Troubleshooting
SiUS071735EB
85
Service Diagnosis
Note:
OL (Q1L) activating temperature: 130°C (266°F)
OL (Q1L) recovery temperature: 95°C (203°F)
High pressure switch (S1PH) activating pressure: 602 psi (4.15 MPa)
High pressure switch (S1PH) recovery pressure: 464 psi (3.2 MPa)
Note:
When replacing the defective thermistor(s), replace the thermistors as ASSY.