatically if the main power supply is turned off and then turned back on again This system consists of multiple indoor units...

Page 10: ...ts less than 12 A Branch the line outside the terminal board of the unit in accordance with electrical equipment standards when using two power wiring of a gauge greater than 2 mm2 1 6 The branch must...

Page 11: ...10 000 hrs Heavy 5 000 hrs Long life filter 2 500 hrs 1 250 hrs Standard filter 200 hrs 100 hrs 2 Thermostat sensor selection Use both the unit sensor or remotesensorif installed AND the remote contr...

Page 12: ...s are only applicable to outdoor units After setting this function be sure to turn on the outdoor unit before performing the test operation on the outdoor unit If any other error display occurs on the...

Page 13: ...xtremely contaminated If the dirt becomes impossible to clean change the air filter Air filter for exchange is optional 1 Open the suction grille Only for bottom suction Slide both knobs simultaneousl...

Page 14: ...e air inlet and outlet are not blocked Remove any obstacle Check if the earth is connected Clean the air filter and outside panels After cleaning the air filter make sure to attach it Turn on the main...

Page 15: ...INAL STRIP POWER SUPPLY X2M TERMINAL STRIP CONTROL Y1E ELECTRONIC EXPANSION VALVE Z1C Z2C NOISE FILTER FERRITE CORE Z1F NOISE FILTER CONNECTOR OPTIONAL ACCESSORY X28A CONNECTOR POWER SUPPLY FOR WIRING...

Page 16: ...NOTES NOTES...

Page 17: ...2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 3 1 1 4 2 L N IN D OUT D F1 F2 F1 F2 Control box P1 P2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 2 5 3 SETTI...

Page 18: ...4PW48241 1 Copyright Daikin...

Reviews: