SiUS071735EB
Service Diagnosis
Service Diagnosis
60
3.2 Wireless Remote Controller (BRC082A43)
Relations
Between Modes
The following modes can be selected by using
INSPECTION/TEST OPERATION
button on the
remote controller.
Service
Diagnosis
To find the error code, proceed as follows:
(R24049)
Press
INSPECTION/TEST
OPERATION
button for
more than 4 seconds.
Press
INSPECTION/TEST
OPERATION
button once.
Field
setting
mode
Service
mode
Normal
mode
Test
operation
mode
Inspection
mode
Press
INSPECTION/TEST
OPERATION
button once.
Press
INSPECTION/TEST
OPERATION
button for more
than 4 seconds.
Indoor unit settings can be made.
Filter cleaning sign time
Others
Following codes can be checked.
Error codes
Indoor model code
Service data can be obtained.
Error code history
Temperature data of various sections
Service settings can be made.
Forced fan ON
Airflow rate setting
Press
INSPECTION/
TEST OPERATION
button once.
Press
ON/OFF
button within 10 seconds
to start test operation.
Test operation will stop automatically
after 15~30 minutes.
Thermostat is forcibly turned on.
After 60
seconds
Press
INSPECTION/TEST
OPERATION
button once.
After 10 seconds without starting test operation
or press
INSPECTION/TEST OPERATION
button once
or 30 min. after the test operation start
Step
Action
1
Press
INSPECTION/TEST OPERATION
button to enter the inspection mode. Then the
figure
0
blinks on the UNIT No. display.
(R24050)
INSPECTION/TEST
OPERATION
button
Summary of Contents for FDMQ09RVJU
Page 12: ...SiUS071735EB 1 List of Functions Part 1 List of Functions 1 Functions 2 ...
Page 14: ...SiUS071735EB 3 Specifications Part 2 Specifications 1 Specifications 4 ...
Page 125: ...SiUS071735EB Check Service Diagnosis 114 15 18 24 class R25105 1 2 3 4 Multimeter ...
Page 127: ...SiUS071735EB Check Service Diagnosis 116 15 18 24 class R20704 W V U DC_P1 DC_N1 ...