FMDQ50~125B7VEB
Air conditioning system
4PW48241-1

Installation and operation manual

6

First perform electric wiring work as instructed in 

"Electric wiring

work" on page 6

 and how to set the remote controller as explained in

"Wiring example and how to set the remote controller" on page 7

.

When electric wiring work is finished

Check drainage flow during COOL running, explained in 

"Test operation"

on page 10

.

When electric wiring work is not finished

Remove the switch box cover and connect the single-phase power
supply and the remote controller to the terminals. (Refer to 

"Electric

wiring work" on page 6

  for switch box attachment/detachment.)

(Refer to 

figure 12

 and 

figure 14

)

Next, press the inspection/test operation button 

 on the remote

controller. The unit will engage the test operation mode. Press the

operation mode selector button 

 until selecting fan operation

. Then, press the on/off button 

. The indoor unit fan and drain

pump will start up. Check that the water has drained from the unit.

Press 

 to go back to the first mode.

E

LECTRIC

 

WIRING

 

WORK

General instructions

All field supplied parts and materials and electric works must
conform to local codes.

Use copper wire only.

Follow the "Wiring diagram" attached to the unit body to wire the
outdoor unit, indoor units and the remote controller. For details
on hooking up the remote controller, refer to the "Installation
manual of the remote controller".

All wiring must be performed by an authorized electrician.

Attach the earth leakage circuit breaker and fuse to the power
supply line.

A main switch or other means for disconnection, having a
contact separation in all poles, must be incorporated in the fixed
wiring in accordance with relevant local and national legislation.
Note that the operation will restart automatically if the main
power supply is turned off and then turned back on again.

This system consists of multiple indoor units. Mark each indoor
unit as unit A, unit B..., and be sure the terminal block wiring to
the outdoor unit is matching properly. If wiring and piping
between the outdoor unit and an indoor unit are mismatched,
the system may cause a malfunction.

Be sure to ground the air conditioner.

Do not connect the ground wire to:
-

gas pipes: might cause explosions or fire if gas leaks.

-

telephone ground wires or lightning rods: might cause 
abnormally high electric potential in the ground during 
lightning storms.

-

plumbing pipes: no grounding effect if hard vinyl piping is 
used.

Make sure electrical wires are stripped
equally.

Electrical characteristics

MCA: Min. circuit Amps (A)
MFA: Max. Fuse Amps (A)

Caution for drain socket

Do not remove the drain pipe plug. Water might leak out.

The drain outlet is only used to discharge water if the drain
pump is not used or before maintenance. Gently put in and
out the drain plug. Excessive force may deform the drain
socket of the drain pan.

Pulling out the plug 

Do not wiggle the plug up and down

Pushing in the plug

Set the plug and push it by using a crosshead screw-
driver

1

Switch box cover

2

Transmission wiring port

3

Power supply wiring port

4

Wiring diagram

5

Switch box

6

Plastic clamp

7

Remote controller wiring

8

Terminal board for unit transmission wiring

9

Power supply wiring

10

Indoor PC board 1

11

Power supply terminal board

12

Transmission wiring between units

13

Indoor PC board 2

14

Indoor PC board 3 (only for 60~125 units)

1

1

2

1

Drain plug

2

Crosshead screwdriver

Model

Hz

Volts

Voltage range

Power supply

MCA

MFA

50

50/60

220-240/220

±10%

1.2

16 A

60

1.1

71

1.3

100

1.6

125

2.1

NOTE

For details, refer to "Electrical data" in the technical
data book.

Summary of Contents for FMDQ50B7VEB

Page 1: ...INSTALLATION AND OPERATION MANUAL FMDQ50B7VEB FMDQ60B7VEB FMDQ71B7VEB FMDQ100B7VEB FMDQ125B7VEB Air conditioning system...

Page 2: ...680 1 5 3 4 2 7 180 460 160 160 300 425 1 3 2 180 460 350 1 2 2 3 5 0 75 625 A 300 mm 1 1 5 m 2 3 1 4 100 mm 1 0 625 mm 1 1 2 4 5 3 6a 7a 7b 7c 6b 6c 8 9 10 11 2 1 3 5 4 700 630 A B 4 3 2 1 1 1 2 4 5...

Page 3: ...12 gitt i henhold til bestemmelsene i 13 noudattaen m r yksi 14 za dodr en ustanoven p edpisu 15 prema odredbama 16 k veti a z 17 zgodnie z postanowieniami Dyrektyw 18 n urma prevederilor 19 ob upo t...

Page 4: ...ontrol system may malfunction Where the air contains high levels of salt such as air near the ocean and where voltage fluctuates a lot e g in factories Also in vehicles or vessels Do not install acces...

Page 5: ...remote controller and indoor unit might be shorter if there are fluorescent lights who are electrically started in the room The indoor unit must be installed as far as possible away from fluorescent...

Page 6: ...Ceiling opening 3 Service access panel optional accessory 4 Air filter 5 Air inlet duct 6 Duct service opening 7 Interchangeable plate NOTE Before installation of the unit in case of installation wit...

Page 7: ...frigerant such as air etc inside the refrigerant circuit Use annealed material only for flare connections Refer to Table 1 for the dimensions of flare nut spaces and the appropriate tightening torque...

Page 8: ...rain raising pipes and insulate them 2 Connect the drain hose to the drain outlet on the indoor unit and tighten it with the clamp Precautions Install the drain raising pipes at a height of less than...

Page 9: ...ant local and national legislation Note that the operation will restart automatically if the main power supply is turned off and then turned back on again This system consists of multiple indoor units...

Page 10: ...ts less than 12 A Branch the line outside the terminal board of the unit in accordance with electrical equipment standards when using two power wiring of a gauge greater than 2 mm2 1 6 The branch must...

Page 11: ...10 000 hrs Heavy 5 000 hrs Long life filter 2 500 hrs 1 250 hrs Standard filter 200 hrs 100 hrs 2 Thermostat sensor selection Use both the unit sensor or remotesensorif installed AND the remote contr...

Page 12: ...s are only applicable to outdoor units After setting this function be sure to turn on the outdoor unit before performing the test operation on the outdoor unit If any other error display occurs on the...

Page 13: ...xtremely contaminated If the dirt becomes impossible to clean change the air filter Air filter for exchange is optional 1 Open the suction grille Only for bottom suction Slide both knobs simultaneousl...

Page 14: ...e air inlet and outlet are not blocked Remove any obstacle Check if the earth is connected Clean the air filter and outside panels After cleaning the air filter make sure to attach it Turn on the main...

Page 15: ...INAL STRIP POWER SUPPLY X2M TERMINAL STRIP CONTROL Y1E ELECTRONIC EXPANSION VALVE Z1C Z2C NOISE FILTER FERRITE CORE Z1F NOISE FILTER CONNECTOR OPTIONAL ACCESSORY X28A CONNECTOR POWER SUPPLY FOR WIRING...

Page 16: ...NOTES NOTES...

Page 17: ...2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 3 1 1 4 2 L N IN D OUT D F1 F2 F1 F2 Control box P1 P2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 2 5 3 SETTI...

Page 18: ...4PW48241 1 Copyright Daikin...

Reviews: