background image

 

FMDQ50~125B7VEB
Air conditioning system
4PW48241-1

Installation and operation manual

8

W

IRING

 

EXAMPLE

Fit the power supply wiring of each unit with a switch and fuse as
shown in 

figure 16

.

Complete system example (2 systems)

When using 1 remote controller for 1 indoor unit (Normal operation)

(See figure 13)

For group control or use with 2 remote controllers 

(See figure 15)

PRECAUTIONS

A single switch can be used to supply power to units on the
same system. However, branch switches and branch circuit
breakers must be selected carefully.

For a group control remote controller, choose the remote
controller that suits the indoor unit which has the most functions.

Do not ground the equipment on gas pipes, water pipes,
lightning rods or crossground with telephones. Improper
grounding could result in electric shock.

F

IELD

 

SETTING

Field setting must be made on the remote controller in function of the
installation condition.

Setting can be made by changing the "Mode number", "First
code No." and "Second code No.".

For setting and operation, refer to the "Field settings" in the
installation manual of the remote controller.

Summary of field settings

1

Power supply

2

Main switch

3

Power supply wiring

4

Transmission wiring

5

Switch

6

Fuse

7

Indoor unit

8

Remote controller

1

Outdoor unit

2

Indoor unit

3

Remote controller (optional accessories)

4

Most downstream indoor unit

5

For use with 2 remote controllers

NOTE

It is not necessary to designate an indoor unit address
when using group control. The address is
automatically set when the power is activated.

Mode 

No.

(Note 1)

First 

code 

No.

Description of setting

Second code No. (Note 2)

01

02

03

04

10 

(20)

0

Filter contamination 
- Heavy/Light
= Setting to define 
time between 2 filter 
cleaning display 
indications. (When 
contamination is 
high, setting can be 
changed to half the 
time inbetween 2 
filter cleaning 
display indications.)

Ultra-long-
life filter

Light

±10,000 hrs.

Hea

vy

±5,000 hrs.

Long-life 
filter

±2,500 hrs.

±1,250 hrs.

Standard 
filter

±200 hrs.

±100 hrs.

2

Thermostat sensor selection

Use both the 
unit sensor (or 
remote sensor if 
installed) AND 
the remote 
controller 
sensor. 
(See note 5+6)

Use unit sensor 
only (or remote 
sensor if 
installed). 
(See note 5+6)

Use remote 
controller 
sensor only. 
(See note 5+6)

3

Setting for display of time 
between 2 filter cleaning display 
indications

Display

Do not display

6

Thermostat sensor in group 
control

Use unit sensor 
only (or remote 
sensor if 
installed). 
(See note 6)

Use both the 
unit senor (or 
remote sensor if 
installed) AND 
the remote 
controller 
sensor. (See 
note 4+5+6)

12 

(22)

0

Output signal X1-X2 of the 
optional KRP1B PCB kit

Thermostat-on + 
compressor run

Operation

Mal-
function

1

ON/OFF input from outside 
(T1/T2 input) = Setting when 
forced ON/OFF is to be 
operated from outside.

Forced OFF

ON/OFF
operation

3

Fan setting during thermostat 
OFF at heating operation

LL

Set speed

OFF 
(See note 3)

4

Differential automatic 
changeover

0°C

1°C

2°C

3°C
(See 
note 7)

5

Auto-restart after power failure

Disabled

Enabled

9

Fixed cool/heat master

Disabled

Enabled

15 

(25)

3

Drain pump ope 
humidifier interlock

Equipped

Not equipped

Note 1 : Setting is carried out in the group mode, however, if the mode number inside parentheses is selected, 

indoor units can also be set individually.

Note 2 : Factory settings of the Second code No. are marked in grey backgrounds.
Note 3 : Only use in combination with optional remote sensor or when setting 10-2-03 is used.
Note 4 : If group control is selected and remote controller sensor is to be used, then set 10-6-02 & 10-2-03.
Note 5 : If setting 10-6-02 + 10-2-01 or 10-2-02 or 10-2-03 are set at the same time, then setting 10-2-01, 

10-2-02 or 10-2-03 have priority.

Note 6 : If setting 10-6-01 + 10-2-01 or 10-2-02 or 10-2-03 are set at the same time, then setting for group 

connection, 10-6-01 has priority and for individual connection, 10-2-01, 10-2-02 or 10-2-03 have 
priority.

Note 7 : More settings for Differential automatic change over temperatures are:

Second code No.

05

4°C

06

5°C

07

6°C

08

7°C

Summary of Contents for FMDQ50B7VEB

Page 1: ...INSTALLATION AND OPERATION MANUAL FMDQ50B7VEB FMDQ60B7VEB FMDQ71B7VEB FMDQ100B7VEB FMDQ125B7VEB Air conditioning system...

Page 2: ...680 1 5 3 4 2 7 180 460 160 160 300 425 1 3 2 180 460 350 1 2 2 3 5 0 75 625 A 300 mm 1 1 5 m 2 3 1 4 100 mm 1 0 625 mm 1 1 2 4 5 3 6a 7a 7b 7c 6b 6c 8 9 10 11 2 1 3 5 4 700 630 A B 4 3 2 1 1 1 2 4 5...

Page 3: ...12 gitt i henhold til bestemmelsene i 13 noudattaen m r yksi 14 za dodr en ustanoven p edpisu 15 prema odredbama 16 k veti a z 17 zgodnie z postanowieniami Dyrektyw 18 n urma prevederilor 19 ob upo t...

Page 4: ...ontrol system may malfunction Where the air contains high levels of salt such as air near the ocean and where voltage fluctuates a lot e g in factories Also in vehicles or vessels Do not install acces...

Page 5: ...remote controller and indoor unit might be shorter if there are fluorescent lights who are electrically started in the room The indoor unit must be installed as far as possible away from fluorescent...

Page 6: ...Ceiling opening 3 Service access panel optional accessory 4 Air filter 5 Air inlet duct 6 Duct service opening 7 Interchangeable plate NOTE Before installation of the unit in case of installation wit...

Page 7: ...frigerant such as air etc inside the refrigerant circuit Use annealed material only for flare connections Refer to Table 1 for the dimensions of flare nut spaces and the appropriate tightening torque...

Page 8: ...rain raising pipes and insulate them 2 Connect the drain hose to the drain outlet on the indoor unit and tighten it with the clamp Precautions Install the drain raising pipes at a height of less than...

Page 9: ...ant local and national legislation Note that the operation will restart automatically if the main power supply is turned off and then turned back on again This system consists of multiple indoor units...

Page 10: ...ts less than 12 A Branch the line outside the terminal board of the unit in accordance with electrical equipment standards when using two power wiring of a gauge greater than 2 mm2 1 6 The branch must...

Page 11: ...10 000 hrs Heavy 5 000 hrs Long life filter 2 500 hrs 1 250 hrs Standard filter 200 hrs 100 hrs 2 Thermostat sensor selection Use both the unit sensor or remotesensorif installed AND the remote contr...

Page 12: ...s are only applicable to outdoor units After setting this function be sure to turn on the outdoor unit before performing the test operation on the outdoor unit If any other error display occurs on the...

Page 13: ...xtremely contaminated If the dirt becomes impossible to clean change the air filter Air filter for exchange is optional 1 Open the suction grille Only for bottom suction Slide both knobs simultaneousl...

Page 14: ...e air inlet and outlet are not blocked Remove any obstacle Check if the earth is connected Clean the air filter and outside panels After cleaning the air filter make sure to attach it Turn on the main...

Page 15: ...INAL STRIP POWER SUPPLY X2M TERMINAL STRIP CONTROL Y1E ELECTRONIC EXPANSION VALVE Z1C Z2C NOISE FILTER FERRITE CORE Z1F NOISE FILTER CONNECTOR OPTIONAL ACCESSORY X28A CONNECTOR POWER SUPPLY FOR WIRING...

Page 16: ...NOTES NOTES...

Page 17: ...2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 3 1 1 4 2 L N IN D OUT D F1 F2 F1 F2 Control box P1 P2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 2 5 3 SETTI...

Page 18: ...4PW48241 1 Copyright Daikin...

Reviews: