background image

 

FMDQ50~125B7VEB
Air conditioning system
4PW48241-1

Installation and operation manual

2

For the following items, take special care during 
construction and check after installation is finished

Notes to the installer

Read this manual carefully to ensure correct installation. Be
sure to instruct the customer how to properly operate the system
and show him/her the enclosed operation manual.

Explain to the customer what system is installed on the site. Be
sure to fill out the appropriate installation specifications in the
chapter "What to do before operation" of the outdoor unit
operation manual.

I

MPORTANT

 

INFORMATION

 

REGARDING

 

THE

 

REFRIGERANT

 

USED

This product contains fluorinated greenhouse gases covered by the
Kyoto Protocol.

Refrigerant type:

R410A

GWP

(1)

 value:

1975

(1)

 GWP = global warming potential

Periodical inspections for refrigerant leaks may be required
depending on European or local legislation. Please contact your local
dealer for more information.

S

ELECTING

 

INSTALLATION

 

SITE

(See 

figure 1

 and 

figure 2

)

1

Select an installation site where the following conditions are
fulfilled and that meets your customer's approval.

-

Where optimum air distribution can be ensured.

-

Where nothing blocks air passage.

-

Where condensate water can be properly drained.

-

Where the false ceiling is not noticeably on an incline.

-

Where sufficient clearance for maintenance and service can 
be ensured.

-

Where there is no risk of flammable gas leaking.

-

Where piping between indoor and outdoor units is possible 
within the allowable limit. (Refer to the installation manual of 
the outdoor unit.)

-

Keep indoor unit, outdoor unit, power supply wiring and 
transmission wiring at least 1 meter away from televisions 
and radios. This is to prevent image interference and noise in 
those electrical appliances. (Noise may be generated 
depending on the conditions under which the electric wave is 
generated, even if 1 meter is kept.)

-

When installing the wireless remote controller kit, the 
distance between wireless remote controller and indoor unit 
might be shorter if there are fluorescent lights who are 
electrically started in the room. The indoor unit must be 
installed as far as possible away from fluorescent lights.

-

Do not place objects that are susceptible to moisture directly 
beneath the indoor or outdoor units. Under certain 
conditions, condensation on the main unit or refrigerant 
pipes, air filter dirt or drain blockage may cause dripping, 
resulting in fouling or failure of the object concerned.

2

Ensure that a protective guard is installed on air suction and air
outlet side to prevent that the fan blades or heat exchanger be
touched.

The protection must comply with relevant European and national
regulations.

3

Use suspension bolts for installation. Check whether the ceiling
is strong enough to support the weight of the indoor unit. If there
is a risk, reinforce the ceiling before installing the unit.

Tick 

 

when 

checked

Is the indoor unit fixed firmly?

The unit may drop, vibrate or make noise.

Is the gas leak test finished?

It may result in insufficient cooling or heating.

Is the unit fully insulated and checked for air leaks?

Condensate water may drip.

Does drainage flow smoothly?

Condensate water may drip.

Does the power supply voltage correspond to that shown on the 
name plate?

The unit may malfunction or components may burn out.

Are wiring and piping correct?

The unit may malfunction or components may burn out.

Is the unit safely grounded?

Dangerous at electric leakage.

Is the wiring size according to specifications?

The unit may malfunction or components may burn out.

Is nothing blocking the air outlet or inlet of either the indoor or 
outdoor units?

It may result in insufficient cooling or heating.

Are refrigerant piping length and additional refrigerant charge 
noted down?

The refrigerant charge in the system might not be clear.

Are the air filters fixed properly (when installing with rear duct)?

Maintenance of the air filters can be impossible.

Is the external static pressure set?

It may result in insufficient cooling or heating.

1

Service space

2

Drain pipe

3

Power supply wiring port

4

Transmission wiring port

5

Maintenance drain outlet

6

Gas pipe

7

Liquid pipe

Summary of Contents for FMDQ50B7VEB

Page 1: ...INSTALLATION AND OPERATION MANUAL FMDQ50B7VEB FMDQ60B7VEB FMDQ71B7VEB FMDQ100B7VEB FMDQ125B7VEB Air conditioning system...

Page 2: ...680 1 5 3 4 2 7 180 460 160 160 300 425 1 3 2 180 460 350 1 2 2 3 5 0 75 625 A 300 mm 1 1 5 m 2 3 1 4 100 mm 1 0 625 mm 1 1 2 4 5 3 6a 7a 7b 7c 6b 6c 8 9 10 11 2 1 3 5 4 700 630 A B 4 3 2 1 1 1 2 4 5...

Page 3: ...12 gitt i henhold til bestemmelsene i 13 noudattaen m r yksi 14 za dodr en ustanoven p edpisu 15 prema odredbama 16 k veti a z 17 zgodnie z postanowieniami Dyrektyw 18 n urma prevederilor 19 ob upo t...

Page 4: ...ontrol system may malfunction Where the air contains high levels of salt such as air near the ocean and where voltage fluctuates a lot e g in factories Also in vehicles or vessels Do not install acces...

Page 5: ...remote controller and indoor unit might be shorter if there are fluorescent lights who are electrically started in the room The indoor unit must be installed as far as possible away from fluorescent...

Page 6: ...Ceiling opening 3 Service access panel optional accessory 4 Air filter 5 Air inlet duct 6 Duct service opening 7 Interchangeable plate NOTE Before installation of the unit in case of installation wit...

Page 7: ...frigerant such as air etc inside the refrigerant circuit Use annealed material only for flare connections Refer to Table 1 for the dimensions of flare nut spaces and the appropriate tightening torque...

Page 8: ...rain raising pipes and insulate them 2 Connect the drain hose to the drain outlet on the indoor unit and tighten it with the clamp Precautions Install the drain raising pipes at a height of less than...

Page 9: ...ant local and national legislation Note that the operation will restart automatically if the main power supply is turned off and then turned back on again This system consists of multiple indoor units...

Page 10: ...ts less than 12 A Branch the line outside the terminal board of the unit in accordance with electrical equipment standards when using two power wiring of a gauge greater than 2 mm2 1 6 The branch must...

Page 11: ...10 000 hrs Heavy 5 000 hrs Long life filter 2 500 hrs 1 250 hrs Standard filter 200 hrs 100 hrs 2 Thermostat sensor selection Use both the unit sensor or remotesensorif installed AND the remote contr...

Page 12: ...s are only applicable to outdoor units After setting this function be sure to turn on the outdoor unit before performing the test operation on the outdoor unit If any other error display occurs on the...

Page 13: ...xtremely contaminated If the dirt becomes impossible to clean change the air filter Air filter for exchange is optional 1 Open the suction grille Only for bottom suction Slide both knobs simultaneousl...

Page 14: ...e air inlet and outlet are not blocked Remove any obstacle Check if the earth is connected Clean the air filter and outside panels After cleaning the air filter make sure to attach it Turn on the main...

Page 15: ...INAL STRIP POWER SUPPLY X2M TERMINAL STRIP CONTROL Y1E ELECTRONIC EXPANSION VALVE Z1C Z2C NOISE FILTER FERRITE CORE Z1F NOISE FILTER CONNECTOR OPTIONAL ACCESSORY X28A CONNECTOR POWER SUPPLY FOR WIRING...

Page 16: ...NOTES NOTES...

Page 17: ...2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 3 1 1 4 2 L N IN D OUT D F1 F2 F1 F2 Control box P1 P2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 2 5 3 SETTI...

Page 18: ...4PW48241 1 Copyright Daikin...

Reviews: