background image

English

5

SELECTING INSTALLATION SITE

Condensation may occur if the relative humidity within the ceiling is 
beyond 80%, or if the unit intakes outside air whose temperature is
–5°C or below during heating. Install an emergency drain pan (field 
supply) under the unit to prevent water leakage.

1

Select an installation site where the following conditions and 
the customer’s requirements are satisfied. 

• Where optimum air distribution is available.
• Where nothing blocks air passage.
• Where condensate can be properly drained.
• Where the ceiling is strong enough to bear the indoor unit weight.
• Where the false ceiling is not noticeably on an incline.
• Where sufficient clearance for maintenance and service can be 

ensured. (Refer to Fig. 2)

• Where there is no risk of flammable gas leakage.
• The belt needs regular maintenance.
• Where piping between indoor and outdoor units is possible within 

the allowable limit. (Refer to the installation manual for the out-
door unit.)

• The unit is not for use where silent operation is required.

Install the unit in a place such as an equipment room where noise 
is not a problem.

• Install the inspection opening at the side of the control box for the 

convenience of maintenance and inspection.

• Place the unit so that the outlet vent does not blow air directly on 

occupants of the room.

• Do not install the air inlet of the air conditioner at places such as 

factories and kitchens, where oil or dust may be taken in.

• Keep indoor unit, outdoor unit, power supply wiring and transmis-

sion wiring at least 1 meter away from televisions and radios. This 
is to prevent image interference and noise in those electrical 
appliances.
(Noise may be generated depending on the conditions under 
which the electric wave is generated, even at the distance of 
1 meter.)

2

Use suspension bolts for installation. Check whether the ceil-
ing is strong enough to support the weight of the unit or not. If 
there is a risk of falling, reinforce the ceiling before installing 
the unit.

3

When exposing the body of this unit, install the unit where the 
bottom is more than 2.5 m high out of the customer’s reach.

4

The air filter (field supply) must be installed within the duct.
(Refer to Fig. 3) A return air filter must be installed during the 
operation of the air conditioner.
• Please choose an appropriate air filter according to the 

actual conditions of the intake air; otherwise it may lead to 
dirtiness, low performance or water leakage of the heat 
exchanger.

Fig. 2

Service 

space

800 or more

(Air inlet duct)

Air outlet duct

Air flow 

passage

Inspection hatch

(   450)

500 or more

500 or more

300 or more

100

500 or more

Service space

[Unit:mm]

Fig. 3

Supporting plate
(field supply)

Return air filter 
(field supply)

500 or more

770 or more

50 or more

Service cover 1(R)

Provide enough clearance between 
the unit and the surrounding walls 
to prevent contact.

Ceiling surface

For maintenance of control box, the 
suspension bolts should be 500 mm 
or more away from the unit.

[Unit:mm]

01_EN_3PR05311-2.fm  Page 5  Tuesday, June 2, 2009  4:39 PM

Summary of Contents for FDQ16PY1

Page 1: ...ODELS Duct Connection type FDQ16PY1 FDQ20PY1 FDQ16PYL FDQ20PYL READ THESE INSTRUCTIONS CAREFULLY BEFORE INSTALLATION KEEP THIS MANUAL IN A HANDY PLACE FOR FUTURE REFERENCE English 01_CV1_3PR05311 2 fm...

Page 2: ...ORE INSTALLATION 6 REPLACING FAN MOTOR PULLEY AND V BELT 8 INSTALLATION OF THE INDOOR UNIT 9 REFRIGERANT PIPING WORK 10 DRAIN PIPING WORK 11 INSTALLING THE DUCT 12 ELECTRIC WIRING WORK 12 FIELD SETTIN...

Page 3: ...ified installation work after taking into account strong winds typhoons or earthquakes Failure to do so during installation work may result in the unit falling and causing accidents Make sure that a s...

Page 4: ...cord and connecting wires at least 1 meter away from televisions or radios to prevent picture interference and noise Depending on the incoming signal strength a distance of 1 meter may not be suffici...

Page 5: ...NUAL FOR REMOTE CONTROLLER Indoor and outdoor unit combinations Do not use in any combination other than those shown below Refer to Fig 1 This unit cannot be connected with other standard indoor units...

Page 6: ...ut Are wiring and piping correct The unit may malfunction or the components burn out Is the unit safely grounded It may result in electric shock Is wiring size according to specifications The unit may...

Page 7: ...il or dust may be taken in Keep indoor unit outdoor unit power supply wiring and transmis sion wiring at least 1 meter away from televisions and radios This is to prevent image interference and noise...

Page 8: ...the air condi tioner and install it to the support plate After removing the control box please retighten the screws to their original posi tions When moving the control box do not apply force to the...

Page 9: ...ngs to reinforce the ceiling to bear the weight of the indoor unit 5 When adjusting air flow volume and external static pressure please change the motor pulley and V belt 665 296 349 1045 100 or more...

Page 10: ...al block 12 Install the new V belt f 13 Fasten the adjustment nuts b 1 2 3 Move the motor stand c so as to tighten the V belt f 14 Adjust the levelness of the fan pulley e and motor pulley g and the s...

Page 11: ...per and lower nuts to the suspension bolt 2 Adjust the unit to the preset height 3 Make sure that the unit is level Adjust the unit using a level gauge If it is installed unevenly water may leak from...

Page 12: ...heating the pipe cut the end of the plug in order to remove it Refer to Fig 10 After brazing these pipes as shown in Fig 11 use the fitting insulation to secure the pipe inside of the unit Refer to F...

Page 13: ...side The drain plug can be removed and placed on either the left or right side as well For best results try to keep the piping as short as possible Slant the piping at an angle to improve flow Refer t...

Page 14: ...attached to the remote controller All wiring must be performed by an authorized electrician A circuit breaker capable of shutting down power supply to the entire system must be installed The resistanc...

Page 15: ...iping completely Refer to Fig 12 2 Check that the wires are not trapped in the control box lid or service cover Do not clamp remote controller cords together with wires connecting the units together D...

Page 16: ...ansmission wiring ground the shield of the shield wire to at the grounding screw of the remote con troller cord grounding terminal inside the control box NOTE 1 Power wiring Fig 16 Fig 15 NOTE 2 3 Gro...

Page 17: ...ing impossible Over tightening may damage terminal screws See the table below for tightening torque for the terminal screws Precautions when connecting the ground terminal When connecting the ground w...

Page 18: ...explains FORCED OFF and ON OFF OPERATIONS in response to Input A 3 How to select FORCED OFF and ON OFF OPERATION See FIELD SETTING FORCED OFF ON OFF OPERATION Input ON stops operation impossible by re...

Page 19: ...manual of the outdoor unit The operation lamp of the remote controller will flash when an malfunction occurs Check the malfunction code on the liquid crys tal display to identify the point of trouble...

Page 20: ...0906 HT 3PR05311 2 EM09A005 01_CV1_3PR05311 2 fm Page 2 Thursday May 21 2009 2 30 PM...

Reviews: