6 Commissioning

Installation manual

9

FDXM25~60F3V1B(9)
Split system air conditioners
4P472267-1B – 2018.07

4

Wrap  the  cables  with  the  sealing  material  (accessory)  to
prevent  water  from  entering  the  unit.  Seal  all  gaps  to  prevent
small animals from entering the system.

WARNING

Provide adequate measures to prevent that the unit can be
used  as  a  shelter  by  small  animals.  Small  animals  that
make contact with electrical parts can cause malfunctions,
smoke or fire.

A

a

c

b

c

A

Indoor PCB (ASSY)

a

Power supply and earth wiring

b

Transmission and user interface wiring

c

Clamps

X

Not allowed

O

Allowed

5

Reattach the service cover.

1~ 50 Hz

220-240 V

b

a

e

c

d

a

Interconnection cable

b

Power supply cable

c

Earth leakage circuit breaker

d

Fuse

e

User interface

5.3.2

Specifications of standard wiring
components

Component

Specification

Interconnection cable
(indoor↔outdoor)

Minimum cable section of

2.5 mm² and applicable for

230 V

User interface cable

Vinyl cords with 0.75 to

1.25 mm² sheath or cables

(2‑core wires)

Maximum 500 m

6

Commissioning

NOTICE

NEVER  operate  the  unit  without  thermistors  and/or
pressure  sensors/switches.  Burning  of  the  compressor
might result.

6.1

Checklist before commissioning

After the installation of the unit, first check the following items. Once
all  below  checks  are  fulfilled,  the  unit  MUST  be  closed,  ONLY  then
can the unit be powered up.

You  read  the  complete  installation  instructions,  as
described in the 

installer reference guide

.

The 

indoor units

 are properly mounted.

In case a wireless user interface is used: The 

indoor unit

decoration panel

 with infrared receiver is installed.

The 

outdoor unit

 is properly mounted.

There are NO 

missing phases

 or 

reversed phases

.

The  system  is  properly 

earthed

  and  the  earth  terminals

are tightened.

The 

fuses

  or  locally  installed  protection  devices  are

installed according to this document, and have NOT been
bypassed.

The 

power  supply  voltage

  matches  the  voltage  on  the

identification label of the unit.

There  are  NO 

loose  connections

  or  damaged  electrical

components in the switch box.

The 

insulation resistance

 of the compressor is OK.

There  are  NO 

damaged  components

  or 

squeezed

pipes

 on the inside of the indoor and outdoor units.

There are NO 

refrigerant leaks

.

The  correct  pipe  size  is  installed  and  the 

pipes

  are

properly insulated.

The 

stop valves

 (gas and liquid) on the outdoor unit are

fully open.

6.2

To perform a test run

This  task  is  only  applicable  when  using  the  BRC1E52  or  BRC1E53
user  interface.  When  using  any  other  user  interface,  see  the
installation manual or service manual of the user interface.

NOTICE

Do not interrupt the test run.

INFORMATION

Backlight.

  To  perform  an  ON/OFF  action  on  the  user

interface,  the  backlight  does  not  need  to  be  lit.  For  any
other  action,  it  needs  to  be  lit  first.  The  backlight  is  lit  for
±30 seconds when you press a button.

1

Perform introductory steps.

#

Action

1

Open the liquid stop valve (A) and gas stop valve (B)
by removing the stem cap and turning
counterclockwise with a hex wrench until it stops.

A

B

2

Close the service cover to prevent electric shocks.

3

Turn ON power for at least 6 hours before starting
operation to protect the compressor.

Summary of Contents for FDXM25F3V1B9

Page 1: ...allation manual Split system air conditioners English Installation manual Split system air conditioners FDXM25F3V1B FDXM35F3V1B FDXM50F3V1B FDXM60F3V1B FDXM25F3V1B9 FDXM35F3V1B9 FDXM50F3V1B9 FDXM60F3V...

Page 2: ...ca acestea s fie utilizate n conformitate cu instruc iunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili on vastavuses j rgmis...

Page 3: ...acestea s fie utilizate n conformitate cu instruc iunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili on vastavuses j rgmis t...

Page 4: ...s or for commercial and household use by lay persons Documentation set This document is part of a documentation set The complete set consists of General safety precautions Safety instructions that you...

Page 5: ...d a mm 400 A Minimum distance to the floor 2 7 m to avoid accidental touching 2 5 m in case the fan is covered e g false ceiling grille a Control box b Maintenance space c Ceiling d Floor surface e Se...

Page 6: ...rear suction bottom suction 2 1 2 1 Install the unit temporarily 6 Attach the hanger bracket to the suspension bolt 7 Fix the unit securely Level Make sure the unit is level at all four corners using...

Page 7: ...00 to prevent air from being trapped in the piping Use hanging bars as shown 1 1 5 m a a Hanging bar O Allowed X Not allowed Condensation Take measures against condensation Insulate the complete drain...

Page 8: ...recommended bubble test solution from your wholesaler Do not use soap water which may cause cracking of flare nuts soap water may contain salt which absorbs moisture that will freeze when the piping g...

Page 9: ...e properly mounted In case a wireless user interface is used The indoor unit decoration panel with infrared receiver is installed The outdoor unit is properly mounted There are NO missing phases or re...

Page 10: ...ly set temperature is not displayed The wiring is disconnected or there is a wiring error between power supply and outdoor unit between outdoor unit and indoor units between indoor unit and user inter...

Page 11: ...LED V L PILOT LAMP LIGHT EMITTING DIODE HAP LIGHT EMITTING DIODE SERVICE MONITOR GREEN HIGH VOLTAGE HIGH VOLTAGE IES INTELLIGENT EYE SENSOR IPM INTELLIGENT POWER MODULE K R KCR KFR KHuR K M MAGNETIC...

Page 12: ...4P472267 1B 2018 07 Copyright 2017 Daikin...

Reviews: