5 Installation

Installation manual

6

FDXM25~60F3V1B(9)

Split system air conditioners

4P472267-1B – 2018.07

d

e

A

B

f

620

500

f

a1

b

b

a2

c

Class

A (mm)

B (mm)

35

740

790

60

1140

1190

a1

Nut (field supply)

a2

Double nut (field supply)

b

Washer (accessories)

c

Hanger bracket

d

Control box

e

Suspension bolt pitch

f

Overall dimension

External  static  pressure. 

Refer  to  technical  documentation  to

ensure that the unit's external static pressure is not exceeded.

Ceiling opening. 

(Ceiling with opening for installation)

1

Pass  all  pipes  and  wiring  through  the  unit's  piping  and  wiring
holes.

2

Make sure that the ceiling is level.

Installation example:

b

a

c

e

d

a

Anchor bolt

b

Ceiling slab

c

Long nut or turn-buckle

d

Suspension bolt

e

Indoor unit

Install  suction  cover  and  air  filter  (accessory)

  In  case  of

bottom suction:

3

Remove the suction cover.

c

a

b

4

Reattach the removed suction cover.

c

b

a

a

Air inlet

b

Air outlet

c

Suction cover

5

Attach  the  air  filter  (accessory)  by  pushing  down  the  hooks  (2
hooks for 25+35 type, 3 hooks for 50+60 type).

rear suction

bottom suction

2

1

2

1

Install the unit temporarily.

6

Attach the hanger bracket to the suspension bolt.

7

Fix the unit securely.

Level

. Make sure the unit is level at all four corners using a level

or a water-filled vinyl tube.

b

a

a

Level

b

Vinyl tube

8

Tighten the upper nut.

NOTICE

Do  NOT  install  the  unit  tilted. 

Possible  consequence: 

If

the unit is tilted against the direction of the condensate flow
(the  drain  piping  side  is  raised),  the  float  switch  might
malfunction and cause water to drip.

5.1.2

Guidelines when installing the ducting

WARNING

If  the  one  or  more  rooms  are  connected  with  the  unit  via
duct system make sure:

▪ there are no operating ignition sources (example: open

flames,  an  operating  gas  appliance  or  an  operating
electric  heater)  in  case  the  floor  area  is  less  than  A

min

specified in the General safety precautions;

▪ no  auxiliary  devices,  which  may  be  a  potential  ignition

source,  are  installed  in  the  duct  work  (example:  hot
surfaces  with  a  temperature  exceeding  700°C  and
electric switching device);

▪ only  auxiliary  devices  approved  by  manufacturer  are

used in the duct work.

WARNING

Do  NOT  install  operating  ignition  sources  (example:  open
flames, an operating gas appliance or an operating electric
heater) in the duct work.

Summary of Contents for FDXM25F3V1B9

Page 1: ...allation manual Split system air conditioners English Installation manual Split system air conditioners FDXM25F3V1B FDXM35F3V1B FDXM50F3V1B FDXM60F3V1B FDXM25F3V1B9 FDXM35F3V1B9 FDXM50F3V1B9 FDXM60F3V...

Page 2: ...ca acestea s fie utilizate n conformitate cu instruc iunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili on vastavuses j rgmis...

Page 3: ...acestea s fie utilizate n conformitate cu instruc iunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili on vastavuses j rgmis t...

Page 4: ...s or for commercial and household use by lay persons Documentation set This document is part of a documentation set The complete set consists of General safety precautions Safety instructions that you...

Page 5: ...d a mm 400 A Minimum distance to the floor 2 7 m to avoid accidental touching 2 5 m in case the fan is covered e g false ceiling grille a Control box b Maintenance space c Ceiling d Floor surface e Se...

Page 6: ...rear suction bottom suction 2 1 2 1 Install the unit temporarily 6 Attach the hanger bracket to the suspension bolt 7 Fix the unit securely Level Make sure the unit is level at all four corners using...

Page 7: ...00 to prevent air from being trapped in the piping Use hanging bars as shown 1 1 5 m a a Hanging bar O Allowed X Not allowed Condensation Take measures against condensation Insulate the complete drain...

Page 8: ...recommended bubble test solution from your wholesaler Do not use soap water which may cause cracking of flare nuts soap water may contain salt which absorbs moisture that will freeze when the piping g...

Page 9: ...e properly mounted In case a wireless user interface is used The indoor unit decoration panel with infrared receiver is installed The outdoor unit is properly mounted There are NO missing phases or re...

Page 10: ...ly set temperature is not displayed The wiring is disconnected or there is a wiring error between power supply and outdoor unit between outdoor unit and indoor units between indoor unit and user inter...

Page 11: ...LED V L PILOT LAMP LIGHT EMITTING DIODE HAP LIGHT EMITTING DIODE SERVICE MONITOR GREEN HIGH VOLTAGE HIGH VOLTAGE IES INTELLIGENT EYE SENSOR IPM INTELLIGENT POWER MODULE K R KCR KFR KHuR K M MAGNETIC...

Page 12: ...4P472267 1B 2018 07 Copyright 2017 Daikin...