Trial Operation
SiUS071735EB
121
Trial Operation and Field Settings
With Wired Remote Controller (BRC1E73)
1. Set to COOL or HEAT operation using the
remote controller.
2. Press and hold
Cancel
button for 4 seconds
or longer. Service settings menu is
displayed.
3. Select
in the service
settings menu, and press
Menu/OK
button.
Basic screen returns and “Test Operation”
is displayed at the bottom.
4. Press
On/Off
button within 10 seconds, and
the test operation starts.
Monitor the operation of the indoor unit for a
minimum of 10 minutes. During test
operation, the indoor unit will continue to
cool/heat regardless of the temperature
setpoint and room temperature.
In the case of above-mentioned
procedures 3 and 4 in reverse order, test
operation can start as well.
5. Press and hold
Cancel
button for 4 seconds
or longer in the basic screen.
Service settings menu is displayed.
6. Select
in the service
settings menu, and press
Menu/OK
button.
Basic screen returns and normal operation
is conducted.
Test operation will stop automatically
after 15 ~ 30 minutes. To stop the
operation, press
On/Off
button.
Test Operation
Test Operation
Basic screen
1.
2.
3.
4.
5.
Service Settings
menu screen
Press and hold Cancel
button for 4 seconds or
longer during backlight lit.
Press Menu/OK button.
Press On/Off button
(within 10 seconds).
6.
Basic screen
Press and hold Cancel
button for 4 seconds or
longer during backlight lit.
Press Menu/OK button.
Cool
Set to
68
F
Summary of Contents for FDMQ09RVJU
Page 12: ...SiUS071735EB 1 List of Functions Part 1 List of Functions 1 Functions 2 ...
Page 14: ...SiUS071735EB 3 Specifications Part 2 Specifications 1 Specifications 4 ...
Page 125: ...SiUS071735EB Check Service Diagnosis 114 15 18 24 class R25105 1 2 3 4 Multimeter ...
Page 127: ...SiUS071735EB Check Service Diagnosis 116 15 18 24 class R20704 W V U DC_P1 DC_N1 ...