14
English
<Precautions When Doing Wiring Work>
NOTE)
1. All wiring going into the control box should be passed through a plastic push.
2. Please fix the clamps at the internal and external sides (two at each side) of the control box.
3. Fix the power wires and the ground wires as illustrated.
4. Fix the branch wires and the remote controller wires as illustrated.
5. The specification for the fuses on the indoor unit PCB: 250V 5A (F1U)
6. If using shield wire for transmission wiring, ground the shield of the shield wire to “
”, at the grounding screw of the remote con-
troller cord grounding terminal inside the control box.
NOTE) 1.
Power wiring
Fig.16
Fig.15
NOTE) 2. 3.
Ground wire
NOTE) 2. 3.
NOTE) 2. 4.
Branch wire
NOTE) 2. 4.
Clamp
(accessory (4))
Remote controller wiring
Noiseless earth
Grounding terminal for
the remote controller
* Remote controller cord
(Shield wire NOTE 6)
* Do not clamp remote controller cords
together with wires connecting the units.
Doing so may cause malfunction.
Earth
screw
C-cup washer
Shield part
Ground the shield part of
shielded wire.
(Refer to NOTE 6)
01_EN_3PR05311-2.fm Page 14 Tuesday, June 2, 2009 4:39 PM