background image

10

English

REFRIGERANT PIPING WORK

< Refer to the attached installation manual for the outdoor unit for its refrigerant piping.>

<Provide heat insulation work completely on both sides of the gas piping and the liquid piping. Otherwise it may result in water leak-
age. (Please use insulation materials which can bear high temperatures of 120°C or above.) The heat insulation layer of the refriger-
ant piping has to be thickened (with the thickness above 20 mm) if the temperature exceeds 30°C and the humidity is above 80% RH 
at the refrigerant piping; otherwise condensation may occure on the surface of the insulation materials.>
<Before refrigerant piping work, check which type of refrigerant is used. The machine may not work properly if incorrect refrigerant is 
used.>

CAUTION

• Use a pipe cutter and flare tool suitable for the type of refrigerant.
• Apply refrigerant oil or either oil around the flare portions before connecting.
• To prevent dust, moisture or other foreign matter from infiltrating the tube, pinch or enclose the ends of the tube.
• Do not allow anything other than the designated refrigerant to get mixed into the refrigerant circuit, such as air, etc.

If any refrigerant gas leaks, ventilate the room thoroughly right away.

• The outdoor unit is already charged with refrigerant.
• Use a common wrench and a torque wrench when installing/removing the piping of the machine, as illustrated herein.
• Please ensure good ventilation at the installation site since leakage from the refrigerant pipelines may occur during installation.

Check the size of the refrigerant piping with the chart below.

• Fill the indoor unit with refrigerant.

See the installation manual that came with the outdoor unit for details on the refrigerant piping.

• Remove the cardboard. Before heating the pipe, cut the end of the plug in order to remove it. (Refer to Fig.10)
• After brazing these pipes as shown in Fig.11, use the fitting insulation to secure the pipe inside of the unit . (Refer to Figs.12-1 and 13)
• Install the clamps as close to the body as possible to absorb leaking condensation. After clamping, wrap the clamp with insulation 

(field supply). This is to prevent condensation from forming on the clamp section.

• Wrap the fitting insulation’s joints with tape (field supply), making sure that there is no gap between the fitting insulation. (Refer to 

Fig.12-2)

• Prevent any gas mixture other than the specified refrigerant from entering into the refrigerating cycle.
• Please ensure good ventilation at the installation site if leakage of refrigerant gas occurs during installation.
• Insulate the connecting pipelines completely because the temperature at the gas piping may reach up to 120°C during the heating 

process.
Use fitting insulation which can endure the highest temperature.

(L=Insertion length, refer to Fig. 11)

Model

Refrigerant piping size

Gas pipe

Liquid pipe

FDQ16

φ

28.6  L=12

φ

12.7  L=8

FDQ20

φ

28.6  L=12

φ

15.9  L=8

WARNING

• Do not heat the plugs before cutting off their ends in 

order to release pressure, otherwise the plugs may 
burst.

• Be careful not to burn the body of air conditioner when 

brazing the pipe.

• Wrap the piping with a wet cloth to prevent heat con-

duction during brazing.

Fig.10

Fig.11

Fig.12-1

Fig.13

Cut before 
heating

Cardboard

Indoor unit

Indoor unit

Insertion 
length L (mm)

Insulation for fitting (1)
(accessory)

Gas 
piping

Clamp (4) 

(accessory)

Insulation for fitting (2) 
(accessory)

Seal the 

holes

Indoor unit 
Outside

(2)  (1)

15 or more 
Inside

Liquid piping

Insulate the piping using the 
fitting insulation (field supply)

Insulation for fitting 

(field supply)

Tape
(field supply)

To outdoor unit

Copper 
pipe

Wrap with a wet cloth to 
prevent heat conduction.

Fig.12-2

90˚

Plug

[Unit:mm]

01_EN_3PR05311-2.fm  Page 10  Tuesday, June 2, 2009  4:39 PM

Summary of Contents for FDQ16PY1

Page 1: ...ODELS Duct Connection type FDQ16PY1 FDQ20PY1 FDQ16PYL FDQ20PYL READ THESE INSTRUCTIONS CAREFULLY BEFORE INSTALLATION KEEP THIS MANUAL IN A HANDY PLACE FOR FUTURE REFERENCE English 01_CV1_3PR05311 2 fm...

Page 2: ...ORE INSTALLATION 6 REPLACING FAN MOTOR PULLEY AND V BELT 8 INSTALLATION OF THE INDOOR UNIT 9 REFRIGERANT PIPING WORK 10 DRAIN PIPING WORK 11 INSTALLING THE DUCT 12 ELECTRIC WIRING WORK 12 FIELD SETTIN...

Page 3: ...ified installation work after taking into account strong winds typhoons or earthquakes Failure to do so during installation work may result in the unit falling and causing accidents Make sure that a s...

Page 4: ...cord and connecting wires at least 1 meter away from televisions or radios to prevent picture interference and noise Depending on the incoming signal strength a distance of 1 meter may not be suffici...

Page 5: ...NUAL FOR REMOTE CONTROLLER Indoor and outdoor unit combinations Do not use in any combination other than those shown below Refer to Fig 1 This unit cannot be connected with other standard indoor units...

Page 6: ...ut Are wiring and piping correct The unit may malfunction or the components burn out Is the unit safely grounded It may result in electric shock Is wiring size according to specifications The unit may...

Page 7: ...il or dust may be taken in Keep indoor unit outdoor unit power supply wiring and transmis sion wiring at least 1 meter away from televisions and radios This is to prevent image interference and noise...

Page 8: ...the air condi tioner and install it to the support plate After removing the control box please retighten the screws to their original posi tions When moving the control box do not apply force to the...

Page 9: ...ngs to reinforce the ceiling to bear the weight of the indoor unit 5 When adjusting air flow volume and external static pressure please change the motor pulley and V belt 665 296 349 1045 100 or more...

Page 10: ...al block 12 Install the new V belt f 13 Fasten the adjustment nuts b 1 2 3 Move the motor stand c so as to tighten the V belt f 14 Adjust the levelness of the fan pulley e and motor pulley g and the s...

Page 11: ...per and lower nuts to the suspension bolt 2 Adjust the unit to the preset height 3 Make sure that the unit is level Adjust the unit using a level gauge If it is installed unevenly water may leak from...

Page 12: ...heating the pipe cut the end of the plug in order to remove it Refer to Fig 10 After brazing these pipes as shown in Fig 11 use the fitting insulation to secure the pipe inside of the unit Refer to F...

Page 13: ...side The drain plug can be removed and placed on either the left or right side as well For best results try to keep the piping as short as possible Slant the piping at an angle to improve flow Refer t...

Page 14: ...attached to the remote controller All wiring must be performed by an authorized electrician A circuit breaker capable of shutting down power supply to the entire system must be installed The resistanc...

Page 15: ...iping completely Refer to Fig 12 2 Check that the wires are not trapped in the control box lid or service cover Do not clamp remote controller cords together with wires connecting the units together D...

Page 16: ...ansmission wiring ground the shield of the shield wire to at the grounding screw of the remote con troller cord grounding terminal inside the control box NOTE 1 Power wiring Fig 16 Fig 15 NOTE 2 3 Gro...

Page 17: ...ing impossible Over tightening may damage terminal screws See the table below for tightening torque for the terminal screws Precautions when connecting the ground terminal When connecting the ground w...

Page 18: ...explains FORCED OFF and ON OFF OPERATIONS in response to Input A 3 How to select FORCED OFF and ON OFF OPERATION See FIELD SETTING FORCED OFF ON OFF OPERATION Input ON stops operation impossible by re...

Page 19: ...manual of the outdoor unit The operation lamp of the remote controller will flash when an malfunction occurs Check the malfunction code on the liquid crys tal display to identify the point of trouble...

Page 20: ...0906 HT 3PR05311 2 EM09A005 01_CV1_3PR05311 2 fm Page 2 Thursday May 21 2009 2 30 PM...

Reviews: