SiUS071735EB
Control Specification
Functions and Control
40
2.10 Defrost Control
Outline
Defrosting is carried out by the cooling cycle (reverse cycle). The defrosting time or outdoor heat
exchanger temperature must be more than a certain value to finish defrosting.
Details
Conditions for Starting Defrost
The starting conditions are determined with the outdoor temperature and the outdoor heat
exchanger temperature.
The system is in heating operation.
The compressor operates for 6 minutes.
More than
A
minutes (depending on the duration of the previous defrost control) of accumulated
time have passed since the start of the operation, or ending the previous defrosting.
Conditions for Canceling Defrost
The judgment is made with the outdoor heat exchanger temperature (
B
).
09/12 class
15/18 class
24 class
A
(minute)
20 ~ 25
44
44
B
(°C)
2 ~ 20
6 ~ 12
6 ~ 12
(°F)
35.6 ~ 68.0
42.8 ~ 53.6
42.8 ~ 53.6
C
(Hz)
64
48
48
D
(Hz)
64
70
70
E
(seconds)
40
60
60
F
(seconds)
60
60
60
G
(seconds)
120 ~ 630
120 ~ 460
120 ~ 460
H
(seconds)
50
60
90
J
(seconds)
8
5
5
K
(pulse)
400
450
450
L
(pulse)
300
300 ~ 450
300 ~ 450
M
(pulse)
350
300
200
Frequency
Compressor
Four way valve
Fan
ON
OFF
ON
OFF
ON
OFF
0 Hz
0 Hz
C
Hz
D
Hz
J
sec.
PI control
8 sec.
H
sec.
(R21661)
E
sec.
F
sec.
G
sec.
L
pulse zone
Electronic
expansion valve
opening
Normal
control
K
pulse
zone
M
pulse
zone
Starting
control
Summary of Contents for FDMQ09RVJU
Page 12: ...SiUS071735EB 1 List of Functions Part 1 List of Functions 1 Functions 2 ...
Page 14: ...SiUS071735EB 3 Specifications Part 2 Specifications 1 Specifications 4 ...
Page 125: ...SiUS071735EB Check Service Diagnosis 114 15 18 24 class R25105 1 2 3 4 Multimeter ...
Page 127: ...SiUS071735EB Check Service Diagnosis 116 15 18 24 class R20704 W V U DC_P1 DC_N1 ...