7 Disposal

Installation manual

10

FDXM25~60F3V1B(9)

Split system air conditioners

4P472267-1B – 2018.07

#

Action

4

On the user interface, set the unit to cooling operation
mode.

2

Start the test run

#

Action

Result

1

Go to the home menu.

Cool

Set to

28

°C

2

Press at least 4 seconds.

The Service Settings menu
is displayed.

3

Select Test Operation.

Return

Setting

Service Settings                   1/3

Test Operation

Maintenance Contact

Field Settings

Demand

Min Setpoints Differential

Group Address

4

Press.

Test Operation is
displayed on the home
menu.

Cool

Return

Setting

Test Operation

5

Press within 10 seconds.

Test run starts.

3

Check operation for 3 minutes.

4

Stop the test run.

#

Action

Result

1

Press at least 4 seconds.

The Service Settings menu
is displayed.

2

Select Test Operation.

Return

Setting

Service Settings                   1/3

Test Operation

Maintenance Contact

Field Settings

Demand

Min Setpoints Differential

Group Address

3

Press.

The unit returns to normal
operation, and the home
menu is displayed.

6.3

Error codes when performing a
test run

If  the  installation  of  the  outdoor  unit  has  NOT  been  done  correctly,
the following error codes may be displayed on the user interface:

Error code

Possible cause

Nothing displayed

(the currently set
temperature is not
displayed)

▪ The  wiring  is  disconnected  or  there  is  a

wiring  error  (between  power  supply  and
outdoor  unit,  between  outdoor  unit  and
indoor  units,  between  indoor  unit  and
user interface).

▪ The  fuse  on  the  outdoor  or  indoor  unit

PCB has blown.

E3, E4 or L8

▪ The stop valves are closed.

▪ The air inlet or air outlet is blocked.

E7

There is a missing phase in case of three-
phase power supply units.

Note: 

Operation will be impossible. Turn

OFF the power, recheck the wiring, and
switch two of the three electrical wires.

L4

The air inlet or air outlet is blocked.

U0

The stop valves are closed.

U2

▪ There is a voltage imbalance.

▪ There  is  a  missing  phase  in  case  of

three-phase  power  supply  units. 

Note:

Operation  will  be  impossible.  Turn  OFF
the power, recheck the wiring, and switch
two of the three electrical wires.

U4 or UF

The inter-unit branch wiring is not correct.

UA

The outdoor and indoor unit are
incompatible.

7

Disposal

NOTICE

Do  NOT  try  to  dismantle  the  system  yourself:  dismantling
of  the  system,  treatment  of  the  refrigerant,  oil  and  other
parts  MUST  comply  with  applicable  legislation.  Units
MUST  be  treated  at  a  specialised  treatment  facility  for
reuse, recycling and recovery.

8

Technical data

▪ A 

subset

  of  the  latest  technical  data  is  available  on  the  regional

Daikin website (publicly accessible).

▪ The 

full  set

  of  latest  technical  data  is  available  on  the  Daikin

extranet (authentication required).

Summary of Contents for FDXM25F3V1B9

Page 1: ...allation manual Split system air conditioners English Installation manual Split system air conditioners FDXM25F3V1B FDXM35F3V1B FDXM50F3V1B FDXM60F3V1B FDXM25F3V1B9 FDXM35F3V1B9 FDXM50F3V1B9 FDXM60F3V...

Page 2: ...ca acestea s fie utilizate n conformitate cu instruc iunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili on vastavuses j rgmis...

Page 3: ...acestea s fie utilizate n conformitate cu instruc iunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili on vastavuses j rgmis t...

Page 4: ...s or for commercial and household use by lay persons Documentation set This document is part of a documentation set The complete set consists of General safety precautions Safety instructions that you...

Page 5: ...d a mm 400 A Minimum distance to the floor 2 7 m to avoid accidental touching 2 5 m in case the fan is covered e g false ceiling grille a Control box b Maintenance space c Ceiling d Floor surface e Se...

Page 6: ...rear suction bottom suction 2 1 2 1 Install the unit temporarily 6 Attach the hanger bracket to the suspension bolt 7 Fix the unit securely Level Make sure the unit is level at all four corners using...

Page 7: ...00 to prevent air from being trapped in the piping Use hanging bars as shown 1 1 5 m a a Hanging bar O Allowed X Not allowed Condensation Take measures against condensation Insulate the complete drain...

Page 8: ...recommended bubble test solution from your wholesaler Do not use soap water which may cause cracking of flare nuts soap water may contain salt which absorbs moisture that will freeze when the piping g...

Page 9: ...e properly mounted In case a wireless user interface is used The indoor unit decoration panel with infrared receiver is installed The outdoor unit is properly mounted There are NO missing phases or re...

Page 10: ...ly set temperature is not displayed The wiring is disconnected or there is a wiring error between power supply and outdoor unit between outdoor unit and indoor units between indoor unit and user inter...