5 Installation

Installation manual

8

FDXM25~60F3V1B(9)

Split system air conditioners

4P472267-1B – 2018.07

c

Bucket

d

Refrigerant pipes

e

Drain outlet

5.2

Connecting the refrigerant piping

DANGER: RISK OF BURNING

5.2.1

To connect the refrigerant piping to the
indoor unit

CAUTION

Install refrigerating pipe or components in a position where
they  are  unlikely  to  be  exposed  to  any  substance  which
may corrode refrigerant containing components, unless the
components  are  constructed  of  materials  which  are
inherently  resistant  to  being  corroded  or  are  suitably
protected against being so corroded.

WARNING: FLAMMABLE MATERIAL

The  R32  refrigerant  (if  applicable)  in  this  unit  is  mildly
flammable.  Refer  to  the  outdoor  unit  specifications  for  the
type of refrigerant to be used.

Pipe length

. Keep refrigerant piping as short as possible.

Flare  connections

.  Connect  refrigerant  piping  to  the  unit  using

flare connections.

Insulation

.  Insulate  the  refrigerant  piping  on  the  indoor  unit  as

follows:

A

B

a

d

c

e f

b

b

a

d

c

e f

b

b

2

4

3

g

1

2

3

4

g

A

B

1

A

Gas piping

B

Liquid piping

a

Insulation material (field supply)

b

Cable tie (accessory)

c

Insulation pieces: Large (gas pipe), small (liquid pipe)
(accessories)

d

Flare nut (attached to the unit)

e

Refrigerant pipe connection (attached to the unit)

f

Unit

g

Sealing pads: Medium 1 (gas pipe), medium 2 (liquid pipe)
(accessories)

1

Turn up the seams of the insulation pieces.

2

Attach to the base of the unit.

3

Tighten the cable ties on the insulation pieces.

4

Wrap the sealing pad from the base of the unit to the top of
the flare nut.

NOTICE

Make  sure  to  insulate  all  refrigerant  piping.  Any  exposed
piping might cause condensation.

5.2.2

To check for leaks

NOTICE

Do NOT exceed the unit's maximum working pressure (see
"PS High" on the unit name plate).

NOTICE

Make  sure  to  use  a  recommended  bubble  test  solution
from  your  wholesaler.  Do  not  use  soap  water,  which  may
cause cracking of flare nuts (soap water may contain salt,
which  absorbs  moisture  that  will  freeze  when  the  piping
gets  cold),  and/or  lead  to  corrosion  of  flared  joints  (soap
water  may  contain  ammonia  which  causes  a  corrosive
effect between the brass flare nut and the copper flare).

1

Charge the system with nitrogen gas up to a gauge pressure of
at  least  200  kPa  (2  bar).  It  is  recommended  to  pressurize  to
3000 kPa (30 bar) in order to detect small leaks.

2

Check  for  leaks  by  applying  the  bubble  test  solution  to  all
connections.

3

Discharge all nitrogen gas.

5.3

Connecting the electrical wiring

DANGER: RISK OF ELECTROCUTION

WARNING

ALWAYS use multicore cable for power supply cables.

WARNING

If the supply cord is damaged, it MUST be replaced by the
manufacturer,  its  service  agent  or  similarly  qualified
persons in order to avoid a hazard.

5.3.1

To connect the electrical wiring on the
indoor unit

It is important to keep the power supply and the transmission wiring
separated  from  each  other.  In  order  to  avoid  any  electrical
interference  the  distance  between  both  wirings  should  ALWAYS  be
at least 50 mm.

NOTICE

Be sure to keep the power line and transmission line apart
from  each  other.  Transmission  wiring  and  power  supply
wiring may cross, but may NOT run parallel.

1

Remove the service cover.

a c

b

d

A B

e

f

e

g

g

A

Outside the unit

B

Inside the unit

a

Control box cover

b

Connection of interconnection cable (including earth)

c

Wiring diagram

d

Connection of user interface wiring

e

Sealing material (accessory)

f

Opening for cables

g

Wire

2

User  interface  cable

:  Route  the  cable  through  the  frame,

connect the cable to the terminal block, and fix the cable with a
cable tie.

3

Interconnection  cable

  (indoor↔outdoor):  Route  the  cable

through  the  frame,  connect  the  cable  to  the  terminal  block
(make  sure  the  numbers  match  with  the  numbers  on  the
outdoor unit, and connect the earth wire), and fix the cable with
a cable tie.

Summary of Contents for FDXM25F3V1B9

Page 1: ...allation manual Split system air conditioners English Installation manual Split system air conditioners FDXM25F3V1B FDXM35F3V1B FDXM50F3V1B FDXM60F3V1B FDXM25F3V1B9 FDXM35F3V1B9 FDXM50F3V1B9 FDXM60F3V...

Page 2: ...ca acestea s fie utilizate n conformitate cu instruc iunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili on vastavuses j rgmis...

Page 3: ...acestea s fie utilizate n conformitate cu instruc iunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili on vastavuses j rgmis t...

Page 4: ...s or for commercial and household use by lay persons Documentation set This document is part of a documentation set The complete set consists of General safety precautions Safety instructions that you...

Page 5: ...d a mm 400 A Minimum distance to the floor 2 7 m to avoid accidental touching 2 5 m in case the fan is covered e g false ceiling grille a Control box b Maintenance space c Ceiling d Floor surface e Se...

Page 6: ...rear suction bottom suction 2 1 2 1 Install the unit temporarily 6 Attach the hanger bracket to the suspension bolt 7 Fix the unit securely Level Make sure the unit is level at all four corners using...

Page 7: ...00 to prevent air from being trapped in the piping Use hanging bars as shown 1 1 5 m a a Hanging bar O Allowed X Not allowed Condensation Take measures against condensation Insulate the complete drain...

Page 8: ...recommended bubble test solution from your wholesaler Do not use soap water which may cause cracking of flare nuts soap water may contain salt which absorbs moisture that will freeze when the piping g...

Page 9: ...e properly mounted In case a wireless user interface is used The indoor unit decoration panel with infrared receiver is installed The outdoor unit is properly mounted There are NO missing phases or re...

Page 10: ...ly set temperature is not displayed The wiring is disconnected or there is a wiring error between power supply and outdoor unit between outdoor unit and indoor units between indoor unit and user inter...

Page 11: ...LED V L PILOT LAMP LIGHT EMITTING DIODE HAP LIGHT EMITTING DIODE SERVICE MONITOR GREEN HIGH VOLTAGE HIGH VOLTAGE IES INTELLIGENT EYE SENSOR IPM INTELLIGENT POWER MODULE K R KCR KFR KHuR K M MAGNETIC...

Page 12: ...4P472267 1B 2018 07 Copyright 2017 Daikin...

Reviews: