
SiUS071735EB
Main Functions
Functions and Control
20
1.4 Program Dry Operation
Outline
Program dry operation removes humidity while preventing the room temperature from lowering.
Since the microcomputer controls both the temperature and airflow rate, the temperature
adjustment and
FAN
setting buttons are inoperable.
Details
The microcomputer automatically sets the temperature and airflow rate. The difference between
the room thermistor temperature at start-up and the target temperature is divided into two zones.
Then, the unit operates in an appropriate capacity for each zone to maintain the temperature and
humidity at a comfortable level.
Room thermistor
temperature at start-up
Target temperature
X
Thermostat OFF point
Y
Thermostat ON point
Z
24.5°C or more
(76.1°F or more)
Room thermistor
temperature at start-up
X – 2.5°C
(X – 4.5°F)
X – 1.0°C
(X – 1.8°F)
16.5 ~ 24°C
(61.7 ~ 75.2°F)
X – 2.0°C
(X – 3.6°F)
X – 1.0°C
(X – 1.8°F)
16°C or less
(60.8°F or less)
16°C
(60.8°F)
X – 2.0°C
(X – 3.6°F)
X – 1.0°C = 15°C
(X – 1.8°F = 59°F)
Zone A = Thermostat OFF
Target temperature X
Zone B
Room temperature
Room temperature
Zone C = Thermostat ON
Y = X – 2.5
°
C (4.5
°
F)
or
Y = X – 2.0
°
C (3.6
°
F)
Z = X – 1.0
°
C (1.8
°
F)
X – 1.0
°
C (1.8
°
F)
(R24367)
Summary of Contents for FDMQ09RVJU
Page 12: ...SiUS071735EB 1 List of Functions Part 1 List of Functions 1 Functions 2 ...
Page 14: ...SiUS071735EB 3 Specifications Part 2 Specifications 1 Specifications 4 ...
Page 125: ...SiUS071735EB Check Service Diagnosis 114 15 18 24 class R25105 1 2 3 4 Multimeter ...
Page 127: ...SiUS071735EB Check Service Diagnosis 116 15 18 24 class R20704 W V U DC_P1 DC_N1 ...